Carrier 50RTP03-20 specifications Appendix a Wshp Screen Open Configuration, Service, Test

Page 53

APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

SCREEN NAME

PASSWORD

 

POINT NAME

EDITABLE

RANGE

DEFAULT

NOTES

LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto= Intermittant operation during both

 

 

 

 

 

 

 

 

occupied and unoccupied periods/

 

 

 

 

 

 

Auto/Continuous/

 

Continuous = Intermittant during unoccupied

 

 

 

 

Fan Mode

X

Continuous

periods and continuous during occupied

 

 

 

 

Always On

 

 

 

 

 

 

 

periods/Always on = fan operates

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continuously during both occupied and

 

 

 

 

 

 

 

 

unoccupied periods

 

 

 

 

Fan On Delay

X

0 - 30 sec

10 sec

Defines the delay time before the fan begins

 

 

 

 

to operate after heating or cooling is started

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defines the amount of time the fan will

 

 

 

 

Fan Off Delay

X

0 - 180 sec

45 sec

continue to operate after heating or

 

 

 

 

 

 

 

 

cooling is stopped

 

 

 

 

Heating Enable

X

Disable/Enable

Enable

Provides capability to manually

 

 

 

 

disable heating operation

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Enable

X

Disable/Enable

Enable

Provides capability to manually

 

 

 

 

disable cooling operation

 

 

 

 

 

 

 

 

 

 

 

 

Minimum SAT in

X

40 - 60 ° F

50 ° F

Defines the minimum acceptable operating

 

 

 

 

Cooling

temperature for the Supply Air

Configuration

 

 

 

 

 

 

 

Maximum SAT in

X

80 - 140 ° F

110 ° F

Defines the maximum acceptable operating

 

 

 

 

 

 

 

 

Heating

temperature for the Supply Air

 

Admin Password

 

 

 

 

 

 

 

 

 

 

Normally set to 100% if 2 position damper

 

 

level access only

 

Damper Ventilation

 

 

 

 

 

 

X

0 - 100%

100%

type or set to minimum ventilation position if

 

Unit

 

 

Position

 

 

 

 

 

 

damper type = DCV

Configuration

 

 

 

 

 

 

 

 

DCV Maximum Vent

X

0 - 100%

100%

Usually set at 100% - Used to limit maximum

 

 

 

 

 

 

 

 

Position

damper opening in DCV mode

 

 

 

 

 

 

 

 

 

 

 

Filter Alarm Timer

X

0 - 9999 hrs

0 hrs

Disables Filter Alarm if set to 0

 

 

 

 

Pushbutton Override

X

Disable/Enable

Enable

Enables Override Feature on Rnet sensor

 

 

 

 

SPT Sensor Set Point

X

Disable/Enable

Enable

Enables Set Point adjustment capability

 

 

 

 

Adjustment

on Rnet Sensor

 

 

 

 

 

 

 

 

 

 

 

Lockout Cooling if

 

-65 - 80 ° F

-65 ° F

Cooling is locked out when OAT is less than

 

 

 

 

X

configured value and OAT is actively being

 

 

 

 

OAT <

 

 

 

 

 

 

 

broadcast

 

 

 

 

 

 

 

 

 

 

 

 

Lockout Heating if

 

35 - 150 ° F

150 ° F

Heating is locked out when OAT is greater

 

 

 

 

X

than configured value and OAT is actively

 

 

 

 

OAT >

 

 

 

 

 

 

 

being broadcast

 

 

 

 

 

 

 

 

 

 

 

 

Power Fail Restart

X

0 - 600 sec

60 sec

Delay before equipment starts

 

 

 

 

Delay

 

 

 

 

 

 

 

 

 

 

 

 

Occupancy Schedules

X

Disable/Enable

Enable

Enables unit occupied

 

 

 

 

Set Point Separation

X

2 - 9 ° F

4 ° F

Used to enforce minimum

 

 

 

 

set point separation

 

 

 

 

 

 

 

 

 

 

 

 

Test Mode

X

Disable/Enable

Disable

Used to enable test mode. Will automatically

 

 

 

 

reset to disable after 1 hour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used to test all fan speeds. Sequences fan

 

 

 

 

Fan Test

X

Disable/Enable

Disable

from low to high and operates each speed for

 

 

 

 

 

 

 

 

1 minute. Resets to disable on completion

 

 

 

 

Fan Speed

 

Off/Low Speed/Medium

 

Displays current fan operation

 

 

 

 

 

Speed/High Speed/On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used to test compressor cooling and heating

 

 

 

 

 

 

 

 

operation. Sequences cooling stage 1, then

 

 

 

 

Compressor Test

X

Disable/Enable

Disable

stage 2, then heating stage 2 and reduces

 

 

 

 

 

 

 

 

capacity to stage 1. Operates for 1 minute per

 

 

 

 

 

 

 

 

step. Resets to disable on completion.

