4.Loosen belt tension and take belt off. See Fig. 20.

5.Remove bolt-belt adjustment assembly. See Fig. 20.

a50-8482

STEP 5

8. Put 3 panels back onto unit. See Fig. 23.

CONTROL

BOX

STEP 4

a50-8485

BOLT-BELT ADJUSTMENT ASM

Fig. 20 — Remove Belt and Bolt-Belt Adjustment

Assembly

6.Move bolt-belt adjustment assembly to opposite side and reattach. See Fig. 21.

a50-8483

STEP 6

Fig. 21 — Move Bolt-Belt Adjustment Assembly

7.Put belt back on and tighten. Put control box cover and motor cover on return side. See Fig. 22.

a50-8484

CONTROL BOX

COVER

MOTOR

COVER

Fig. 22 — Replace Belt and Motor and

Control Box Covers

FRONT RETURN TOP DISCHARGE

Fig. 23 — Replace Access Panels

Step 5 — Check Duct System — The duct system should be sized to handle the design airflow quietly.

NOTE: Depending on the unit, the fan wheel may have a ship- ping support installed at the factory. This must be removed before operating unit.

SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recom- mended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should in- clude internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an uncon- ditioned space is not recommended since it will sweat and adversely affect the unit’s performance.

To reduce air noise, at least one 90-degree elbow could be included in the supply and return air ducts, provided system performance is not adversely impacted. The blower speed can be also changed in the field to reduce air noise or excessive air- flow, provided system performance is not adversely impacted. EXISTING DUCT SYSTEM — If the unit is connected to existing ductwork, consider the following:

Verify that the existing ducts have the proper capacity to handle the unit airflow. If the ductwork is too small, larger ductwork should be installed.

Check existing ductwork for leaks and repair as necessary.

NOTE: Local codes may require ventilation air to enter the space for proper indoor air quality. Hard-duct ventilation may be required for the ventilating air supply. If hard ducted venti- lation is not required, be sure that a proper air path is provided for ventilation air to unit to meet ventilation requirement of the space.

Step 6 — Install Condensate Drain — The con- densate drain can be connected to either side of the unit. The 50VQP units come with a flex hose and 1 in. (25 m) FPT con- densate connection tied inside. To install the condensate drain (see Fig. 24.):

1.Untie the flex hose and make interal trap on either the left side or right side of the unit.

2.Internally attach mounting plate with FPT fitting.

9

Image 9
Contents Safety Considerations ContentsGeneral Installation406 50VQP Unit Physical Data442 782A50-8436 50VQP084-150 Unit DimensionsA50-8437 50VQP168-300 Unit DimensionsA50-8466 A50-8467A50-8468 A50-8470 A50-8469A50-8471 A50-8472A50-8477 A50-8476A50-8478 A50-8479A50-8485 A50-8482A50-8483 A50-8484Trap Condensate Drain A50-8486Field Power Supply Wiring Water Quality Guidelines 50VQP084-168 Unit with Complete C Control Typical A50-843850VQP084-168 with Deluxe D Control Typical A50-8439AL1 J6J5J1 J8 50VQP Unit Electrical Data Standard Unit 50VQP Unit Electrical Data Dual Point Power UnitPRE-START-UP Field Control WiringA50- 6268tf.tif A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 421 459 499 533 569 600 633 663 691 722 749 412 455 492 526 563 595 628 658 687 718 745441 478 513 549 581 614 644 672 703 730 759 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 526 561 592 621 649 679 706 732 758 785 809 833 857 882 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897544 575 605 633 661 691 717 742 767 794 818 842 867 890 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 553 588 620 653 685 715 744 771 796 822 847 872 896 538 574 609 640 673 703 733 761 788 812 838 863 888 912568 602 633 666 697 726 755 782 806 832 857 881 904 581 613 646 678 706 735 763 791 817 842 867 889Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger 50VQP Unit Operating LimitsAntifreeze Percentages by Volume Approximate Fluid Volume L Per 30 M of PipeOperation Coaxial Water Pressure DropUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceTroubleshooting Refrigerant ChargingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location A50-8163Troubleshooting Unit Does Not Operate Page Page Catalog No Form 50VQP-C1SI 11-10 Copyright 2010 Carrier CorporationII. START-UP 50VQP START-UP ChecklistBook Catalog No Form 62AQ-1SI Pg CL-1 Replaces New TabCooling Cycle Analysis Heating Cycle Analysis