Carrier 50VQP084-300 specifications A50-8466, A50-8467, A50-8468

Page 6

PROTECTION — Once the units are properly positioned on the jobsite, they must be covered with either a shipping carton, vinyl film, or an equivalent protective covering. Open ends of pipes stored on the jobsite must be capped. This precaution is especially important in areas where painting, plastering, or spraying of fireproof material, etc. is not yet complete. Foreign material that is allowed to accumulate within the units can pre- vent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.

CAUTION

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

INSPECT UNIT — To prepare the unit for installation, com- plete the procedures listed below:

1.Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.

2.Do not remove the packaging until the unit is ready for installation.

3.Verify that the unit’s refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.

4.Inspect all electrical connections. Be sure connections are clean and tight at their terminations.

5.Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.

6.Remove the four 1/4 in. (6 mm) shipping bolts from com- pressor support plate (two bolts on each side) to maxi- mize vibration and sound alternation.

CAUTION

Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.

7.Remove any blower support cardboard from inlet of the blower.

8.Locate and verify any accessory kit located in compressor and/or blower section.

9.Remove any access panel screws that may be difficult to remove once unit is installed.

Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP:

Units are for indoor use only.

Locate in areas where ambient temperatures are between 4.4 C and 37.8 C and relative humidity is no greater than 75%.

Provide sufficient space for water, electrical and duct connections.

NOTE: Water inlets/outlets and high/low voltage electrical access are available on either side of the unit. Electrical ac- cess is also available on the unit front. See Fig. 2 and 3.

Locate unit in an area that allows for easy access and removal of filter and access panels.

NOTE: Unit has full filter frame bottom access for 25, 51, or 102 mm filters.

ALLOW enough space for service personnel to perform maintenance.

Provisions must be made for return air to freely enter the space if unit needs to be installed in a confined area such as a closet.

Step 4 — Mount the Unit — Vertical units are avail- able in rear or front return air configurations.

DISCHARGE CONFIGURATION CONVERSION — To change the discharge configuration of the unit from top dis- charge to straight (right or left) discharge, follow the procedure below. To change the discharge configuration of the unit from straight (right or left) discharge to top discharge, reverse the procedure below.

1. Remove the 3 panels as shown in Fig. 4.

BLOWER ACCESS

PANEL

C-BOX/

MOTOR ACCESS

PANEL

COMPRESSOR

ACCESS PANEL

a50-8466

Fig. 4 — Remove Panels

2.Remove blockoff air handler. Loosen belt and remove. See. Fig. 5.

a50-8467

BLOCKOFF

AIR HANDLER

Fig. 5 — Remove Blockoff Air Handler and Belt

3.Remove 4 bolts from blower panel. Remove 4 bolts (2 bolts on each side) from blower sides. See Fig. 6.

STEP 3

a50-8468

STEP 3

Fig. 6 — Remove Bolts from

Blower Panel and Sides

6

Image 6
Contents Contents Safety ConsiderationsInstallation General442 50VQP Unit Physical Data406 78250VQP084-150 Unit Dimensions A50-843650VQP168-300 Unit Dimensions A50-8437A50-8466 A50-8467A50-8468 A50-8471 A50-8469A50-8470 A50-8472A50-8478 A50-8476A50-8477 A50-8479A50-8483 A50-8482A50-8485 A50-8484A50-8486 Trap Condensate DrainField Power Supply Wiring Water Quality Guidelines A50-8438 50VQP084-168 Unit with Complete C Control TypicalA50-8439 50VQP084-168 with Deluxe D Control TypicalAL1 J6J5J1 J8 50VQP Unit Electrical Data Dual Point Power Unit 50VQP Unit Electrical Data Standard UnitA50- 6268tf.tif Field Control WiringPRE-START-UP A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 441 478 513 549 581 614 644 672 703 730 759 412 455 492 526 563 595 628 658 687 718 745421 459 499 533 569 600 633 663 691 722 749 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 544 575 605 633 661 691 717 742 767 794 818 842 867 890 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897526 561 592 621 649 679 706 732 758 785 809 833 857 882 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 568 602 633 666 697 726 755 782 806 832 857 881 904 538 574 609 640 673 703 733 761 788 812 838 863 888 912553 588 620 653 685 715 744 771 796 822 847 872 896 581 613 646 678 706 735 763 791 817 842 867 889Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs START-UP DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Operating LimitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode 50VQP Unit Operating LimitsOperation Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume Coaxial Water Pressure DropUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaTroubleshooting Refrigerant ChargingAir Coil Fan Motor Removal A50-8163 FP1 and FP2 Thermistor LocationTroubleshooting Unit Does Not Operate Page Page Copyright 2010 Carrier Corporation Catalog No Form 50VQP-C1SI 11-10Book Catalog No 50VQP START-UP ChecklistII. START-UP Form 62AQ-1SI Pg CL-1 Replaces New TabHeating Cycle Analysis Cooling Cycle Analysis