Carrier 50VQP084-300 specifications A50-8439, 50VQP084-168 with Deluxe D Control Typical

Page 14

 

LEGEND

AL

Alarm Relay

BC

Blower Contactor

CB

Circuit Breaker

CC

Compressor Contactor

CO

Sensor, Condensate Overflow

DPP

Dual Point Power

DS

Disconnect Switch

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

HP

High-Pressure Switch

HPWS

High-Pressure Water Switch

JW3

Clippable Field Selection Jumper

LOC

Loss of Charge Pressure Switch

MV

Motorized Valve

PDB

Power Distribution Block

PDB2

Power Distribution Block Dual Point Option

RVS

Reversing Valve Solenoid

TRANS — Transformer

Factory Line Voltage Wiring

Factory Low Voltage Wiring

Field Line Voltage Wiring

Field Low Voltage Wiring

Printed Circuit Trace

Optional Wiring

14

Relay/Contactor Coil

Thermistor

Condensate Pan

Circuit Breaker

Ground

Solenoid Coil

Relay Contacts - N.O.

Relay Contacts - N.C.

Temperature Switch

Switch - Low Pressure

Switch - High Pressure

Wire Nut

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC (National Electrical Code) and local codes.

3.380/420-v transformers will be connected for 380-v operation. For 420-v operation, dis- connect VIO lead at L1, and attach BRN lead to L1. Close open end of VIO lead.

4.FP1 thermistor provides freeze protection for WATER. When using ANTIFREEZE solu- tion, cut JW3 jumper.

5.Typical heat pump thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1” and voltage rating equal to or greater than unit supply voltage.

6.24-v alarm signal shown. For dry alarm contact, cut AL2 DRY (JW4) jumper and dry con- tact will be available between AL1 and AL2.

7.Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top two standoffs as shown.)

8.For dual point power option, blower wires (3 qty) will go to PDB2 only.

a50-8439

Deluxe D

Fig. 28 — 50VQP084-168 with Deluxe D Control (Typical)

Image 14
Contents Contents Safety ConsiderationsInstallation General442 50VQP Unit Physical Data406 78250VQP084-150 Unit Dimensions A50-843650VQP168-300 Unit Dimensions A50-8437A50-8468 A50-8466A50-8467 A50-8471 A50-8469A50-8470 A50-8472A50-8478 A50-8476A50-8477 A50-8479A50-8483 A50-8482A50-8485 A50-8484A50-8486 Trap Condensate DrainField Power Supply Wiring Water Quality Guidelines A50-8438 50VQP084-168 Unit with Complete C Control TypicalA50-8439 50VQP084-168 with Deluxe D Control TypicalJ1 J8 AL1J6J5 50VQP Unit Electrical Data Dual Point Power Unit 50VQP Unit Electrical Data Standard UnitA50- 6268tf.tif Field Control WiringPRE-START-UP A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 441 478 513 549 581 614 644 672 703 730 759 412 455 492 526 563 595 628 658 687 718 745421 459 499 533 569 600 633 663 691 722 749 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 544 575 605 633 661 691 717 742 767 794 818 842 867 890 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897526 561 592 621 649 679 706 732 758 785 809 833 857 882 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 568 602 633 666 697 726 755 782 806 832 857 881 904 538 574 609 640 673 703 733 761 788 812 838 863 888 912553 588 620 653 685 715 744 771 796 822 847 872 896 581 613 646 678 706 735 763 791 817 842 867 889Field Selectable Inputs Complete C Control Jumper Settings See FigDeluxe D Control Jumper Settings See Fig START-UP DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Operating LimitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode 50VQP Unit Operating LimitsOperation Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume Coaxial Water Pressure DropComplete C and Deluxe D Board System Test Units with Aquazone Complete C ControlUnits with Aquazone Deluxe D Control Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaAir Coil Fan Motor Removal TroubleshootingRefrigerant Charging A50-8163 FP1 and FP2 Thermistor LocationTroubleshooting Unit Does Not Operate Page Page Copyright 2010 Carrier Corporation Catalog No Form 50VQP-C1SI 11-10Book Catalog No 50VQP START-UP ChecklistII. START-UP Form 62AQ-1SI Pg CL-1 Replaces New TabHeating Cycle Analysis Cooling Cycle Analysis