CAUTION
DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com- plete the procedures listed below:
1.Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2.Verify that the unit is the correct model for the entering water temperature of the job.
3.Do not remove the packaging until the unit is ready for installation.
4.Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
5.Inspect all electrical connections. Be sure connections are clean and tight at the terminals.
6.Compressors are internally
7.Remove any blower support cardboard from inlet of the blower if present.
8.Locate and verify any accessory kit located in compressor section.
9.Remove any access panel screws that may be difficult to remove once unit is installed.
Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for WSHP. Re- fer to Fig.
•Provide sufficient space for water, electrical and duct connections
•Locate unit in an area that allows for easy access and removal of filter and access panels
•Allow enough space for service personnel to perform maintenance
Table 1 — Physical Data — Aquazone™ 50RTP03-20 Units
UNIT 50RTP | 03 |
| 04 |
| 05 |
| 06 |
| 08 |
| 10 |
| 12 |
| 14 |
| 20 |
Compressor (qty) |
|
|
| Scroll (1) |
|
|
|
|
|
|
| Scroll (2) |
|
|
|
| |
Factory Charge | 64 |
| 84 |
| 120 |
| 132 |
| 108 |
| 120 |
| 130 |
| 192 |
| 300 |
Blower Motor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Motor Quantity |
|
|
|
|
|
|
| 1 |
|
|
|
|
|
|
|
| |
Standard Motor (hp) | 1 |
| 1 |
| 1 |
| 1.5 |
| 2 |
| 3 |
| 3 |
| 3 |
| 5 |
Large Motor (hp) | N/A |
| 1.5 |
| 1.5 |
| 2 |
| 3 |
| 5 |
| 5 |
| 5 |
| 7.5 |
Blower(s) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Number of Blowers |
|
|
|
|
| 1 |
|
|
|
|
|
|
|
| 2 | ||
Blower Wheel Size (dia x w) | 10 x 6 |
|
|
| 2 x 12 |
| 15 x 11 |
| 15 x 15 |
|
| 15 x 11 | |||||
A29 |
| A30 |
| A32 |
| AX33 |
| B40 |
| BX42 |
| BX46 |
| B39 |
| BX40 | |
Water Connection Size |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IPT (in.) | 3/4 |
|
| 1 |
| 11/4 |
|
| 11/2 |
|
|
|
| 2 | |||
Coax Volume |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Volume (US Gallons) | 0.61 |
| 0.77 |
| 1.11 |
| 1.30 |
| 1.69 |
| 2.29 |
| 2.68 |
| 3.83 |
| 4.77 |
|
|
|
|
|
|
|
| ||||||||||
Condensate Connection Size |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FPT (in.) |
|
|
|
|
|
|
| 1 |
|
|
|
|
|
|
|
| |
Air Coil Data |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air Coil Total Face Area (sq ft) | 5 |
|
|
| 7 |
| 9.33 |
|
| 10.5 |
|
| 20 | ||||
Filter, Standard, Qty...Size (in.) |
|
| 4...16 x 20 |
|
|
|
|
| 6...16 x 20 |
| 8...16 x 20, | ||||||
|
|
|
|
|
|
|
| 2...20 x 20 | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Operating Weight (lb) | 735 |
| 785 |
| 835 |
| 880 |
| 1080 |
| 1125 |
| 1175 |
| 1770 |
| 1960 |
Shipping Weight (lb) | 750 |
| 800 |
| 850 |
| 900 |
| 1100 |
| 1150 |
| 1200 |
| 1800 |
| 2000 |
Corner Weights (lb) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
184 |
| 196 |
| 208.5 |
| 224 |
| 292 |
| 303.5 |
| 320 |
| 479 |
| 530 | |
259 |
| 276 |
| 293.5 |
| 298 |
| 380 |
| 395.5 |
| 406 |
| 623 |
| 690 | |
108.5 |
| 117 |
| 124.5 |
| 134 |
| 193 |
| 202 |
| 212.5 |
| 315 |
| 350 | |
183.5 |
| 196 |
| 208.5 |
| 224 |
| 215 |
| 224 |
| 236.5 |
| 353 |
| 390 | |
Curb, Installed (lb) |
|
|
| 83 |
|
|
|
| 94 |
|
|
|
| 128 | |||
IPT — Iron (National) Pipe Thread |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3