Carrier 50VQP084-300 specifications 50VQP Unit Electrical Data Standard Unit

Page 16

Table 3 — 50VQP Unit Electrical Data — Standard Unit

50VQP UNIT

VOLTAGE

MIN/MAX

BLOWER

 

COMPRESSOR

FAN

TOTAL UNIT

 

MAX FUSE/

 

 

 

 

MOTOR

MCA

SIZE

(V-Ph-Hz)

VOLTAGE

OPTION

qty

 

RLA

LRA

FLA

HACR

 

FLA

 

 

 

 

 

 

 

 

 

 

 

 

084

380/420-3-50

360/440

A,B,C

1

 

11.2

75.0

1.8

13.0

15.8

25

E

1

 

11.2

75.0

2.5

13.7

16.5

25

 

 

 

 

096

380/420-3-50

360/440

A,B,C

1

 

12.2

101.0

2.5

14.7

17.8

25

120

380/420-3-50

360/440

A,B,C

1

 

16.7

111.0

3.6

20.3

24.5

40

E

1

 

16.7

111.0

4.9

21.6

25.8

40

 

 

 

 

150

380/420-3-50

360/440

A,B,C

1

 

18.6

118.0

4.9

23.5

28.2

45

E

1

 

18.6

118.0

7.8

26.4

31.1

45

 

 

 

 

168

380/420-3-50

360/440

A,B,C

2

 

11.2

75.0

3.4

25.8

28.6

35

192

380/420-3-50

360/440

A,B,C

2

 

12.2

101.0

4.9

29.3

32.3

40

240

380/420-3-50

360/440

A,B,C

2

 

16.7

111.0

7.8

41.2

45.4

60

300

380/420-3-50

360/440

A,B,C

2

 

18.6

118.0

7.8

45.0

49.7

60

E

2

 

18.6

118.0

12.2

49.4

54.0

70

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning, and Refrigeration

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

RLA — Rated Load Amps

NOTES:

1.HACR circuit breaker in U.S.A. only.

2.All fuses Class RK-5.

Table 4 — 50VQP Unit Electrical Data — Dual Point Power Unit

50VQP

VOLTAGE

MIN/MAX

BLOWER

 

 

 

COMPRESSOR

 

EMERGENCY POWER SUPPLY

UNIT

(V-Ph-Hz)

VOLTAGE

OPTION

qty

RLA

LRA

TOTAL

COMP

COMP

FAN MOTOR

FAN

FAN

SIZE

 

COMP FLA

MCA

MAX FUSE

FLA

MCA

MAX FUSE

 

 

 

 

 

 

 

084

 

380/420-3-50

360/440

A,B,C

1

11.2

75.0

11.2

14.0

25

1.8

2.3

15

 

E

1

11.2

75.0

11.2

14.0

25

2.5

3.1

15

 

 

 

 

096

 

380/420-3-50

360/440

A,B,C

1

12.2

101.0

12.2

15.3

25

2.5

3.1

15

120

 

380/420-3-50

360/440

A,B,C

1

16.7

111.0

16.7

20.9

35

3.6

4.5

15

 

E

1

16.7

111.0

16.7

20.9

35

4.9

6.1

15

 

 

 

 

150

 

380/420-3-50

360/440

A,B,C

1

18.6

118.0

18.6

23.3

40

4.9

6.1

15

 

E

1

18.6

118.0

18.6

23.3

40

7.8

9.8

15

 

 

 

 

168

 

380/420-3-50

360/440

A,B,C

2

11.2

75.0

22.4

25.2

35

3.4

4.3

15

192

 

380/420-3-50

360/440

A,B,C

2

12.2

101.0

24.4

27.4

35

4.9

6.1

15

240

 

380/420-3-50

360/440

A,B,C

2

16.7

111.0

33.4

37.6

50

7.8

9.8

15

300

 

380/420-3-50

360/440

A,B,C

2

18.6

118.0

37.2

41.9

60

7.8

9.8

15

 

E

2

18.6

118.0

37.2

41.9

60

12.2

15.3

25

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

FLA — Full Load Amps

 

 

 

 

 

 

 

 

 

 

 

HACR — Heating, Air Conditioning, and Refrigeration

 

 

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

MCA

Minimum Circuit Amps

 

 

 

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

 

 

 

NOTES:

1.HACR circuit breaker in U.S.A. only.

2.All fuses Class RK-5.

16

Image 16
Contents Contents Safety ConsiderationsInstallation General50VQP Unit Physical Data 406442 78250VQP084-150 Unit Dimensions A50-843650VQP168-300 Unit Dimensions A50-8437A50-8467 A50-8466A50-8468 A50-8469 A50-8470A50-8471 A50-8472A50-8476 A50-8477A50-8478 A50-8479A50-8482 A50-8485A50-8483 A50-8484A50-8486 Trap Condensate DrainField Power Supply Wiring Water Quality Guidelines A50-8438 50VQP084-168 Unit with Complete C Control TypicalA50-8439 50VQP084-168 with Deluxe D Control TypicalJ6J5 AL1J1 J8 50VQP Unit Electrical Data Dual Point Power Unit 50VQP Unit Electrical Data Standard UnitField Control Wiring PRE-START-UPA50- 6268tf.tif A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 412 455 492 526 563 595 628 658 687 718 745 421 459 499 533 569 600 633 663 691 722 749441 478 513 549 581 614 644 672 703 730 759 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897 526 561 592 621 649 679 706 732 758 785 809 833 857 882544 575 605 633 661 691 717 742 767 794 818 842 867 890 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958 598 623 656 687 715 744 772 799 825 850 872 896 919 942 963605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 538 574 609 640 673 703 733 761 788 812 838 863 888 912 553 588 620 653 685 715 744 771 796 822 847 872 896568 602 633 666 697 726 755 782 806 832 857 881 904 581 613 646 678 706 735 763 791 817 842 867 889Deluxe D Control Jumper Settings See Fig Complete C Control Jumper Settings See FigField Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Cooling Mode Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger 50VQP Unit Operating LimitsApproximate Fluid Volume L Per 30 M of Pipe Antifreeze Percentages by VolumeOperation Coaxial Water Pressure DropUnits with Aquazone Deluxe D Control Units with Aquazone Complete C ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaRefrigerant Charging TroubleshootingAir Coil Fan Motor Removal A50-8163 FP1 and FP2 Thermistor LocationTroubleshooting Unit Does Not Operate Page Page Copyright 2010 Carrier Corporation Catalog No Form 50VQP-C1SI 11-1050VQP START-UP Checklist II. START-UPBook Catalog No Form 62AQ-1SI Pg CL-1 Replaces New TabHeating Cycle Analysis Cooling Cycle Analysis