Carrier 50RTP03-20 Operating Limits, Unit Start-Up Cooling Mode, Unit Start-Up Heating Mode

Page 37

START-UP

Use the procedure outlined below to initiate proper unit start-up.

NOTE: This equipment is designed for indoor installation only.

Operating Limits

ENVIRONMENT — This equipment is designed for outdoor installation ONLY. Extreme variations in temperature, humidi- ty and corrosive water or air will adversely affect the unit per- formance, reliability and service life.

POWER SUPPLY — A voltage variation of ± 10% of name- plate utilization voltage is acceptable.

UNIT STARTING CONDITIONS — See Table 15 for unit starting conditions.

Table 15 — Starting Conditions — 50RTP Units

AIR LIMITS

COOLING

HEATING

Minimum Entering Air

40 F

40 F

Maximum Entering Air (db)

110 F

80 F

WATER LIMITS

 

 

Minimum Entering Fluid

40 F

20 F

Maximum Entering Fluid

120 F

90 F

LEGEND

 

 

db — Dry Bulb

NOTE: These starting conditions are not normal or continuous operating conditions. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature. See Table 16 for operating limits.

WARNING

When the disconnect switch is closed, high voltage is pres- ent in some areas of the electrical panel. Exercise caution when working with the energized equipment.

1.Restore power to system.

2.Turn thermostat fan position to ON. Blower should start.

3.Balance airflow at registers.

4.Adjust all valves to the full open position and turn on the line power to all heat pump units.

5.Operate unit in the cooling cycle. Room temperature should be approximately 70 to 75 F dry bulb. Loop water temperature entering the heat pumps should be between 60 and 110 F.

NOTE: Three factors determine the operating limits of a unit:

(1)entering air temperature, (2) water temperature and (3) ambient temperature. Whenever any of these factors are at a minimum or maximum level, the other two factors must be at a normal level to ensure proper unit operation. See Table 15.

Table 16 — Operating Limits — 50RTP Units

AIR LIMITS

COOLING

HEATING

Minimum Entering Air

60 F

50 F

Maximum Entering Air (db)

90 F

80 F

WATER LIMITS

 

 

Minimum Entering Fluid

40 F

20 F

Maximum Entering Fluid

120 F

90 F

LEGEND

 

 

db — Dry Bulb

Scroll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction, perform the following procedure.

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure does not rise to normal levels:

1.Turn off power to the unit. Install disconnect tag.

2.Reverse any two of the unit power leads.

3.Reapply power to the unit and verify pressures are correct.

The suction and discharge pressure levels should now move to their normal start-up levels.

When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not provide cooling.

After a few minutes of reverse operation, the scroll com- pressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset, turn the thermostat on and then off.

NOTE: There is a 5-minute time delay before the compressor will start.

Unit Start-Up Cooling Mode

1.Adjust the unit thermostat to the warmest position. Slowly reduce the thermostat position until the compres- sor activates.

2.Check for cool air delivery at unit grille a few minutes after the unit has begun to operate.

3.Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line. Be sure the condensate trap in- cludes a water seal.

4.Check the temperature of both supply and discharge water. If temperature is within range, proceed. If tempera- ture is outside the range, check the cooling refrigerant pressures.

5.Air temperature drop across the coil should be checked when compressor is operating. Air temperature drop should be between 15 and 25 F.

Unit Start-Up Heating Mode

NOTE: Operate the unit in heating cycle after checking the cooling cycle. Allow five minutes between tests for the pres- sure or reversing valve to equalize.

1.Turn thermostat to lowest setting and set thermostat switch to HEAT position.

2.Slowly turn the thermostat to a higher temperature until the compressor activates.

3.Check for warm air delivery at the unit grille within a few minutes after the unit has begun to operate.

4.Check the temperature of both supply and discharge water. If temperature is within range, proceed. If tempera- ture is outside the range, check the heating refrigerant pressures.

5.Once the unit has begun to run, check for warm air deliv- ery at the unit grille.

6.Air temperature rise across the coil should be checked when compressor is operating. Air temperature rise should be between 20 and 30 F after 15 minutes at load.

7.Check for vibration, noise and water leaks.

37

Image 37
Contents Safety Considerations ContentsGeneral InstallationPhysical Data Aquazone 50RTP03-20 Units Outside Air Water Condensate DimensionsIn/Out FPT Drain 03,04 12.57 x 18.95 x 11/4 10,12 11/2 In/Out FPT14,20 18.95 x 50RTP14,20 Unit Dimensions78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25 Return Air Transition Supply Air Transition Exterior50 RTP Install Condensate DrainWater Quality Guidelines Connect Electrical WiringFLA Hacr Electrical Data50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3900 38004000 4100 50RTP10 Blower Performance Data4200 4400 43004500 460050RTP12 Blower Performance Data 6200 50RTP14 Blower Performance Data6600 64006800 700050RTP20 Blower Performance Data Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns Open 10,000ECR See legend and notes on 50RTP08-20 Units 50RTP03-06 UnitsHpwr A50-8557 Sizes Typical Control Wiring with Deluxe D and LON ControllerJ1 J8 J6J5AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Compressor-Stage Connect Low Voltage WiringReversing Valve Fan 24Vac Hot 24Vac Com Deluxe DDeluxe D Control Jumper Settings See Complete C Control Jumper Settings SeePRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeSTART-UP Operating LimitsBACview6 Display Interface Unit Start-Up with Wshp Open ControlsPage Operation Antifreeze Percentages by VolumeUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceAir Coil Fan Motor Removal Refrigerant ChargingReplacing the Wshp Open Controller’s Bat ’ to 4’FP1 and FP2 Thermistor Location TroubleshootingAir temperature out of range TroubleshootingReduced or no water flow Overcharged with refrigerantUnit Does Not Operate Alarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Electronically Commutated Motor Configuration ServiceAlarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50RTP START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisAlong Dotted Line Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New