Carrier 50VQP084-300 Operation, Coaxial Water Pressure Drop, Antifreeze Percentages by Volume

Page 36

Table 17 — Coaxial Water Pressure Drop

50VQP

 

 

PRESSURE DROP (kPa)

 

UNIT

L/s

 

 

 

 

 

 

–1 C

 

10 C

21 C

 

32 C

SIZE

 

 

 

 

 

 

 

 

 

 

 

0.66

16.5

 

13.8

8.3

 

7.6

084

1.00

37.9

 

31.7

23.4

 

20.7

 

1.32

63.4

 

54.4

42.7

 

39.3

 

0.76

26.2

 

21.4

15.8

 

13.8

096

1.13

55.1

 

46.9

36.5

 

33.1

 

1.51

89.6

 

77.2

63.4

 

59.3

 

0.95

14.5

 

11.7

8.3

 

6.9

120

1.42

36.5

 

30.3

24.1

 

22.1

 

1.89

64.8

 

55.8

46.2

 

42.7

 

1.20

18.6

 

14.5

10.3

 

9.0

150

1.76

42.7

 

35.8

28.2

 

25.5

 

2.39

75.8

 

65.5

53.1

 

49.6

 

1.32

18.6

 

15.2

9.6

 

8.3

168

1.98

42.0

 

35.8

26.2

 

23.4

 

2.65

71.7

 

61.3

47.5

 

44.1

 

1.51

28.9

 

24.1

17.9

 

15.8

192

2.27

62.0

 

52.4

41.3

 

37.9

 

1.89

100.6

 

86.8

71.0

 

66.1

 

2.84

16.5

 

13.1

9.0

 

7.6

240

3.78

40.7

 

33.8

26.9

 

24.8

 

2.39

72.3

 

63.4

51.7

 

48.2

 

3.53

21.4

 

16.5

11.7

 

10.3

300

4.79

48.2

 

40.7

31.7

 

28.9

 

3.78

85.4

 

73.7

59.9

 

55.8

NOTE: If air is purged from the system while using a 250 mm PVC flush tank, only a 25 to 50 mm level drop will be noticed since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop. If level is less than 25 to 50 mm, reverse the flow.

8.Repeat this procedure until all air is purged.

9.Restore power.

Antifreeze may be added before, during or after the flushing process. However, depending on when it is added in the process, it can be wasted. Refer to the Antifreeze sec- tion for more detail.

Loop static pressure will fluctuate with the seasons. Pres- sures will be higher in the winter months than during the warmer months. This fluctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for several minutes to condition the loop to a homogenous temperature.

When complete, perform a final flush and pressurize the loop to a static pressure of 275 to 350 kPa for winter months or 100 to 140 kPa for summer months.

After pressurization, be sure to remove the plug from the end of the loop pump motor(s) to allow trapped air to be discharged and to ensure the motor housing has been flood- ed. Be sure the loop flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger.

Antifreeze — In areas where entering loop temperatures drop below 4.4 C or where piping will be routed through ar- eas subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 8.3° C below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is –1.1 C, the leaving loop temperature would be –5.6 to –3.9 C. Therefore, the freeze protection should be at –9.4 C (–1.1 C – 8.3 C = –9.4 C) Calculate the total volume of fluid in the piping sys- tem. See Table 18. Use the percentage by volume in

Table 19 to determine the amount of antifreeze to use. Anti- freeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity. .

IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or intro- duced under water level to prevent alcohols from fuming.

FREEZE PROTECTION SELECTION — The –1.1 C FP1 factory setting (water) should be used to avoid freeze damage to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (antifreeze –12.2 C) set point to avoid nuisance faults.

