Carrier 50VQP084-300 specifications Unit Does Not Operate

Page 43

Table 23 — Troubleshooting (cont)

 

FAULT

 

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Only Compressor Runs

 

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.

 

 

 

 

 

 

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in Test mode.

 

 

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR

 

 

 

 

 

 

contacts.

 

 

 

 

 

 

Check fan power enable relay operation (if present).

 

 

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

Unit Does Not Operate in

 

 

X

Reversing valve

Set for cooling demand and check 24-vac on RV coil and at control.

Cooling

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

operating engage and disengage RV coil voltage to push valve.

 

 

 

 

X

Thermostat setup

Check for ‘O’ RV setup not ‘B’.

 

 

 

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil.

Insufficient Capacity/

 

X

X

Dirty filter

Replace or clean.

Not Cooling or Heating

 

 

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Properly

 

 

 

 

 

heating

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

cooling

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

X

X

Leaky ductwork

Check supply and return-air temperatures at the unit and at distant

 

 

 

 

 

 

duct registers if significantly different, duct leaks are present.

 

 

 

X

X

Low refrigerant charge

Check superheat and subcooling.

 

 

 

X

X

Restricted metering device

Check superheat and subcooling. Replace.

 

 

 

 

X

Defective reversing valve

Perform RV touch test.

 

 

 

X

X

Thermostat improperly

Check location and for air drafts behind thermostat.

 

 

 

 

 

located

 

 

 

 

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

 

 

X

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

 

 

exchanger

 

 

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

heating

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

 

 

 

 

 

cooling

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

 

 

 

 

 

 

 

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture.

 

 

 

X

 

Air temperature out of range

Bring return-air temperature within design parameters.

 

 

 

 

 

in heating

 

 

 

 

 

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

 

 

exchanger

 

 

 

 

X

X

Unit overcharged

Check superheat and subcooling. Reweigh in charge.

 

 

 

X

X

Non-condensables in

Vacuum system and reweigh in charge.

 

 

 

 

 

system

 

 

 

 

X

X

Restricted metering device

Check superheat and subcooling. Replace.

Low Suction Pressure

 

X

 

Reduced water flow in

Check pump operation or water valve operation/setting.

 

 

 

 

 

heating

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

 

 

range

 

 

 

 

 

X

Reduced airflow in cooling

Check for dirty air filter and clean or replace.

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering air temperature within design

 

 

 

 

 

 

parameters.

 

 

 

X

X

Insufficient charge

Check for refrigerant leaks.

Low Discharge Air

 

X

 

Too high airflow

Check blower.

Temperature in Heating

 

X

 

Poor performance

See ‘Insufficient Capacity’ above.

High Humidity

 

 

X

Too high airflow

Check blower.

 

 

 

 

X

Unit oversized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

LEGEND

 

 

 

 

FP

Freeze Protection

 

 

 

 

HP

High Pressure

 

 

 

 

LED — Light-Emitting Diode

 

 

 

 

LP

Low Pressure

 

 

 

 

RV

Reversing Valve

 

 

 

 

43

Image 43
Contents Safety Considerations ContentsGeneral Installation782 50VQP Unit Physical Data406 442A50-8436 50VQP084-150 Unit DimensionsA50-8437 50VQP168-300 Unit DimensionsA50-8467 A50-8466A50-8468 A50-8472 A50-8469A50-8470 A50-8471A50-8479 A50-8476A50-8477 A50-8478A50-8484 A50-8482A50-8485 A50-8483Trap Condensate Drain A50-8486Field Power Supply Wiring Water Quality Guidelines 50VQP084-168 Unit with Complete C Control Typical A50-843850VQP084-168 with Deluxe D Control Typical A50-8439J6J5 AL1J1 J8 50VQP Unit Electrical Data Standard Unit 50VQP Unit Electrical Data Dual Point Power UnitA50-8441 Field Control WiringPRE-START-UP A50- 6268tf.tifPage 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 456 495 529 561 595 625 656 685 712 741 767 412 455 492 526 563 595 628 658 687 718 745421 459 499 533 569 600 633 663 691 722 749 441 478 513 549 581 614 644 672 703 730 75950VQP120 Blower Performance Data 555 589 618 646 676 702 728 753 779 803 827 850 875 898 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897526 561 592 621 649 679 706 732 758 785 809 833 857 882 544 575 605 633 661 691 717 742 767 794 818 842 867 89050VQP150 Blower Performance Data 618 647 678 708 738 766 793 819 844 867 891 914 937 959 980 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 605 637 666 697 727 755 783 809 835 858 882 905 928 951 97350VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 581 613 646 678 706 735 763 791 817 842 867 889 538 574 609 640 673 703 733 761 788 812 838 863 888 912553 588 620 653 685 715 744 771 796 822 847 872 896 568 602 633 666 697 726 755 782 806 832 857 881 904Deluxe D Control Jumper Settings See Fig Complete C Control Jumper Settings See FigField Selectable Inputs Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UP50VQP Unit Operating Limits Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Water Temperature Change Through Heat ExchangerCoaxial Water Pressure Drop Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume OperationUnits with Aquazone Deluxe D Control Units with Aquazone Complete C ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceRefrigerant Charging TroubleshootingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location A50-8163Troubleshooting Unit Does Not Operate Page Page Catalog No Form 50VQP-C1SI 11-10 Copyright 2010 Carrier CorporationForm 62AQ-1SI Pg CL-1 Replaces New Tab 50VQP START-UP ChecklistII. START-UP Book Catalog NoCooling Cycle Analysis Heating Cycle Analysis