APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
SCREEN NAME | PASSWORD |
| POINT NAME | EDITABLE | RANGE | DEFAULT | NOTES | |
LEVEL |
| |||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
| Off, Fan Only,Economize, |
|
|
|
|
|
| Operating Mode |
| Cooling, Heating, Cont Fan, Test, |
| Displays unit operating mode |
|
|
|
|
|
| Start Delay, Dehumidify |
|
|
|
|
|
| Fan Operating Mode |
| Auto/Continuous/Always On |
| Displays how the fan is configured |
|
|
|
|
|
| to operate | ||
|
|
|
|
|
|
|
| |
|
|
|
| Occupancy Status |
| Unoccupied/Occupied |
| Displays the current occupancy status |
|
|
|
|
|
| Always Occupied/Local Schedule/ |
|
|
|
|
|
|
|
| BACnet Schedule/BAS Keypad/ |
| Displays the origin of the |
|
|
|
| Occupancy Control |
| Occupied Contact/Holiday Schedule/ |
| |
|
|
|
|
|
| occupancy control | ||
|
|
|
|
|
| Override Schedule/Pushbutton |
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| Override/Unoccupied None |
|
|
|
|
|
| Outside Air |
| ° F |
| Displays OAT (Viewable only if OAT |
|
|
|
| Temperature |
|
| is a network broadcast) | |
|
|
|
|
|
|
| ||
|
|
|
| SPT |
| ° F |
| Displays SPT |
|
|
|
| SPT Status |
| Normal/Above Limit/Below |
| Displays the SPT status |
|
|
|
|
| Limit/Sensor Failure |
| ||
|
|
|
|
|
|
|
| |
|
|
|
| SPT Sensor Status |
| Inactive/Connected |
| Displays the connection status |
|
|
|
|
|
| of the Rnet sensor | ||
|
|
|
|
|
|
|
| |
|
|
|
| Condensate Overflow |
| Normal/Alarm |
| Displays the status of the |
|
|
|
|
|
| condensate overflow | ||
|
|
|
|
|
|
|
| |
|
|
|
| Cooling Set Point |
| ° F |
| Displays the actual set point |
|
|
|
|
|
| being used for cooling control | ||
|
|
|
|
|
|
|
| |
|
|
|
| Heating Set Point |
| ° F |
| Displays the actual set point |
| Unit | No Password |
|
|
| being used for heating control | ||
|
|
|
|
|
| |||
Maintenance | required |
|
|
| ° F |
| Displays the offset values from the Rnet | |
|
|
|
| Set Point Adjustment |
|
| user set point adjustment that is being | |
|
|
|
|
|
|
|
| applied to the configured set points |
|
|
|
| Auxiliary Heat Control |
| ° F |
| Displays the calculated set point being |
|
|
|
| Set Point |
|
| used for auxiliary heating control | |
|
|
|
|
|
|
| ||
|
|
|
| H2O Economizer |
| ° F |
| Displays the calculated set point being |
|
|
|
| Control Set Point |
|
|
| used for economizer control |
|
|
|
| Calculated IAQ/ |
|
|
| Displays the ventilation damper |
|
|
|
| Ventilation Damper |
| % |
| |
|
|
|
|
|
| position calculated by the DCV control | ||
|
|
|
| position |
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| Active Compressor |
| 0/1/2 |
| Displays the actual number of |
|
|
|
| Stages |
|
| compressor stages operating | |
|
|
|
|
|
|
| ||
|
|
|
| SAT |
| ° F |
| Displays SAT |
|
|
|
| Reset Filter Alarm | X | No/Yes |
| Used to reset the filter alarm timer after |
|
|
|
|
| the filter has been cleaned or replaced | |||
|
|
|
|
|
|
|
| |
|
|
|
| Overflow Contact |
| Closed/Open |
| Displays the state of the condensate |
|
|
|
|
|
| overflow switch contact | ||
|
|
|
|
|
|
|
| |
|
|
|
| Occupancy Contact |
| Closed/Open |
| Displays the state of the external/ |
|
|
|
|
|
| remote occupancy input switch contact | ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
| Inactive/Occupied/ |
| Provides capability to force the |
|
|
|
| BAS/Keypad Override | X | Inactive | equipment to operate in an | |
|
|
|
| Unoccupied | ||||
|
|
|
|
|
|
| occupied or unoccupied mode | |
|
|
|
|
|
|
|
| |
|
|
|
| OAT Input |
| N/A / Network |
| Displays if an OAT value is being |
|
|
|
|
|
| received from the Network | ||
|
|
|
|
|
|
|
| |
|
|
|
| BACnet | X |
|
| See TPI |
|
|
|
| Keypad Configuration | X |
|
| Mapping |
System Settings |
|
| Password | X |
|
| Changes password | |
|
| Network | X |
|
| See TPI | ||
|
|
|
|
|
| |||
|
|
|
| BACnet Time Master | X |
|
| See TPI |
|
|
|
| Clock Set | X |
|
| Changes clock/time setting |
|
|
|
| Override Schedules |
| Inactive/Active Occupied |
|
|
|
|
|
| Pushbutton Override |
| Inactive/Active Occupied |
|
|
Occupancy | No Password |
| Keypad Override |
| Inactive/Active Occupied/Active |
| Used to display the active and | |
|
| Unoccupied |
| |||||
Maintenance | required |
|
|
|
| inactive occupancy control inputs | ||
| Schedules |
| Inactive/Active Occupied |
| ||||
|
|
|
|
|
|
| ||
|
|
|
| Occupancy Contact |
| Inactive/Active Occupied |
|
|
|
|
|
| BAS on/off |
| Inactive/Active Occupied |
|
|
|
|
|
| Local Occupancy | X | Disable/Enable | Enable |
|
|
|
|
| Schedules |
| |||
|
|
|
|
|
|
|
| |
|
| User/Admin |
| Local Holiday | X | Disable/Enable | Disable | Used to define which occupancy inputs |
Schedule |
| Schedules | ||||||
Password level |
|
|
|
| are used to determine | |||
Configuration |
| Local Override |
|
|
| |||
access |
| X | Disable/Enable | Disable | occupancy mode. | |||
|
|
| Schedules | |||||
|
|
|
|
|
|
|
| |
|
|
|
| BACnet Occupancy | X | Disable/Enable | Disable |
|
|
|
|
| Schedules |
| |||
|
|
|
|
|
|
|
| |
| LEGEND |
|
|
|
|
| ||
BAS — Building Automation System |
|
|
|
| ||||
DCV — Demand Controlled Ventilation |
|
|
|
| ||||
ECM | — Electronically Commutated Motor |
|
|
|
| |||
IAQ | — Indoor Air Quality |
|
|
|
|
| ||
OAT | — Outdoor Air Temperature |
|
|
|
| |||
RH | — Relative Humidity |
|
|
|
|
| ||
SAT — Supply Air Temperature |
|
|
|
| ||||
SPT | — Space Temperature |
|
|
|
|
| ||
TPI | — Third Party Integration |
|
|
|
|
|