4.Loosen belt tension and take belt off. See Fig. 20.
5.Remove
a50-8482
STEP 5
8. Put 3 panels back onto unit. See Fig. 23.
CONTROL
BOX
STEP 4
a50-8485
Fig. 20 — Remove Belt and Bolt-Belt Adjustment
Assembly
6.Move
a50-8483
STEP 6
Fig. 21 — Move Bolt-Belt Adjustment Assembly
7.Put belt back on and tighten. Put control box cover and motor cover on return side. See Fig. 22.
a50-8484
CONTROL BOX
COVER
MOTOR
COVER
Fig. 22 — Replace Belt and Motor and
Control Box Covers
FRONT RETURN TOP DISCHARGE
Fig. 23 — Replace Access Panels
Step 5 — Check Duct System — The duct system should be sized to handle the design airflow quietly.
NOTE: Depending on the unit, the fan wheel may have a ship- ping support installed at the factory. This must be removed before operating unit.
SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recom- mended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should in- clude internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an uncon- ditioned space is not recommended since it will sweat and adversely affect the unit’s performance.
To reduce air noise, at least one
•Verify that the existing ducts have the proper capacity to handle the unit airflow. If the ductwork is too small, larger ductwork should be installed.
•Check existing ductwork for leaks and repair as necessary.
NOTE: Local codes may require ventilation air to enter the space for proper indoor air quality.
Step 6 — Install Condensate Drain — The con- densate drain can be connected to either side of the unit. The 50VQP units come with a flex hose and 1 in. (25 m) FPT con- densate connection tied inside. To install the condensate drain (see Fig. 24.):
1.Untie the flex hose and make interal trap on either the left side or right side of the unit.
2.Internally attach mounting plate with FPT fitting.
9