Carrier 50RTP03-20 specifications 50RTP05 Blower Performance Data

Page 13

Table 6 — 50RTP05 Blower Performance Data

AIRFLOW

ESP

 

 

 

 

AIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

(cfm)

0.0

0.1

0.2

0.3

 

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

 

1.2

1.3

1.4

1.5

 

 

 

 

bhp

0.17

0.22

0.26

0.29

 

0.31

0.34

0.37

0.40

0.44

0.47

0.5

0.53

 

0.56

0.60

0.63

0.65

1500

Sheave/Motor

B

B

B

B

 

A

A

A

A

A

A

A

A

 

A

C

C

C

rpm

516

573

625

670

 

710

755

785

820

850

880

900

925

 

945

970

990

1010

 

 

 

 

Turns Open

5.0

4.5

3.5

2.5

 

4.5

4.0

3.5

3.0

2.0

1.5

1.5

1.0

 

0.5

3.0

2.5

2.5

 

bhp

0.20

0.24

0.28

0.32

 

0.35

0.38

0.41

0.45

0.48

0.52

0.55

0.58

 

0.62

0.65

0.68

0.70

1600

Sheave/Motor

B

B

B

A

 

A

A

A

A

A

A

A

A

 

C

C

C

C

rpm

526

583

635

680

 

725

765

795

830

860

890

915

940

 

965

990

1010

1030

 

 

 

 

Turns Open

5.0

4.5

3.5

5.0

 

4.5

3.5

3.0

2.5

2.0

1.5

1.0

0.5

 

3.0

2.5

2.5

2.0

 

bhp

0.23

0.26

0.30

0.34

 

0.38

0.42

0.45

0.49

0.53

0.56

0.60

0.64

 

0.67

0.71

0.73

0.75

1700

Sheave/Motor

B

B

B

A

 

A

A

A

A

A

A

A

A

 

C

C

C

C

rpm

536

589

640

685

 

730

770

805

840

875

900

930

955

 

980

1005

1025

1045

 

 

 

 

Turns Open

4.5

4.0

3.0

5.0

 

4.0

3.5

3.0

2.5

2.0

1.5

1.0

0.5

 

3.0

2.5

2.0

2.0

 

bhp

0.25

0.29

0.33

0.37

 

0.41

0.46

0.50

0.54

0.58

0.62

0.65

0.68

 

0.72

0.76

0.78

0.81

1800

Sheave/Motor

B

B

B

A

 

A

A

A

A

A

A

A

C

 

C

C

C

C

rpm

547

599

650

695

 

740

780

815

855

885

915

940

965

 

995

1020

1040

1060

 

 

 

 

Turns Open

4.5

4.0

3.0

4.5

 

4.0

3.5

2.5

2.0

1.5

1.0

0.5

3.0

 

2.5

2.0

2.0

1.5

 

bhp

0.29

0.32

0.37

0.41

 

0.46

0.50

0.55

0.59

0.62

0.66

0.70

0.73

 

0.77

0.81

0.85

0.88

1900

Sheave/Motor

B

B

B

A

 

A

A

A

A

A

A

A

C

 

C

C

C

C

rpm

568

620

665

710

 

755

790

830

865

895

925

955

985

 

1015

1035

1060

1080

 

 

 

 

Turns Open

4.5

3.5

3.0

4.5

 

3.5

3.0

2.5

2.0

1.5

1.0

0.5

2.5

 

2.0

2.0

1.5

1.0

 

bhp

0.33

0.36

0.42

0.47

 

0.52

0.57

0.61

0.66

0.69

0.73

0.77

0.81

 

0.85

0.89

0.92

0.96

2000

Sheave/Motor

B

B

A

A

 

A

A

A

A

A

A

C

C

 

C

C

C

C

rpm

589

635

680

725

 

765

805

845

880

910

940

975

1005

 

1030

1055

1075

1100

 

 

 

 

Turns Open

4.0

3.5

5.0

4.0

 

3.5

3.0

2.0

1.5

1.0

0.5

3.0

2.5

 

2.0

1.5

1.5

1.0

 

bhp

0.41

0.45

0.49

0.52

 

0.57

0.63

0.68

0.72

0.76

0.80

0.84

0.88

 

0.92

0.96

1.00

1.04

2100

Sheave/Motor

B

B

A

A

 

A

A

A

A

A

A

C

C

 

C

C

E

E

rpm

615

660

700

740

 

780

820

860

895

925

960

990

1020

 

1045

1070

1095

1120

 

 

 

 

Turns Open

3.5

3.0

4.5

4.0

 

3.0

2.5

2.0

1.5

1.0

0.5

2.5

2.0

 

2.0

1.5

1.0

0.5

 

bhp

0.44

0.49

0.54

0.58

 

0.64

0.69

0.74

0.78

0.83

0.87

0.91

0.96

 

