Carrier 50VQP084-300 specifications Field Power Supply Wiring

Page 11

Boiler drains and other valves should be connected using a “T” connector to allow acid flushing for the heat exchanger.

Do not overtighten connections.

Route piping to avoid service access areas to unit.

Use PVC SCH80 or copper piping material.

NOTE: PVC SCH40 should not be used due to system high pressure and temperature extremes.

Water Supply and Quantity — Check water supply. Water supply should be plentiful and of good quality. See Table 2 for water quality guidelines.

IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed- system application design requirements may cause damage to the tube-in-tube heat exchanger that is not the responsi- bility of the manufacturer.

In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treat- ment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits.

Step 8 — Field Power Supply Wiring

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

CAUTION

Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors.

All field-installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.

Refer to unit wiring diagrams Fig. 27-30 for a schematic of the field connections which must be made by the installing (or electrical) contractor. See Tables 3 and 4 for fuses sizes.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.

Operating voltage must be the same voltage and phase as shown in electrical data shown in Tables 3 and 4.

Make all final electrical connections with a length of flexi- ble conduit to minimize vibration and sound transmission to the building.

POWER CONNECTION — Line voltage connection is made by connecting the incoming line voltage wires to the L side of the CC terminal. See Tables 3 and 4 for correct wire and maximum overcurrent protection sizing.

SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter- mine the percentage voltage imbalance:

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

 

average voltage

 

 

Example: Supply voltage is 420-3-50.

 

 

 

AB = 425 volts

 

 

 

BC = 422 volts

 

 

 

AC = 417 volts

 

 

 

Average Voltage =

425 + 422 + 417

 

3

 

 

 

 

 

=

1264

 

 

 

3

 

= 421

Determine maximum deviation from average voltage:

(AB) 425 – 421 = 4 v (BC) 422 – 421 = 1 v (AC) 421 – 418 = 3 v

Maximum deviation is 4 v. Determine percent voltage imbalance.

% Voltage Imbalance = 100 x 4214

= 0.95%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.

NOTE: If more than 2% voltage imbalance is present, contact local electric utility.

420-VOLT OPERATION — All 380/420 volt units are factory wired for 380 volts. The transformers may be switched to 420-volt operation (as illustrated on the wiring diagram) by disconnecting the VIO lead at L1 and attaching the BRN lead to L1. Close open end of VIO lead.

11

Image 11
Contents Safety Considerations ContentsGeneral Installation782 50VQP Unit Physical Data406 442A50-8436 50VQP084-150 Unit DimensionsA50-8437 50VQP168-300 Unit DimensionsA50-8468 A50-8466A50-8467 A50-8472 A50-8469A50-8470 A50-8471A50-8479 A50-8476A50-8477 A50-8478A50-8484 A50-8482A50-8485 A50-8483Trap Condensate Drain A50-8486Field Power Supply Wiring Water Quality Guidelines 50VQP084-168 Unit with Complete C Control Typical A50-843850VQP084-168 with Deluxe D Control Typical A50-8439J1 J8 AL1J6J5 50VQP Unit Electrical Data Standard Unit 50VQP Unit Electrical Data Dual Point Power UnitA50-8441 Field Control WiringPRE-START-UP A50- 6268tf.tifPage 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 456 495 529 561 595 625 656 685 712 741 767 412 455 492 526 563 595 628 658 687 718 745421 459 499 533 569 600 633 663 691 722 749 441 478 513 549 581 614 644 672 703 730 75950VQP120 Blower Performance Data 555 589 618 646 676 702 728 753 779 803 827 850 875 898 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897526 561 592 621 649 679 706 732 758 785 809 833 857 882 544 575 605 633 661 691 717 742 767 794 818 842 867 89050VQP150 Blower Performance Data 618 647 678 708 738 766 793 819 844 867 891 914 937 959 980 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 605 637 666 697 727 755 783 809 835 858 882 905 928 951 97350VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 581 613 646 678 706 735 763 791 817 842 867 889 538 574 609 640 673 703 733 761 788 812 838 863 888 912553 588 620 653 685 715 744 771 796 822 847 872 896 568 602 633 666 697 726 755 782 806 832 857 881 904Field Selectable Inputs Complete C Control Jumper Settings See FigDeluxe D Control Jumper Settings See Fig Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UP50VQP Unit Operating Limits Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Water Temperature Change Through Heat ExchangerCoaxial Water Pressure Drop Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume OperationComplete C and Deluxe D Board System Test Units with Aquazone Complete C ControlUnits with Aquazone Deluxe D Control Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceAir Coil Fan Motor Removal TroubleshootingRefrigerant Charging FP1 and FP2 Thermistor Location A50-8163Troubleshooting Unit Does Not Operate Page Page Catalog No Form 50VQP-C1SI 11-10 Copyright 2010 Carrier CorporationForm 62AQ-1SI Pg CL-1 Replaces New Tab 50VQP START-UP ChecklistII. START-UP Book Catalog NoCooling Cycle Analysis Heating Cycle Analysis