Carrier 50VQP084-300 specifications Start-Up, Operating Limits, Start Up System

Page 34

Auto Dehumidification Mode or High Fan Mode — Switch 7 provides selection of auto dehumidification fan mode or high fan mode. In auto dehumidification fan mode the fan speed relay will remain off during cooling stage 2 if terminal H is active. In high fan mode, the fan enable and fan speed relays will turn on when terminal H is active. Set the switch to ON for auto dehumidification fan mode or to OFF for high fan mode.

Switch 8 — Not used.

Table 13 — DIP Switch Block S2 —

Accessory 1 Relay Options

ACCESSORY 1

DIP SWITCH POSITION

RELAY OPTIONS

1

2

3

Cycle with Fan

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

LEGEND

 

 

 

NSB — Night Setback

OAD — Outside Air Damper

NOTE: All other DIP switch combinations are invalid.

Table 14 — DIP Switch Block S2 —

Accessory 2 Relay Options

ACCESSORY 2

DIP SWITCH POSITION

RELAY OPTIONS

4

5

6

Cycle with Fan

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

LEGEND

 

 

 

NSB — Night Setback

OAD — Outside Air Damper

NOTE: All other switch combinations are invalid.

Deluxe D Control Accessory Relay Configura- tions — The following accessory relay settings are applica- ble for both Deluxe D controls only:

CYCLE WITH FAN — In this configuration, the relay will be ON any time the Fan Enable relay is on.

CYCLE WITH COMPRESSOR — In this configuration, the relay will be ON any time the Compressor relay is on.

DIGITAL NIGHT SET BACK (NSB) — In this configura- tion, the relay will be ON if the NSB input is connected to ground C.

NOTE: If there are no relays configured for digital NSB, then the NSB and override (OVR) inputs are automatically config- ured for mechanical operation.

MECHANICAL NIGHT SET BACK — When NSB input is connected to ground C, all thermostat inputs are ignored. A thermostat set back heating call will then be connected to the OVR input. If OVR input becomes active, then the Deluxe D control will enter Night Low Limit (NLL) staged heating mode. The NLL staged heating mode will then provide heating during the NSB period.

WATER VALVE (SLOW OPENING) — If relay is config- ured for Water Valve (slow opening), the relay will start 60 sec- onds prior to starting compressor relay.

OUTSIDE AIR DAMPER (OAD) — If relay is configured for OAD, the relay will normally be ON any time the Fan Enable relay is energized. The relay will not start for 30 min- utes following a return to normal mode from NSB, when NSB is no longer connected to ground C. After 30 minutes, the relay will start if the Fan Enable is set to ON.

CAUTION

To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless anti- freeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze.

START-UP

Use the procedure outlined below to initiate proper unit start-up.

NOTE: This equipment is designed for indoor installation only.

Operating Limits

ENVIRONMENT — This equipment is designed for indoor installation ONLY. Extreme variations in temperature, humidi- ty and corrosive water or air will adversely affect the unit per- formance, reliability and service life.

POWER SUPPLY — A voltage variation of ± 10% of name- plate utilization voltage is acceptable.

UNIT STARTING CONDITIONS — All units start and op- erate in an ambient of 7.2 C with entering-air at 4.4 C, entering- water at –6.7 C and with both air and water at the flow rates used.

NOTE: These operating conditions are not normal or continu- ous operating conditions. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.

WARNING

When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with the energized equipment.

Start Up System

1.Restore power to system.

2.Turn thermostat fan position to ON. Blower should start.

3.Balance airflow at registers.

4.Adjust all valves to the full open position and turn on the line power to all heat pump units.

5.Operate unit in the cooling cycle. Room temperature should be approximately 10 to 38 C dry bulb. Loop water temperature entering the heat pumps should be between 10 and 49 F.

NOTE: Three factors determine the operating limits of a

unit: (1) entering-air temperature, (2) water temperature and

(3)ambient temperature. Whenever any of these factors are at a minimum or maximum level, the other two factors must be at a normal level to ensure proper unit operation. See Table 15.

Scroll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

34

Image 34
Contents Contents Safety ConsiderationsInstallation General442 50VQP Unit Physical Data406 78250VQP084-150 Unit Dimensions A50-843650VQP168-300 Unit Dimensions A50-8437A50-8467 A50-8466A50-8468 A50-8471 A50-8469A50-8470 A50-8472A50-8478 A50-8476A50-8477 A50-8479A50-8483 A50-8482A50-8485 A50-8484A50-8486 Trap Condensate DrainField Power Supply Wiring Water Quality Guidelines A50-8438 50VQP084-168 Unit with Complete C Control TypicalA50-8439 50VQP084-168 with Deluxe D Control TypicalJ6J5 AL1J1 J8 50VQP Unit Electrical Data Dual Point Power Unit 50VQP Unit Electrical Data Standard UnitA50- 6268tf.tif Field Control WiringPRE-START-UP A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 441 478 513 549 581 614 644 672 703 730 759 412 455 492 526 563 595 628 658 687 718 745421 459 499 533 569 600 633 663 691 722 749 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 544 575 605 633 661 691 717 742 767 794 818 842 867 890 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897526 561 592 621 649 679 706 732 758 785 809 833 857 882 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 568 602 633 666 697 726 755 782 806 832 857 881 904 538 574 609 640 673 703 733 761 788 812 838 863 888 912553 588 620 653 685 715 744 771 796 822 847 872 896 581 613 646 678 706 735 763 791 817 842 867 889Deluxe D Control Jumper Settings See Fig Complete C Control Jumper Settings See FigField Selectable Inputs START-UP DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Operating LimitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode 50VQP Unit Operating LimitsOperation Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume Coaxial Water Pressure DropUnits with Aquazone Deluxe D Control Units with Aquazone Complete C ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaRefrigerant Charging TroubleshootingAir Coil Fan Motor Removal A50-8163 FP1 and FP2 Thermistor LocationTroubleshooting Unit Does Not Operate Page Page Copyright 2010 Carrier Corporation Catalog No Form 50VQP-C1SI 11-10Book Catalog No 50VQP START-UP ChecklistII. START-UP Form 62AQ-1SI Pg CL-1 Replaces New TabHeating Cycle Analysis Cooling Cycle Analysis