Table 18 — Approximate Fluid Volume (L)

per 30 M of Pipe

PIPE

DIAMETER (in.) [mm]

VOLUME (gal.) [L]

Copper

1

[25.4]

4.1

[15.5]

 

1.25 [31.8]

6.4

[24.2]

 

1.5 [38.1]

9.2

[34.8]

Rubber Hose

1

[25.4]

3.9

[14.8]

Polyethylene

3/4 IPS SDR11

2.8

[10.6]

 

1

IPS SDR11

4.5

[17.0]

 

11/4 IPS SDR11

8.0

[30.8]

 

1/2 IPS SDR11

10.9

[41.3]

 

2

IPS SDR11

18.0

[68.1]

 

11/4 IPS SCH40

8.3

[31.4]

 

11/2 IPS SCH40

10.9

[41.3]

 

2

IPS SCH40

17.0

[64.4]

LEGEND

IPS — Internal Pipe Size

SCH — Schedule

SDR — Standard Dimensional Ratio

NOTE: Volume of heat exchanger is approximately 3.78 liters.

Table 19 — Antifreeze Percentages by Volume

 

MINIMUM TEMPERATURE FOR FREEZE

ANTIFREEZE

 

PROTECTION (C)

 

 

–12.2

–9.4

–6.7

–3.9

Methanol (%)

25

21

16

10

100% USP Food Grade

38

30

22

15

Propylene Glycol (%)

 

 

 

 

Ethanol (%)

29

25

20

14

Cooling Tower/Boiler Systems — These systems typically use a common loop maintained at 15.6 C to 32.2 C. The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary.

Ground Coupled, Closed Loop and Plateframe Heat Exchanger Well Systems — These systems allow water temperatures from –1.1 to 43.3 C. The external loop field is divided up into 51 mm polyethylene supply and return lines. Each line has valves connected in such a way that upon system start-up, each line can be isolated for flush- ing using only the system pumps. Air separation should be located in the piping system prior to the fluid re-entering the loop field.

OPERATION

Power Up Mode — The unit will not operate until all the inputs, terminals and safety controls are checked for normal operation.

NOTE: The compressor will have a 5-minute anti-short cycle upon power up.

36

Image 36
Contents Contents Safety ConsiderationsInstallation General50VQP Unit Physical Data 406442 78250VQP084-150 Unit Dimensions A50-843650VQP168-300 Unit Dimensions A50-8437A50-8466 A50-8467A50-8468 A50-8469 A50-8470A50-8471 A50-8472A50-8476 A50-8477A50-8478 A50-8479A50-8482 A50-8485A50-8483 A50-8484A50-8486 Trap Condensate DrainField Power Supply Wiring Water Quality Guidelines A50-8438 50VQP084-168 Unit with Complete C Control TypicalA50-8439 50VQP084-168 with Deluxe D Control TypicalAL1 J6J5J1 J8 50VQP Unit Electrical Data Dual Point Power Unit 50VQP Unit Electrical Data Standard UnitField Control Wiring PRE-START-UPA50- 6268tf.tif A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 412 455 492 526 563 595 628 658 687 718 745 421 459 499 533 569 600 633 663 691 722 749441 478 513 549 581 614 644 672 703 730 759 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897 526 561 592 621 649 679 706 732 758 785 809 833 857 882544 575 605 633 661 691 717 742 767 794 818 842 867 890 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958 598 623 656 687 715 744 772 799 825 850 872 896 919 942 963605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 538 574 609 640 673 703 733 761 788 812 838 863 888 912 553 588 620 653 685 715 744 771 796 822 847 872 896568 602 633 666 697 726 755 782 806 832 857 881 904 581 613 646 678 706 735 763 791 817 842 867 889Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Cooling Mode Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger 50VQP Unit Operating LimitsApproximate Fluid Volume L Per 30 M of Pipe Antifreeze Percentages by VolumeOperation Coaxial Water Pressure DropUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaTroubleshooting Refrigerant ChargingAir Coil Fan Motor Removal A50-8163 FP1 and FP2 Thermistor LocationTroubleshooting Unit Does Not Operate Page Page Copyright 2010 Carrier Corporation Catalog No Form 50VQP-C1SI 11-1050VQP START-UP Checklist II. START-UPBook Catalog No Form 62AQ-1SI Pg CL-1 Replaces New TabHeating Cycle Analysis Cooling Cycle Analysis