Table 23 — Troubleshooting

 

FAULT

 

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Main Power Problems

 

X

X

Green Status LED Off

Check line voltage circuit breaker and disconnect.

 

 

 

 

 

 

Check for line voltage between L1 and L2 on the contactor.

 

 

 

 

 

 

Check for 24-vac between R and C on controller.

 

 

 

 

 

 

Check primary/secondary voltage on transformer.

HP Fault — Code 2

 

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

High Pressure

 

 

 

cooling

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

 

 

 

 

 

 

 

X

Water temperature out of

Bring water temperature within design parameters.

 

 

 

 

 

range in cooling

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

heating

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

Dirty air coil — construction dust, etc. Perform preventative mainte-

 

 

 

 

 

 

nance; Clean air coil.

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

X

 

Air temperature out of range

Bring return-air temperature within design parameters.

 

 

 

 

 

in heating

 

 

 

 

X

X

Overcharged with refrigerant

Check superheat/subcooling vs. typical operating condition.

 

 

 

X

X

Bad HP switch

Check switch continuity and operation. Replace.

LP Fault — Code 3

 

X

X

Insufficient charge

Check for refrigerant leaks.

Low Pressure/Loss of

 

X

 

Compressor pump down at

Check charge and start-up water flow.

Charge

 

 

 

 

 

start-up

 

 

 

 

 

 

 

FP1 Fault — Code 4

 

X

 

Reduced or no water flow in

Check pump operation or water valve operation/setting.

Water Freeze Protection

 

 

 

heating

 

 

 

 

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

X

 

Inadequate antifreeze level

Check antifreeze density with hydrometer.

 

 

 

X

 

Improper freeze protect set-

Clip JW3 jumper for antifreeze (–12.2 C) use.

 

 

 

 

 

ting (–1.1 C vs –12.2 C)

 

 

 

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

 

 

range

 

 

 

 

X

X

Bad thermistor

Check temperature and impedance correlation.

FP2 Fault — Code 5

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Air Coil Freeze

 

 

 

cooling

Check fan motor operation and airflow restrictions.

Protection

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

 

 

 

 

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering-air temperature within design

 

 

 

 

 

 

parameters.

 

 

 

 

X

Improper freeze protect set-

Normal airside applications will require –1.1 C only.

 

 

 

 

 

ting (–1.1 C vs –12.2 C)

 

 

 

 

X

X

Bad thermistor

Check temperature and impedance correlation.

Condensate Fault —

 

X

X

Blocked drain

Check for blockage and clean drain.

Code 6

 

X

X

Improper trap

Check trap dimensions and location ahead of vent.

 

 

 

 

 

 

 

X

Poor drainage

Check for piping slope away from unit.

 

 

 

 

 

 

Check slope of unit toward outlet.

 

 

 

 

 

 

Poor venting. Check vent location.

 

 

 

 

X

Moisture on sensor

Check for moisture shorting to air coil.

Over/Under Voltage —

 

X

X

Under voltage

Check power supply and 24-vac voltage before and during operation.

Code 7

 

 

 

 

Check power supply wire size.

(Auto Resetting)

 

 

 

 

 

 

 

 

Check compressor starting.

 

 

 

 

 

 

 

 

 

 

 

 

Check 24-vac and unit transformer tap for correct power supply voltage.

 

 

 

X

X

Over voltage

Check power supply voltage and 24 vac before and during operation.

 

 

 

 

 

 

Check 24-vac and unit transformer tap for correct power supply voltage.

Performance Monitor —

 

X

 

Heating mode FP2> 51.7 C

Check for poor airflow or overcharged unit.

Code 8

 

 

X

Cooling mode FP1> 51.7 C

Check for poor water flow or airflow.

 

 

 

 

 

OR FP2< 4.4 C

 

No Fault Code Shown

 

X

X

Compressor overload

Check and replace if necessary.

 

 

 

X

X

Control board

Reset power and check operation.

Unit Short Cycles

 

X

X

Dirty air filter

Check and clean air filter.

 

 

 

X

X

Unit in Test mode

Reset power or wait 20 minutes for auto exit.

 

 

 

X

X

Unit selection

Unit may be oversized for space. Check sizing for actual load of space.

 

 

 

X

X

Compressor overload

Check and replace if necessary.

Only Fan Runs

 

X

X

Thermostat position

Ensure thermostat set for heating or cooling operation.

 

 

 

X

X

Unit locked out

Check for lockout codes. Reset power.

 

 

 

X

X

Compressor overload

Check compressor overload. Replace if necessary.

 

 

 

X

X

Thermostat wiring

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in Test mode.

 

LEGEND

 

 

 

 

FP

Freeze Protection

 

 

 

 

HP

High Pressure

 

 

 

 

LED — Light-Emitting Diode

 

 

 

 

LP

Low Pressure

 

 

 

 

RV

Reversing Valve

 

 

 

 

42

Image 42
Contents Contents Safety ConsiderationsInstallation General442 50VQP Unit Physical Data406 78250VQP084-150 Unit Dimensions A50-843650VQP168-300 Unit Dimensions A50-8437A50-8466 A50-8467A50-8468 A50-8471 A50-8469A50-8470 A50-8472A50-8478 A50-8476A50-8477 A50-8479A50-8483 A50-8482A50-8485 A50-8484A50-8486 Trap Condensate DrainField Power Supply Wiring Water Quality Guidelines A50-8438 50VQP084-168 Unit with Complete C Control TypicalA50-8439 50VQP084-168 with Deluxe D Control TypicalAL1 J6J5J1 J8 50VQP Unit Electrical Data Dual Point Power Unit 50VQP Unit Electrical Data Standard UnitA50- 6268tf.tif Field Control WiringPRE-START-UP A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 441 478 513 549 581 614 644 672 703 730 759 412 455 492 526 563 595 628 658 687 718 745421 459 499 533 569 600 633 663 691 722 749 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 544 575 605 633 661 691 717 742 767 794 818 842 867 890 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897526 561 592 621 649 679 706 732 758 785 809 833 857 882 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 568 602 633 666 697 726 755 782 806 832 857 881 904 538 574 609 640 673 703 733 761 788 812 838 863 888 912553 588 620 653 685 715 744 771 796 822 847 872 896 581 613 646 678 706 735 763 791 817 842 867 889Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs START-UP DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Operating LimitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode 50VQP Unit Operating LimitsOperation Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume Coaxial Water Pressure DropUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaTroubleshooting Refrigerant ChargingAir Coil Fan Motor Removal A50-8163 FP1 and FP2 Thermistor LocationTroubleshooting Unit Does Not Operate Page Page Copyright 2010 Carrier Corporation Catalog No Form 50VQP-C1SI 11-10Book Catalog No 50VQP START-UP ChecklistII. START-UP Form 62AQ-1SI Pg CL-1 Replaces New TabHeating Cycle Analysis Cooling Cycle Analysis