Carrier 50VQP084-300 Field Selectable Inputs, Complete C Control Jumper Settings See Fig

Page 33

FIELD SELECTABLE INPUTS

Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field.

IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.

Complete C Control Jumper Settings (See Fig. 27)

WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit, DO NOT clip the jumper. To select –12.2 C as the limit, clip the jumper.

AIR COIL FREEZE PROTECTION (FP2) LIMIT SET- TING — Select jumper 2 (JW2-FP2 Low Temp) to choose FP2 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit, DO NOT clip the jumper. To select –12.2 C as the limit, clip the jumper.

ALARM RELAY SETTING — Select jumper 1 (JW1-AL2 Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper.

Complete C Control DIP Switches — The Com- plete C control has 1 DIP switch block with five switches. See Fig. 27.

PERFORMANCE MONITOR (PM) — DIP switch 1 will enable or disable this feature. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.

STAGE 2 — DIP switch 2 will enable or disable compressor delay. Set DIP switch to OFF for stage 2 in which the compres- sor will have a 3-second delay before energizing.

NOTE: The alarm relay will not cycle during Test mode if switch is set to OFF, stage 2.

DIP SWITCH 3 — not used. DIP SWITCH 4 — not used.

DIP SWITCH 5 — DIP switch 5 is used to initiate 1 or 3 tries for the FP1 fault. If water freeze protection for the water coil then DIP switch 5 can be set to lock out on the FP1 fault after one try.

Deluxe D Control Jumper Settings (See Fig. 28)

WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit, DO NOT clip the jumper. To select –12.2 C as the limit, clip the jumper.

AIR COIL FREEZE PROTECTION (FP2) LIMIT SET- TING — Select jumper 2 (JW2-FP2 Low Temp) to choose FP2 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit, DO NOT clip the jumper. To select –12.2 C as the limit, clip the jumper.

ALARM RELAY SETTING — Select jumper 4 (JW4-AL2 Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper. LOW PRESSURE SETTING — The Deluxe D Control can be configured for Low Pressure Setting (LP). Select jumper 1 (JW1-LP Norm Open) for choosing between low pressure in- put normally opened or closed. To configure for normally closed operation, do not clip the jumper. To configure for nor- mally open operation, clip the jumper.

Deluxe D Control DIP Switches — The Deluxe D control has 2 DIP switch blocks. Each DIP switch block has 8 switches and is labeled either S1 or S2 on the circuit board. See Fig. 28.

DIP SWITCH BLOCK 1 (S1) — This set of switches offers the following options for Deluxe D control configuration: Performance Monitor (PM) — Set switch 1 to enable or dis- able performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.

Compressor Relay Staging Operation — Switch 2 will enable or disable compressor relay staging operation. The compressor relay can be set to turn on with stage 1 or stage 2 call from the thermostat. This setting is used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave ap- plications. In master/slave applications, each compressor and fan will stage according to its switch 2 setting. If switch is set to stage 2, the compressor will have a 3-second delay before ener- gizing during stage 2 demand.

NOTE: If DIP switch is set for stage 2, the alarm relay will not cycle during Test mode.

Heating/Cooling Thermostat Type — Switch 3 provides selec- tion of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for cooling stage 2, W1 is used for heating stage 1 and O/W2 is used for heating stage 2. Select ON for heat pump applications. In heat pump mode, Y1 used is for compressor stage 1, Y2 is used for compressor stage 2, W1 is used for heating stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.

O/B Thermostat Type — Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out- put. Select ON for heat pumps with O output. Select OFF for heat pumps with B output.

Dehumidification Fan Mode — Switch 5 provides selection of normal or dehumidification fan mode. Select OFF for dehu- midification mode. The fan speed relay will remain OFF dur- ing cooling stage 2. Select ON for normal mode. The fan speed relay will turn on during cooling stage 2 in normal mode.

Switch 6 — Not used.

Boilerless Operation — Switch 7 provides selection of boil- erless operation and works in conjunction with switch 8. In boilerless operation mode, only the compressor is used for heating when FP1 is above the boilerless changeover tempera- ture set by switch 8 below. Select ON for normal operation or select OFF for boilerless operation.

Boilerless Changeover Temperature — Switch 8 on S1 pro- vides selection of boilerless changeover temperature set point. Select OFF for set point of 10.0 C or select ON for set point of 4.4 C.

If switch 8 is set for 10.0 C, then the compressor will be used for heating as long as the FP1 is above 10.0 C. The com- pressor will not be used for heating when the FP1 is below

10.0C and the compressor will operate in emergency heat mode, staging on EH1 and EH2 to provide heat. If a thermal switch is being used instead of the FP1 thermistor, only the compressor will be used for heating mode when the FP1 termi- nals are closed. If the FP1 terminals are open, the compressor is not used and the control goes into emergency heat mode.

DIP SWITCH BLOCK 2 (S2) — This set of DIP switches is used to configure accessory relay options. See Fig. 28. Switches 1 to 3 — These DIP switches provide selection of Accessory 1 relay options. See Table 13 for DIP switch combinations.

Switches 4 to 6 — These DIP switches provide selection of Accessory 2 relay options. See Table 14 for DIP switch combinations.

33

Image 33
Contents Safety Considerations ContentsGeneral Installation406 50VQP Unit Physical Data442 782A50-8436 50VQP084-150 Unit DimensionsA50-8437 50VQP168-300 Unit DimensionsA50-8466 A50-8467A50-8468 A50-8470 A50-8469A50-8471 A50-8472A50-8477 A50-8476A50-8478 A50-8479A50-8485 A50-8482A50-8483 A50-8484Trap Condensate Drain A50-8486Field Power Supply Wiring Water Quality Guidelines 50VQP084-168 Unit with Complete C Control Typical A50-843850VQP084-168 with Deluxe D Control Typical A50-8439AL1 J6J5J1 J8 50VQP Unit Electrical Data Standard Unit 50VQP Unit Electrical Data Dual Point Power UnitPRE-START-UP Field Control WiringA50- 6268tf.tif A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 421 459 499 533 569 600 633 663 691 722 749 412 455 492 526 563 595 628 658 687 718 745441 478 513 549 581 614 644 672 703 730 759 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 526 561 592 621 649 679 706 732 758 785 809 833 857 882 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897544 575 605 633 661 691 717 742 767 794 818 842 867 890 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 553 588 620 653 685 715 744 771 796 822 847 872 896 538 574 609 640 673 703 733 761 788 812 838 863 888 912568 602 633 666 697 726 755 782 806 832 857 881 904 581 613 646 678 706 735 763 791 817 842 867 889Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger 50VQP Unit Operating LimitsAntifreeze Percentages by Volume Approximate Fluid Volume L Per 30 M of PipeOperation Coaxial Water Pressure DropUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceTroubleshooting Refrigerant ChargingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location A50-8163Troubleshooting Unit Does Not Operate Page Page Catalog No Form 50VQP-C1SI 11-10 Copyright 2010 Carrier CorporationII. START-UP 50VQP START-UP ChecklistBook Catalog No Form 62AQ-1SI Pg CL-1 Replaces New TabCooling Cycle Analysis Heating Cycle Analysis