e.Enter ON/OFF time, then press continue.

f.Press OK to apply and save to a particular day of the week.

g.Continue to add the same or different schedule spe- cific days of the week.

To add exceptions to the schedule:

i.Press Add softkey.

ii.Select exception type from following:

Date

Date Range

Week-N-Day

Calender Reference

9.Go back to Home Screen.

10.Remove BACview6 cable from SPT sensor by reversing the process in Step 1.

11.Perform system test.

Flow Regulation — Flow regulation can be accom- plished by two methods. Most water control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger, the flow rate can be deter- mined. Adjust the water control valve until the flow of 1.5 to 2 gpm is achieved. Since the pressure constantly varies, two pressure gages may be needed in some applications.

An alternative method is to install a flow control device. These devices are typically an orifice of plastic material de- signed to allow a specified flow rate that are mounted on the outlet of the water control valve. Occasionally these valves produce a velocity noise that can be reduced by applying some back pressure. To accomplish this, slightly close the leaving isolation valve of the well water setup.

WARNING

Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon- nect locations to alert others not to restore power until flushing is completed.

System Cleaning and Flushing — Cleaning and flushing the unit is the single most important step to ensure proper start-up and continued efficient operation of the system. Follow the instructions below to properly clean and flush the system:

1.Verify that electrical power to the units is disconnected.

2.Install the system with the supply hose connected directly to the return riser valve. Use a single length of flexible hose.

3.Open all air vents. Fill the system with water. Do not al- low system to overflow. Bleed all air from the system. Check the system for leaks and repair appropriately.

4.Verify that all strainers are in place. Start the pumps and systematically check each vent to ensure that all air is bled from the system.

5.Verify that makeup water is available. Adjust makeup water appropriately to replace the air which was bled from the system. Check and adjust the water/air level in the expansion tank.

6.Set the boiler (when used) to raise the loop temperature to approximately 85 F. Open a drain at the lowest point in the system. Adjust the makeup water replacement rate to equal the rate of bleed.

7.Refill the system and add trisodium phosphate in a pro- portion of approximately one pound per 150 gallons of water. Reset the boiler (when used) to raise the loop tem- perature to about 100 F. Circulate the solution for a

minimum of eight to 24 hours. At the end of this period, shut off the circulating pump and drain the solution. Re- peat system cleaning if necessary.

CAUTION

To avoid possible damage to piping systems constructed of plastic piping, DO NOT allow loop temperature to exceed 115 F.

8.When the cleaning process is complete, remove the short- circuited hoses. Reconnect the hoses to the proper supply and return the connections to each of the rooftop units. Refill the system and bleed off all air.

9.Add antifreeze to the system in climates where ambient temperature falls below freezing, using the proportion of antifreeze shown in Table 17. The volume of antifreeze required will vary based on outdoor design temperature.

10.Test the system pH with litmus paper. The system water should be slightly alkaline ( pH 7.5 to 8.5). Add chemi- cals as appropriate to maintain acidity levels.

11.When the system is successfully cleaned, flushed, refilled and bled, check the main system panels, safety cutouts, and alarms. Set the controls to properly maintain loop temperatures.

NOTE: Carrier strongly recommends all piping connections, both internal and external to the unit, be pressure tested by an appropriate method prior to any finishing of the interior space or before access to all connections is limited. Test pressure may not exceed the maximum allowable pressure for the unit and all components within the water system.

Carrier will not be responsible or liable for damages from water leaks due to inadequate or lack of a pressurized leak test, or damages caused by exceeding the maximum pressure rating during installation.

CAUTION

Do Not use “Stop-Leak” or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and will inhibit unit operation.

Antifreeze — In areas where entering loop temperatures drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leav- ing loop temperature would be 22 to 25 F. Therefore, the freeze protection should be at 15 F (30 F – 15 F = 15 F).

IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or introduced under water level to prevent fumes.

Calculate the total volume of fluid in the piping system. Use the percentage by volume in Table 17 to determine the amount of antifreeze to use. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to mea- sure specific gravity.

FREEZE PROTECTION SELECTION — The 30 F FP1 fac- tory setting (water) should be used to avoid freeze damage to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (anti- freeze 13 F) set point to avoid nuisance faults.

39

Image 39
Contents Safety Considerations ContentsGeneral InstallationPhysical Data Aquazone 50RTP03-20 Units Dimensions Outside Air Water CondensateIn/Out FPT Drain 03,04 12.57 x 18.95 x 11/4 10,12 11/2 In/Out FPT14,20 18.95 x 50RTP14,20 Unit Dimensions78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25 Return Air Transition Supply Air Transition Exterior50 RTP Install Condensate DrainWater Quality Guidelines Connect Electrical WiringFLA Hacr Electrical Data50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3800 39004000 50RTP10 Blower Performance Data 41004200 4600 43004400 450050RTP12 Blower Performance Data 6200 50RTP14 Blower Performance Data7000 64006600 680050RTP20 Blower Performance Data Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns Open 10,000ECR See legend and notes on 50RTP08-20 Units 50RTP03-06 UnitsHpwr A50-8557 Sizes Typical Control Wiring with Deluxe D and LON ControllerJ6J5 J1 J8AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Deluxe D Connect Low Voltage WiringCompressor-Stage Reversing Valve Fan 24Vac Hot 24Vac ComField Selectable Inputs Complete C Control Jumper Settings SeeDeluxe D Control Jumper Settings See PRE-START-UPDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsOperating Limits Unit Start-Up Cooling ModeUnit Start-Up Heating Mode START-UPBACview6 Display Interface Unit Start-Up with Wshp Open ControlsPage Units with Aquazone Deluxe D Control Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica Service’ to 4’ Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location TroubleshootingOvercharged with refrigerant TroubleshootingAir temperature out of range Reduced or no water flowUnit Does Not Operate Sensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Appendix a Wshp Screen Open Configuration ServiceTest Electronically Commutated Motor Configuration ServiceAlarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50RTP START-UP ChecklistCatalog No Form 50RTP-1SI Pg CL-2 10A Replaces New Heating Cycle AnalysisCooling Cycle Analysis Along Dotted Line