Carrier 50RTP03-20 specifications 4300, 4400, 4500, 4600, 4700, 4800, 4900, 5000

Page 18

Table 9 — 50RTP10 Blower Performance Data (cont)

AIRFLOW

ESP

 

 

 

 

 

AIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

(cfm)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2.0

 

 

bhp

1.76

1.84

1.93

2.00

2.08

2.17

2.25

2.34

2.42

2.50

2.60

2.70

2.80

2.90

3.00

3.10

3.16

3.24

3.31

3.39

3.45

4300

Sheave/Motor

A

A

A

A

A

A

A

A

C

C

C

C

C

C

E

E

E

E

E

E

E

rpm

776

800

824

844

868

892

912

936

956

976

1000

1020

1040

1060

1080

1100

1116

1136

1152

1172

1188

 

 

Turns Open

4.5

4.0

3.5

3.0

2.5

2.0

1.5

1.0

5.0

4.5

4.0

4.0

3.5

3.0

3.0

2.5

2.0

2.0

1.5

1.0

1.0

 

bhp

1.86

1.95

2.04

2.12

2.22

2.32

2.4

2.48

2.57

2.65

2.74

2.84

3.00

3.04

3.14

3.23

3.30

3.38

3.44

3.52

3.58

4400

Sheave/Motor

A

A

A

A

A

A

A

A

C

C

C

C

E

E

E

E

E

E

E

E

E

rpm

788

812

836

856

880

904

924

944

968

988

1008

1028

1048

1068

1088

1108

1124

1144

1160

1180

1196

 

 

Turns Open

4.5

4.0

3.5

3.0

2.5

2.0

1.5

1.0

4.5

4.5

4.0

3.5

3.5

3.0

2.5

2.5

2.0

1.5

1.5

1.0

1.0

 

bhp

1.96

2.06

2.15

2.23

2.33

2.43

2.52

2.61

2.69

2.78

2.88

3.00

3.08

3.18

3.28

3.35

3.44

3.53

3.61

3.70

4500

Sheave/Motor

A

A

A

A

A

A

A

C

C

C

C

E

E

E

E

E

E

E

E

E

rpm

800

824

848

868

892

916

936

956

976

996

1016

1036

1056

1076

1096

1112

1132

1152

1168

1188

 

 

Turns Open

4.0

3.5

3.0

2.5

2.0

1.5

1.0

5.0

4.5

4.0

4.0

3.5

3.0

3.0

2.5

2.0

2.0

1.5

1.5

1.0

 

bhp

2.12

2.20

2.30

2.38

2.47

2.56

2.64

2.73

2.83

2.92

3.00

3.10

3.20

3.30

3.40

3.49

3.60

3.68

3.79

3.88

4600

Sheave/Motor

A

A

A

A

A

A

A

C

C

C

E

E

E

E

E

E

E

E

E

E

rpm

820

840

864

884

908

928

948

968

992

1012

1028

1048

1068

1088

1108

1124

1144

1160

1180

1196

 

 

Turns Open

3.5

3.0

3.0

2.5

2.0

1.5

1.0

4.5

4.5

4.0

3.5

3.5

3.0

2.5

2.5

2.0

1.5

1.5

1.0

1.0

 

bhp

2.23

2.31

2.40

2.50

2.59

2.68

2.76

2.85

3.00

3.04

3.14

3.24

3.34

3.42

3.53

3.62

3.73

3.84

3.93

4700

Sheave/Motor

A

A

A

A

A

A

C

C

E

E

E

E

E

E

E

E

E

E

E

rpm

832

852

876

900

920

940

960

980

1000

1020

1040

1060

1080

1096

1116

1132

1152

1172

1188

 

 

Turns Open

3.5

3.0

2.5

2.0

1.5

1.0

5.0

4.5

4.0

4.0

3.5

3.0

3.0

2.5

2.0

2.0

1.5

1.0

1.0

 

bhp

2.35

2.46

2.55

2.65

2.73

2.81

2.89

3.00

3.06

3.16

3.26

3.34

3.44

3.55

3.64

3.76

3.86

3.98

4.08

4800

Sheave/Motor

A

A

A

A

A

C

C

E

E

E

E

E

E

E

E

E

E

E

E

rpm

844

868

888

912

932

952

972

992

1012

1032

1052

1068

1088

1108

1124

1144

1160

1180

1196

 

