FIELD SELECTABLE INPUTS
Jumpers and DIP (dual
IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.
Complete C Control Jumper Settings (See Fig. 27)
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3,
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET- TING — Select jumper 2
ALARM RELAY SETTING — Select jumper 1
Complete C Control DIP Switches — The Com- plete C control has 1 DIP switch block with five switches. See Fig. 27.
PERFORMANCE MONITOR (PM) — DIP switch 1 will enable or disable this feature. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor delay. Set DIP switch to OFF for stage 2 in which the compres- sor will have a
NOTE: The alarm relay will not cycle during Test mode if switch is set to OFF, stage 2.
DIP SWITCH 3 — not used. DIP SWITCH 4 — not used.
DIP SWITCH 5 — DIP switch 5 is used to initiate 1 or 3 tries for the FP1 fault. If water freeze protection for the water coil then DIP switch 5 can be set to lock out on the FP1 fault after one try.
Deluxe D Control Jumper Settings (See Fig. 28)
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3,
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET- TING — Select jumper 2
ALARM RELAY SETTING — Select jumper 4
Deluxe D Control DIP Switches — The Deluxe D control has 2 DIP switch blocks. Each DIP switch block has 8 switches and is labeled either S1 or S2 on the circuit board. See Fig. 28.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers the following options for Deluxe D control configuration: Performance Monitor (PM) — Set switch 1 to enable or dis- able performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation — Switch 2 will enable or disable compressor relay staging operation. The compressor relay can be set to turn on with stage 1 or stage 2 call from the thermostat. This setting is used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave ap- plications. In master/slave applications, each compressor and fan will stage according to its switch 2 setting. If switch is set to stage 2, the compressor will have a
NOTE: If DIP switch is set for stage 2, the alarm relay will not cycle during Test mode.
Heating/Cooling Thermostat Type — Switch 3 provides selec- tion of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for cooling stage 2, W1 is used for heating stage 1 and O/W2 is used for heating stage 2. Select ON for heat pump applications. In heat pump mode, Y1 used is for compressor stage 1, Y2 is used for compressor stage 2, W1 is used for heating stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.
O/B Thermostat Type — Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out- put. Select ON for heat pumps with O output. Select OFF for heat pumps with B output.
Dehumidification Fan Mode — Switch 5 provides selection of normal or dehumidification fan mode. Select OFF for dehu- midification mode. The fan speed relay will remain OFF dur- ing cooling stage 2. Select ON for normal mode. The fan speed relay will turn on during cooling stage 2 in normal mode.
Switch 6 — Not used.
Boilerless Operation — Switch 7 provides selection of boil- erless operation and works in conjunction with switch 8. In boilerless operation mode, only the compressor is used for heating when FP1 is above the boilerless changeover tempera- ture set by switch 8 below. Select ON for normal operation or select OFF for boilerless operation.
Boilerless Changeover Temperature — Switch 8 on S1 pro- vides selection of boilerless changeover temperature set point. Select OFF for set point of 10.0 C or select ON for set point of 4.4 C.
If switch 8 is set for 10.0 C, then the compressor will be used for heating as long as the FP1 is above 10.0 C. The com- pressor will not be used for heating when the FP1 is below
10.0C and the compressor will operate in emergency heat mode, staging on EH1 and EH2 to provide heat. If a thermal switch is being used instead of the FP1 thermistor, only the compressor will be used for heating mode when the FP1 termi- nals are closed. If the FP1 terminals are open, the compressor is not used and the control goes into emergency heat mode.
DIP SWITCH BLOCK 2 (S2) — This set of DIP switches is used to configure accessory relay options. See Fig. 28. Switches 1 to 3 — These DIP switches provide selection of Accessory 1 relay options. See Table 13 for DIP switch combinations.
Switches 4 to 6 — These DIP switches provide selection of Accessory 2 relay options. See Table 14 for DIP switch combinations.
33