Step 8 — Connect Low Voltage Wiring

THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the Aquazone™ control board. See Fig. 17-19.

WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at 30 F. In earth loop applications, jumper JW3 should be clipped to change the setting to 13 F when using antifreeze in colder earth loop applications. See Fig. 20.

AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for 30 F and should not need adjusting, unless using anti-freeze.

THERMOSTAT

Compressor-Stage 1

Y1

 

 

Compressor-Stage 2

Y2

Reversing Valve

O

Fan

G

24Vac Hot

R

 

 

24Vac Com

C

 

 

 

AL

 

 

CompleteC 1 CompleteC 2

Y

 

Y

 

 

 

 

 

 

O

 

O

G

 

G

 

 

 

R

 

R

CC

ALAL

ACCESSORY CONNECTIONS — Terminal labeled A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This sig- nal operates with the compressor terminal. See Fig. 21. Refer

Fig. 18 — Thermostat Wiring to Complete C Board

to the specific unit wiring schematic for details.

NOTE: The A terminal should only be used with 24 volt signals — not line voltage signals.

WATER SOLENOID VALVES — Water solenoid valves may be used on primary secondary pump and ground water installa- tions. A typical well water control valve wiring which can limit waste water in a lockout condition is shown in Fig. 21. A slow closing valve may be required to prevent water hammer. When using a slow closing valve, special wiring conditions need to be considered. The valve takes approximately 60 sec- onds to open (very little water will flow before 45 seconds) and it activates the compressor only after the valve is completely

THERMOSTAT

Compressor-Stage 1

Y1

Compressor-Stage 2

Y2

Reversing Valve

O

Fan

G

24Vac Hot

R

 

 

24Vac Com

C

 

 

 

AL

 

 

Deluxe D 1

Deluxe D 2

Y1 COM 2

Y COM 2

Y2

 

O

O

G

G

R

R

CC

AL1AL1

opened by closing its end switch. When wired as shown, the valve will have the following operating characteristics:

1.Remain open during a lockout.

2.Draw approximately 25 to 35 VA through the “Y” signal of the thermostat.

IMPORTANT: This can overheat the anticipators of electromechanical thermostats. Only use relay based electronic thermostats.

 

Capacitor

 

Circ Brkr

 

Grnd

Contactor-CC

 

L2

L1

 

BR

Transformer

 

 

Aquazone “C”

CB

See Note

THERMOSTAT

Low Voltage

Connector

WIRED DIRECTLY

 

TO CONTROL

 

BOARD

 

NOTE: Low voltage connector may be removed for easy installation.

Fig. 17 — Low Voltage Field Wiring

34

Fig. 19 — Thermostat Wiring to Deluxe D Board

AQUAZONE CONTROL (C Control Shown)

Fig. 20 — Typical Aquazone Control Board

Jumper Locations

TERMINAL STRIP P2

C

TYPICAL 24 VAC WATER

VALVE

A

Fig. 21 — Typical D Control Accessory Wiring

Image 34
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data Aquazone 50RTP03-20 Units Outside Air Water Condensate DimensionsIn/Out FPT Drain 03,04 12.57 x In/Out FPT 18.95 x 11/4 10,12 11/250RTP14,20 Unit Dimensions 14,20 18.95 xReturn Air Transition Supply Air Transition Exterior 78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25Install Condensate Drain 50 RTPConnect Electrical Wiring Water Quality GuidelinesElectrical Data FLA Hacr50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3900 38004000 4100 50RTP10 Blower Performance Data4200 4500 43004400 460050RTP12 Blower Performance Data 50RTP14 Blower Performance Data 62006800 64006600 700050RTP20 Blower Performance Data 10,000 Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns OpenECR See legend and notes on 50RTP03-06 Units 50RTP08-20 UnitsHpwr A50-8557 Typical Control Wiring with Deluxe D and LON Controller SizesJ1 J8 J6J5AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Reversing Valve Fan 24Vac Hot 24Vac Com Connect Low Voltage WiringCompressor-Stage Deluxe DPRE-START-UP Complete C Control Jumper Settings SeeDeluxe D Control Jumper Settings See Field Selectable InputsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Operating LimitsUnit Start-Up with Wshp Open Controls BACview6 Display InterfacePage Units with Aquazone Complete C Control Antifreeze Percentages by VolumeOperation Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaReplacing the Wshp Open Controller’s Bat Refrigerant ChargingAir Coil Fan Motor Removal ’ to 4’Troubleshooting FP1 and FP2 Thermistor LocationReduced or no water flow TroubleshootingAir temperature out of range Overcharged with refrigerantUnit Does Not Operate Status Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Configuration Service Electronically Commutated MotorAlarm Page Page Copyright 2010 Carrier Corporation 50RTP START-UP Checklist II. START-UPAlong Dotted Line Heating Cycle AnalysisCooling Cycle Analysis Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New