APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

SCREEN NAME

Configuration

Service

Configuration

PASSWORD

POINT NAME

EDITABLE

RANGE

DEFAULT

NOTES

LEVEL

 

 

 

 

 

 

# of Fan Speeds

X

1,2,3

3

Used to set number of

 

fan motor speeds

 

 

 

 

 

 

 

 

 

 

When set to Fan On, G output is

 

 

 

 

 

energized when ever any fan speed

 

G Output Type

X

Fan On/Fan Low

Fan On

is active (required for ECM and Fan

 

control board). When set to Fan

 

 

 

 

 

 

 

 

 

 

Low, output is only energized for

 

 

 

 

 

Low Speed

 

Compressor Stages

X

One Stage/Two Stages

One Stage

Defines the number of

 

stages of compression

 

 

 

 

 

 

Reversing Valve Type

X

O type output/B type output

O type

Determines reversing valve

 

signal output type

 

 

 

 

 

 

Leaving Air Auxiliary

X

None/2-Position HW/1 Stage

None

Determines Auxiliary

 

Heat Type

Electric/Modulating HW

Reheat Coil Type

 

 

 

 

Entering Air Water

X

None/2-Position/Modulating

None

Determines Entering Air

 

Economizer Type

Economizer Coil Type

 

 

 

 

 

2-Position Water

X

Normally Closed/Normally Open

Normally

Determines type of 2-position

 

Valve Type

Closed

water valve used

 

 

 

 

Modulating Water

X

Normally Closed/Normally Open

Normally

Determines type of modulating

 

Valve Type

Closed

water valve used

 

 

 

 

Ventilation Damper

X

None/2-Position/DCV

None

Determines type of ventilation

 

Type

damper control to be used

 

 

 

 

 

 

 

 

 

Used to determine ventilation

 

Damper Actuator Type

X

(0-10 volt)/(2-10 volt)

0-10 volt

damper output signal range

 

 

 

 

 

(closed - open)

 

Humidity Sensor

X

None/Installed

None

Set to Installed if humidity

 

sensor is present

 

 

 

 

 

Admin Password

Factory Dehumidifica-

X

None/Installed

None

Set to Installed if factory-installed

level access only

tion Reheat Coil

dehumidification reheat coil

 

 

 

 

is present

 

 

 

 

 

 

Occupancy

X

Occupied Open/Occupied Closed

Occupied

Used to determine external occu-

 

Input Logic

CLOSED

pancy switch contact occupied state

 

 

 

 

Condensate Switch

X

5 - 600 seconds

10 sec

Delay before equipment alarms on

 

Alarm Delay

high condensate level

 

 

 

 

 

Condensate Switch

X

Alarm OPEN/Alarm CLOSED

Alarm

Determine Alarm state of

 

Alarm State

CLOSED

condensate switch input

 

 

 

 

Minimum Condenser

 

25 - 60 ° F

60 ° F

Determines the minimum

 

Water Temperature in

X

acceptable water loop temperature

 

Heating

 

 

 

to start heating

 

Maximum Condenser

 

65 - 100 ° F

90 ° F

Determines the maximum

 

Water Temperature in

X

acceptable water loop temperature

 

Heating

 

 

 

to start heating

 

Minimum Condenser

 

30 - 60 ° F

60 ° F

Determines the minimum

 

Water Temperature in

X

acceptable water loop temperature

 

Cooling

 

 

 

to start cooling

 

Maximum Condenser

 

85 - 120 ° F

95 ° F

Determines the maximum

 

Water Temperature in

X

acceptable water loop temperature

 

Cooling

 

 

 

to start cooling

 

IAQ sensor

X

0 - 5 ma

4 ma

Minimum output current (mA)

 

minimum input

for IAQ sensor

 

 

 

 

 

IAQ sensor

X

5 - 20 ma

20 ma

Maximum output current (mA) for

 

maximum input

IAQ sensor

 

 

 

 

 

IAQ sensor

X

0 - 9999 ppm

0 ppm

Corresponding value in ppm for

 

minimum output

minimum output current

 

 

 

 

 

IAQ sensor

X

0 - 9999 ppm

2000 ppm

Corresponding value in ppm for

 

maximum output

maximum output current

 

 

 

 

 

LEGEND

BAS

Building Automation System

DCV

Demand Controlled Ventilation

ECM

Electronically Commutated Motor

IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration

54

Image 54
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data Aquazone 50RTP03-20 Units Dimensions Outside Air Water CondensateIn/Out FPT Drain 03,04 12.57 x In/Out FPT 18.95 x 11/4 10,12 11/250RTP14,20 Unit Dimensions 14,20 18.95 xReturn Air Transition Supply Air Transition Exterior 78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25Install Condensate Drain 50 RTPConnect Electrical Wiring Water Quality GuidelinesElectrical Data FLA Hacr50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3800 39004000 50RTP10 Blower Performance Data 41004200 4500 43004400 460050RTP12 Blower Performance Data 50RTP14 Blower Performance Data 62006800 64006600 700050RTP20 Blower Performance Data 10,000 Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns OpenECR See legend and notes on 50RTP03-06 Units 50RTP08-20 UnitsHpwr A50-8557 Typical Control Wiring with Deluxe D and LON Controller SizesJ6J5 J1 J8AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Reversing Valve Fan 24Vac Hot 24Vac Com Connect Low Voltage WiringCompressor-Stage Deluxe DPRE-START-UP Complete C Control Jumper Settings SeeDeluxe D Control Jumper Settings See Field Selectable InputsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Operating LimitsUnit Start-Up with Wshp Open Controls BACview6 Display InterfacePage Units with Aquazone Complete C Control Antifreeze Percentages by VolumeOperation Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaReplacing the Wshp Open Controller’s Bat Refrigerant ChargingAir Coil Fan Motor Removal ’ to 4’Troubleshooting FP1 and FP2 Thermistor LocationReduced or no water flow TroubleshootingAir temperature out of range Overcharged with refrigerantUnit Does Not Operate Status Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Electronically Commutated MotorAlarm Page Page Copyright 2010 Carrier Corporation 50RTP START-UP Checklist II. START-UPAlong Dotted Line Heating Cycle AnalysisCooling Cycle Analysis Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New