Configuration

 

 

 

 

 

 

Used to test dehumification mode -

 

 

 

Dehumidification Test

X

Disable/Enable

Disable

Operates for 2 minutes. Resets to

 

 

 

 

 

 

 

disable on completion.

 

 

 

 

 

 

 

 

 

 

Admin Password

 

 

 

Inactive/Heating/Cooling/

 

 

 

Service

 

Testing Compressor

 

Dehumidify/TimeGard

 

Displays compressor test mode

 

level access only

 

 

 

 

 

 

 

 

Wait

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used to test auxiliary heat.

 

 

 

 

Aux Heating Test

X

Disable/Enable

Disable

Sequences fan on and enables

 

Test

 

 

heating coil for 1 minute. Resets to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disable on completion

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used to test entering/return air water loop

 

 

 

 

H2O Economizer Test

X

Disable/Enable

Disable

economizer coil operation. Sequences fan on

 

 

 

 

and opens economizer coil water valve for 1

 

 

 

 

 

 

 

 

minute. Resets to disable on completion

 

 

 

 

Preposition OA

X

Disable/Enable

Disable

Used to preposition OA damper

 

 

 

 

Damper

actuator to set proper preload

 

 

 

 

 

 

 

 

 

 

 

Open Vent

X

Disable/Enable

Disable

Used to test OA damper operation

 

 

 

 

Damper 100%

 

 

 

 

 

 

 

 

 

 

 

 

SAT

 

° F

 

Displays SAT

 

 

 

 

LCWT

 

° F

 

Displays Leaving Condenser

 

 

 

 

 

 

Water Temperature

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

BAS — Building Automation System

 

 

 

 

DCV — Demand Controlled Ventilation

 

 

 

 

ECM

Electronically Commutated Motor

 

 

 

 

IAQ

Indoor Air Quality

 

 

 

 

 

OAT

Outdoor Air Temperature

 

 

 

 

 

RH

Relative Humidity

 

 

 

 

 

SAT — Supply Air Temperature

 

 

 

 

 

SPT

Space Temperature

 

 

 

 

 

TPI

Third Party Integration

 

 

 

 

 

53

Image 53
Contents Safety Considerations ContentsGeneral InstallationPhysical Data Aquazone 50RTP03-20 Units In/Out FPT Drain 03,04 12.57 x DimensionsOutside Air Water Condensate 18.95 x 11/4 10,12 11/2 In/Out FPT14,20 18.95 x 50RTP14,20 Unit Dimensions78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25 Return Air Transition Supply Air Transition Exterior50 RTP Install Condensate DrainWater Quality Guidelines Connect Electrical WiringFLA Hacr Electrical Data50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 4000 38003900 4200 50RTP10 Blower Performance Data4100 4400 43004500 460050RTP12 Blower Performance Data 6200 50RTP14 Blower Performance Data6600 64006800 700050RTP20 Blower Performance Data Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns Open 10,000ECR See legend and notes on 50RTP08-20 Units 50RTP03-06 UnitsHpwr A50-8557 Sizes Typical Control Wiring with Deluxe D and LON ControllerAL1 J6J5J1 J8 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Compressor-Stage Connect Low Voltage WiringReversing Valve Fan 24Vac Hot 24Vac Com Deluxe DDeluxe D Control Jumper Settings See Complete C Control Jumper Settings SeePRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeSTART-UP Operating LimitsBACview6 Display Interface Unit Start-Up with Wshp Open ControlsPage Operation Antifreeze Percentages by VolumeUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceAir Coil Fan Motor Removal Refrigerant ChargingReplacing the Wshp Open Controller’s Bat ’ to 4’FP1 and FP2 Thermistor Location TroubleshootingAir temperature out of range TroubleshootingReduced or no water flow Overcharged with refrigerantUnit Does Not Operate Alarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Test Appendix a Wshp Screen Open ConfigurationService Electronically Commutated Motor Configuration ServiceAlarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50RTP START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisAlong Dotted Line Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New