Carrier 50RTP03-20 specifications 6400, 6600, 6800, 7000

Page 21

Table 11 — 50RTP14 Blower Performance Data (cont)

AIRFLOW

ESP

 

 

 

 

 

AIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

(cfm)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2.0

 

 

bhp

1.43

1.54

1.66

1.78

1.90

2.05

2.21

2.37

2.52

2.62

2.73

2.83

2.95

3.13

3.28

3.47

3.65

3.76

3.87

3.97

4.08

6400

Sheave/Motor

B

B

B

B

A

A

A

A

A

A

A

C

C

E

E

E

E

E

E

E

E

rpm

571

604

636

664

696

724

752

780

808

832

856

880

904

928

948

972

996

1016

1036

1056

1076

 

 

Turns Open

5.5

4.5

3.5

2.5

5.5

4.5

4.0

3.0

2.5

1.5

1.0

5.5

5.0

4.5

4.0

3.5

3.0

2.5

2.0

1.5

1.0

 

bhp

1.55

1.68

1.83

1.96

2.12

2.24

2.36

2.47

2.61

2.74

3.00

3.01

3.17

3.34

3.48

3.66

3.82

3.94

4.06

4.16

4.28

6600

Sheave/Motor

B

B

B

A

A

A

A

A

A

A

D

E

E

E

E

E

E

E

E

E

E

rpm

583

616

648

676

708

736

764

788

816

840

864

888

912

936

956

980

1004

1024

1044

1060

1080

 

 

Turns Open

5.0

4.0

3.0

6.0

5.0

4.0

3.5

3.0

2.0

1.5

1.0

5.0

4.5

4.0

3.5

3.0

2.5

2.5

2.0

1.5

1.0

 

bhp

1.68

1.80

1.94

2.08

2.23

2.37

2.52

2.68

2.79

3.00

3.07

3.10

3.28

3.47

3.63

3.82

3.97

4.11

4.25

4.38

4.52

6800

Sheave/Motor

B

B

B

A

A

A

A

A

A

D

D

E

E

E

E

E

E

E

E

E

E

rpm

600

628

660

692

720

744

772

800

824

848

872

896

920

944

964

988

1008

1028

1048

1068

1088

 

 

Turns Open

4.5

3.5

2.5

5.5

4.5

4.0

3.0

2.5

2.0

1.0

1.0

5.0

4.5

4.0

3.5

3.0

2.5

2.0

1.5

1.5

1.0

 

bhp

1.79

1.97

2.12

2.3

2.4

2.53

2.65

2.76

2.9

3.10

3.17

3.31

3.50

3.66

3.86

4.05

4.18

4.31

4.44

4.57

4.69

7000

Sheave/Motor

B

B

A

A

A

A

A

A

A

D

E

E

E

E

E

E

E

E

E

E

E

rpm

612

644

672

704

728

756

784

808

832

856

880

904

928

948

972

996

1016

1036

1056

1076

1096

 

 

Turns Open

4.0

3.0

6.0

5.0

4.5

3.5

3.0

2.5

1.5

1.0

5.5

5.0

4.5

4.0

3.5

3.0

2.5

2.0

1.5

1.0

1.0

LEGEND

bhp — Brake Horsepower ESP — External Static Pressure

NOTES:

1.A = Standard RPM/Standard Motor, B = Low RPM/Standard Motor, C = High RPM/Standard Motor, D = Standard RPM/ Large Motor, E = High RPM/Large Motor

2.Unit shipped with standard drive package with drive sheave 2.5 turns open unless otherwise requested. Field adjustment may be required for specified CFM.

3.ISO/AHRI rating point with standard drive package and drive sheave open 3.0 turns at .30 ESP.

4.Performance data does not include drive losses and is based on sea level conditions.

5.All airflow is rated at lowest voltage if unit is dual rated, i.e., rated at 208 volts for 208-230 volt units.

21

Image 21
Contents Safety Considerations ContentsGeneral InstallationPhysical Data Aquazone 50RTP03-20 Units Dimensions Outside Air Water CondensateIn/Out FPT Drain 03,04 12.57 x 18.95 x 11/4 10,12 11/2 In/Out FPT14,20 18.95 x 50RTP14,20 Unit Dimensions78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25 Return Air Transition Supply Air Transition Exterior50 RTP Install Condensate DrainWater Quality Guidelines Connect Electrical WiringFLA Hacr Electrical Data50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3800 39004000 50RTP10 Blower Performance Data 41004200 4400 43004500 460050RTP12 Blower Performance Data 6200 50RTP14 Blower Performance Data6600 64006800 700050RTP20 Blower Performance Data Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns Open 10,000ECR See legend and notes on 50RTP08-20 Units 50RTP03-06 UnitsHpwr A50-8557 Sizes Typical Control Wiring with Deluxe D and LON ControllerJ6J5 J1 J8AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Compressor-Stage Connect Low Voltage WiringReversing Valve Fan 24Vac Hot 24Vac Com Deluxe DDeluxe D Control Jumper Settings See Complete C Control Jumper Settings SeePRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeSTART-UP Operating LimitsBACview6 Display Interface Unit Start-Up with Wshp Open ControlsPage Operation Antifreeze Percentages by VolumeUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceAir Coil Fan Motor Removal Refrigerant ChargingReplacing the Wshp Open Controller’s Bat ’ to 4’FP1 and FP2 Thermistor Location TroubleshootingAir temperature out of range TroubleshootingReduced or no water flow Overcharged with refrigerantUnit Does Not Operate Alarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Electronically Commutated Motor Configuration ServiceAlarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50RTP START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisAlong Dotted Line Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New