9.Condensate line is open and correctly pitched.
10.Transformer switched to lower voltage tap if necessary.
11.Blower rotates freely — shipping support is removed.
12.Blower speed is on correct setting.
13.Air filter is clean and in position.
14.Service/access panels are in place.
15.
16.Air coil is clean.
17.Control
AIR COIL — To obtain maximum performance, the air coil should be cleaned before starting the unit. A 10% solution of dishwasher detergent and water is recommended for both sides of the coil. Rinse thoroughly with water.
Airflow and External Static Pressure — The 50VQP units are available with standard, low, and
SHEAVE ADJUSTMENT — The 50VQP units are supplied with a variable sheave drive on the fan motor to adjust for dif- fering airflows at various ESP (external static pressure) condi- tions. See Tables
1.Loosen belt tension and remove belt.
2.Loosen set screw on fan motor.
3.Open sheave to desired position.
4.Retighten set screw and replace belt. NOTE: Set belt tension as outlined below.
BELT TENSION ADJUSTMENT — An overly loose belt will, upon starting motor, produce a slippage “squeal” and
cause premature belt failure and or intermittent airflow. An overly tight belt can cause premature motor or blower bear- ing failure. To adjust the belt tension, follow the procedure outlined below:
1.Remove belt from motor sheave.
2.Lift motor assembly.
3.Loosen the
4.Turn the bolts by hand to the desired position then tighten the
5.Lower the motor assembly.
6.Install the belt.
7.The belt tension can be adjusted by using one of the fol- lowing methods:
a.Tighten until belt deflects approximately 13 mm with very firm finger pressure.
b.Grasp belt midway between two pulleys and twist for a
NOTE: Adjusting less than 90 degrees will over- tighten the belt and adjusting more than 90 degrees will loosen belt.
c.Set proper belt tension to 32 to 36 kg.
NOTE: The motor position should not need adjustment. Motor sheave position is at mid position of each sheave. For example, the motor sheave is 2.5 turns open on a
NOTE: Available airflows for all units are shown in Tables
18