Carrier 50VQP084-300 specifications Water Quality Guidelines

Page 12

Table 2 — Water Quality Guidelines

CONDITION

HX

CLOSED RECIRCULATING†

OPEN LOOP AND RECIRCULATING WELL**

MATERIAL*

 

 

 

Scaling Potential — Primary Measurement

Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.

pH/Calcium Hardness Method

All

N/A

pH < 7.5 and Ca Hardness, <100 ppm

Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)

Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be implemented.

Ryznar Stability Index

All

N/A

 

6.0 - 7.5

 

 

 

 

If >7.5 minimize steel pipe use.

 

 

 

 

 

 

Langelier Saturation Index

All

N/A

 

 

–0.5 to +0.5

 

 

 

If <–0.5 minimize steel pipe use.

 

 

 

 

Based upon 150 F HWG and direct well, 85 F indirect well HX.

Iron Fouling

 

 

 

 

 

 

 

Iron Fe2+ (Ferrous)

All

N/A

 

 

<0.2 ppm (Ferrous)

 

(Bacterial Iron Potential)

If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.

 

 

Iron Fouling

All

N/A

 

 

<0.5 ppm of Oxygen

 

 

 

Above this level deposition will occur.

 

 

 

 

 

 

Corrosion Prevention††

 

 

 

 

 

 

 

pH

All

6 - 8.5

 

6 - 8.5

 

 

 

Monitor/treat as needed.

Minimize steel pipe below 7 and no open tanks with pH <8.

 

 

Hydrogen Sulfide (H2S)

 

 

 

 

<0.5 ppm

 

 

All

N/A

At H2S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.

 

 

Rotten egg smell appears at 0.5 ppm level.

 

 

 

 

 

 

 

 

 

Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.

Ammonia Ion as Hydroxide,

 

 

 

 

<0.5 ppm

 

Chloride, Nitrate and Sulfate

All

N/A

 

 

 

 

 

Compounds

 

 

 

 

 

 

 

Maximum Chloride Levels

 

 

Maximum allowable at maximum water temperature.

 

 

 

50 F (10 C)

 

75 F (24 C)

 

100 F (38 C)

 

Copper

N/A

<20 ppm

 

NR

 

NR

 

Cupronickel

N/A

<150 ppm

 

NR

 

NR

 

304 SS

N/A

<400 ppm

 

<250 ppm

 

<150 ppm

 

316 SS

N/A

<1000 ppm

 

<550 ppm

 

<375 ppm

 

Titanium

N/A

>1000 ppm

 

>550 ppm

 

>375 ppm

Erosion and Clogging

 

 

 

 

 

 

 

Particulate Size and Erosion

 

<10 ppm of particles and a

<10 ppm (<1 ppm “sandfree” for reinjection) of particles and a maximum velocity of

 

 

maximum velocity of 6 fps.

 

All

6 fps. Filtered for maximum 800 micron size. Any particulate that is not removed can

 

Filtered for maximum

 

 

potentially clog components.

 

 

 

800 micron size.

 

 

 

 

 

 

 

 

Brackish

All

N/A

Use cupronickel heat exchanger when concentrations of calcium or sodium chloride

 

are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)

 

 

 

LEGEND

HWG — Hot Water Generator HX — Heat Exchanger

N/A — Design Limits Not Applicable Considering Recirculating Potable Water NR — Application Not Recommended

SSStainless Steel

*Heat exchanger materials considered are copper, cupronickel, 304 SS (stain- less steel), 316 SS, titanium.

†Closed recirculating system is identified by a closed pressurized piping system. **Recirculating open wells should observe the open recirculating design

considerations.

††If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists.

Sulfides in the water quickly oxidize when exposed to air, requiring that no agi- tation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sam- pling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0.

NOTE: To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.

Water Automatic

Control Balance Valve

Valve

Boiler

Drains

Pressure-

Temperature

Plugs

Expansion

Tank

Water Out

Water In

From Pump

Shut-Off

Valve

Strainer – Field-Installed Accessory (16 to 20 mesh recommended for filter sediment)

Fig. 26 — Typical Ground-Water Piping Installation

12

Image 12
Contents Contents Safety ConsiderationsInstallation General50VQP Unit Physical Data 406442 78250VQP084-150 Unit Dimensions A50-843650VQP168-300 Unit Dimensions A50-8437A50-8466 A50-8467A50-8468 A50-8469 A50-8470A50-8471 A50-8472A50-8476 A50-8477A50-8478 A50-8479A50-8482 A50-8485A50-8483 A50-8484A50-8486 Trap Condensate DrainField Power Supply Wiring Water Quality Guidelines A50-8438 50VQP084-168 Unit with Complete C Control TypicalA50-8439 50VQP084-168 with Deluxe D Control TypicalAL1 J6J5J1 J8 50VQP Unit Electrical Data Dual Point Power Unit 50VQP Unit Electrical Data Standard UnitField Control Wiring PRE-START-UPA50- 6268tf.tif A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 412 455 492 526 563 595 628 658 687 718 745 421 459 499 533 569 600 633 663 691 722 749441 478 513 549 581 614 644 672 703 730 759 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897 526 561 592 621 649 679 706 732 758 785 809 833 857 882544 575 605 633 661 691 717 742 767 794 818 842 867 890 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958 598 623 656 687 715 744 772 799 825 850 872 896 919 942 963605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 538 574 609 640 673 703 733 761 788 812 838 863 888 912 553 588 620 653 685 715 744 771 796 822 847 872 896568 602 633 666 697 726 755 782 806 832 857 881 904 581 613 646 678 706 735 763 791 817 842 867 889Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Cooling Mode Unit Start-Up Heating ModeWater Temperature Change Through Heat Exchanger 50VQP Unit Operating LimitsApproximate Fluid Volume L Per 30 M of Pipe Antifreeze Percentages by VolumeOperation Coaxial Water Pressure DropUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaTroubleshooting Refrigerant ChargingAir Coil Fan Motor Removal A50-8163 FP1 and FP2 Thermistor LocationTroubleshooting Unit Does Not Operate Page Page Copyright 2010 Carrier Corporation Catalog No Form 50VQP-C1SI 11-1050VQP START-UP Checklist II. START-UPBook Catalog No Form 62AQ-1SI Pg CL-1 Replaces New TabHeating Cycle Analysis Cooling Cycle Analysis