 

Turns Open

3.0

2.5

2.0

1.5

1.5

5.0

4.5

4.5

4.0

3.5

3.5

3.0

2.5

2.5

2.0

1.5

1.5

1.0

1.0

 

bhp

2.49

2.58

2.68

2.77

2.85

3.00

3.03

3.12

3.22

3.30

3.40

3.50

3.60

3.70

3.82

3.91

4.03

4.13

4900

Sheave/Motor

A

A

A

A

A

E

E

E

E

E

E

E

E

E

E

E

E

E

rpm

860

880

904

924

944

964

984

1004

1024

1040

1060

1080

1100

1116

1136

1152

1172

1188

 

 

Turns Open

3.0

2.5

2.0

1.5

1.0

5.0

4.5

4.0

3.5

3.5

3.0

3.0

2.5

2.0

2.0

1.5

1.0

1.0

 

bhp

2.63

2.72

2.81

2.91

3.00

3.09

3.18

3.28

3.36

3.46

3.56

3.66

3.75

3.87

3.96

4.08

4.18

4.28

5000

Sheave/Motor

A

A

A

A

E

E

E

E

E

E

E

E

E

E

E

E

E

E

rpm

876

896

916

936

956

976

996

1016

1032

1052

1072

1092

1108

1128

1144

1164

1180

1196

 

 

Turns Open

2.5

2.0

1.5

1.0

5.0

4.5

4.0

4.0

3.5

3.5

3.0

2.5

2.5

2.0

1.5

1.5

1.0

1.0

LEGEND

bhp — Brake Horsepower ESP — External Static Pressure

NOTES:

1.A = Standard RPM/Standard Motor, B = Low RPM/Standard Motor, C = High RPM/Standard Motor, E = High RPM/Large Motor

2.Unit shipped with standard drive package with drive sheave 2.5 turns open unless otherwise requested. Field adjustment may be required for specified CFM.

3.ISO/AHRI rating point with standard drive package and drive sheave open 3.0 turns at .30 ESP.

4.Performance data does not include drive losses and is based on sea level conditions.

5.All airflow is rated at lowest voltage if unit is dual rated, i.e., rated at 208 volts for 208-230 volt units.

18

Image 18
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data Aquazone 50RTP03-20 Units Dimensions Outside Air Water CondensateIn/Out FPT Drain 03,04 12.57 x In/Out FPT 18.95 x 11/4 10,12 11/250RTP14,20 Unit Dimensions 14,20 18.95 xReturn Air Transition Supply Air Transition Exterior 78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25Install Condensate Drain 50 RTPConnect Electrical Wiring Water Quality GuidelinesElectrical Data FLA Hacr50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3800 39004000 50RTP10 Blower Performance Data 41004200 4500 43004400 460050RTP12 Blower Performance Data 50RTP14 Blower Performance Data 62006800 64006600 700050RTP20 Blower Performance Data 10,000 Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns OpenECR See legend and notes on 50RTP03-06 Units 50RTP08-20 UnitsHpwr A50-8557 Typical Control Wiring with Deluxe D and LON Controller SizesJ6J5 J1 J8AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Reversing Valve Fan 24Vac Hot 24Vac Com Connect Low Voltage WiringCompressor-Stage Deluxe DPRE-START-UP Complete C Control Jumper Settings SeeDeluxe D Control Jumper Settings See Field Selectable InputsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Operating LimitsUnit Start-Up with Wshp Open Controls BACview6 Display InterfacePage Units with Aquazone Complete C Control Antifreeze Percentages by VolumeOperation Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaReplacing the Wshp Open Controller’s Bat Refrigerant ChargingAir Coil Fan Motor Removal ’ to 4’Troubleshooting FP1 and FP2 Thermistor LocationReduced or no water flow TroubleshootingAir temperature out of range Overcharged with refrigerantUnit Does Not Operate Status Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Electronically Commutated MotorAlarm Page Page Copyright 2010 Carrier Corporation 50RTP START-UP Checklist II. START-UPAlong Dotted Line Heating Cycle AnalysisCooling Cycle Analysis Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New