1.00

1.04

1.08

1.12

2200

Sheave/Motor

B

A

A

A

 

A

A

A

A

A

C

C

C

 

E

E

E

E

rpm

640

680

720

760

 

800

840

880

910

945

975

1005

1035

 

1060

1085

1115

1135

 

 

 

 

Turns Open

3.0

5.0

4.5

3.5

 

3.0

2.5

1.5

1.0

0.5

3.0

2.5

2.0

 

1.5

1.5

1.0

0.5

 

bhp

0.52

0.56

0.60

0.65

 

0.70

0.75

0.80

0.85

0.89

0.94

1.00

1.05

 

1.11

1.16

1.22

1.25

2300

Sheave/Motor

B

A

A

A

 

A

A

A

A

C

C

E

E

 

E

E

E

E

rpm

665

705

745

785

 

825

860

895

930

960

995

1025

1050

 

1080

1105

1135

1155

 

 

 

 

Turns Open

3.0

4.5

4.0

3.5

 

2.5

2.0

1.5

0.5

3.0

2.5

2.0

2.0

 

1.5

1.0

0.5

0.5

 

bhp

0.57

0.62

0.67

0.73

 

0.79

0.84

0.89

1.00

1.00

1.03

1.08

1.14

 

1.20

1.26

1.30

1.35

2400

Sheave/Motor

A

A

A

A

 

A

A

A

D

D

E

E

E

 

E

E

E

E

rpm

695

735

775

810

 

850

885

920

950

980

1015

1040

1070

 

1100

1130

1150

1175

 

 

 

 

Turns Open

5.0

4.0

3.5

3.0

 

2.0

1.5

1.0

0.5

0.0

2.0

2.0

1.5

 

1.0

0.5

0.5

0.0

 

bhp

0.64

0.69

0.75

0.81

 

0.87

0.92

1.00

1.01

1.05

1.11

1.17

1.23

 

1.29

1.34

1.39

1.43

2500

Sheave/Motor

A

A

A

A

 

A

A

D

D

E

E

E

E

 

E

E

E

E

rpm

725

765

800

835

 

870

905

940

970

1000

1030

1060

1090

 

1120

1145

1170

1190

 

 

 

 

Turns Open

4.5

3.5

3.0

2.5

 

2.0

1.5

0.5

0.0

2.5

2.0

1.5

1.0

 

0.5

0.5

0.0

0.0

LEGEND

bhp — Brake Horsepower ESP — External Static Pressure

NOTES:

1.A = Standard RPM/Standard Motor, B = Low RPM/Standard Motor, C = High RPM/Standard Motor, D = Standard RPM/ Large Motor, E = High RPM/Large Motor

2.Unit shipped with standard drive package with drive sheave 2.5 turns open unless otherwise requested. Field adjustment may be required for specified CFM.

3.ISO/AHRI rating point with standard drive package and drive sheave open 3.0 turns at .30 ESP.

4.Performance data does not include drive losses and is based on sea level conditions.

5.All airflow is rated at lowest voltage if unit is dual rated, i.e., rated at 208 volts for 208-230 volt units.

13

Image 13
Contents Safety Considerations ContentsGeneral InstallationPhysical Data Aquazone 50RTP03-20 Units Outside Air Water Condensate DimensionsIn/Out FPT Drain 03,04 12.57 x 18.95 x 11/4 10,12 11/2 In/Out FPT14,20 18.95 x 50RTP14,20 Unit Dimensions78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25 Return Air Transition Supply Air Transition Exterior50 RTP Install Condensate DrainWater Quality Guidelines Connect Electrical WiringFLA Hacr Electrical Data50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3900 38004000 4100 50RTP10 Blower Performance Data4200 4400 43004500 460050RTP12 Blower Performance Data 6200 50RTP14 Blower Performance Data6600 64006800 700050RTP20 Blower Performance Data Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns Open 10,000ECR See legend and notes on 50RTP08-20 Units 50RTP03-06 UnitsHpwr A50-8557 Sizes Typical Control Wiring with Deluxe D and LON ControllerJ1 J8 J6J5AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Compressor-Stage Connect Low Voltage WiringReversing Valve Fan 24Vac Hot 24Vac Com Deluxe DDeluxe D Control Jumper Settings See Complete C Control Jumper Settings SeePRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeSTART-UP Operating LimitsBACview6 Display Interface Unit Start-Up with Wshp Open ControlsPage Operation Antifreeze Percentages by VolumeUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceAir Coil Fan Motor Removal Refrigerant ChargingReplacing the Wshp Open Controller’s Bat ’ to 4’FP1 and FP2 Thermistor Location TroubleshootingAir temperature out of range TroubleshootingReduced or no water flow Overcharged with refrigerantUnit Does Not Operate Alarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Electronically Commutated Motor Configuration ServiceAlarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50RTP START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisAlong Dotted Line Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New