Carrier 50VQP084-300 Field Control Wiring, Pre-Start-Up, A50- 6268tf.tif, A50-8441, A50-8442

Page 17

Step 9 — Field Control Wiring

THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the Aquazone™ control board. See Fig. 27-31.

COMPRESSOR CONTACTOR

CAPACITOR

COMPLETE C CONTROL

NOTE: The A terminal should only be used with 24 volt signals — not line voltage signals.

WATER SOLENOID VALVES — An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water

LINE

LOAD

 

TRANSFORMER

a50-8197

J1

Y

W

R

S1

 

 

CFM

 

 

 

SW1

 

O

 

SW2

 

G

SW3

 

 

 

SW4

 

 

 

SW5

 

Y2

G

SW6

 

 

 

SW7

 

 

 

SW8

 

Y1

G

SW9

 

OFF

ON

 

 

G

G

G DEHUM

 

 

TB1

 

 

 

 

 

 

R

C

Y2 Y1 G

O

W

C

R DH AL1 A

A

AL1

THERMOSTAT CONNECTION

hammer. Figure 33 shows typical wiring for a 24-vac external solenoid valve. Figures 34 and 35 illustrate typical slow closing water control valve wiring for Taco 500 Series and Taco ESP Series valves. Slow closing valves take approximately 60 sec. to open (very little water will flow before 45 sec.). Once fully open, an end switch allows the compressor to be energized (on- ly on valves with end switches). Only relay or triac based elec- tronic thermostats should be used with slow closing valves. When wired as shown, the slow closing valve will operate properly with the following notations:

1.

The valve will remain open during a unit lockout.

2.

The valve will draw approximately 25 to 35 VA through

 

the “Y” signal of the thermostat.

NOTE: Low voltage connector may be removed for easy installation.

Fig. 31 — Low Voltage Field Wiring

WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at –1.1 C. In earth loop applications, jumper JW3 should be clipped to change the setting to –12.2 C when using antifreeze in colder earth loop applications. See Fig. 32.

a50- 6268tf.tif

AQUAZONE CONTROL (Complete C Control Shown)

Fig. 32 — Typical Aquazone™ Control Board

Jumper Locations

AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for –1.1 C and should not need adjusting.

ACCESSORY CONNECTIONS — Terminal labeled A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 33. Refer to the specific unit wiring schematic for details.

TERMINAL STRIP P2

C

TYPICAL

24 VAC WATER VALVE

A

Fig. 33 — Typical Aquazone Accessory Wiring

(Control D Shown)

IMPORTANT: Connecting a water solenoid valve can overheat the anticipators of electromechanical thermo- stats. Only use relay based electronic thermostats.

C

Y1

a50-8441

 

2

AMV

1

3

TACO VALVE

 

HEATER SWITCH

 

C

Y1

 

THERMOSTAT

 

Fig. 34 — AMV Valve Wiring

a50-8442

Fig. 35 — Taco SBV Valve Wiring

PRE-START-UP

System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:

1.Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for 3-phase units.

2.Fuses, breakers and wire are correct size.

3.Low voltage wiring is complete.

4.Piping and system flushing is complete.

5.Air is purged from closed loop system.

6.System is balanced as required. Monitor if necessary.

7.Isolation valves are open.

8.Water control valves or loop pumps are wired.

17

Image 17
Contents Safety Considerations ContentsGeneral Installation406 50VQP Unit Physical Data442 782A50-8436 50VQP084-150 Unit DimensionsA50-8437 50VQP168-300 Unit DimensionsA50-8468 A50-8466A50-8467 A50-8470 A50-8469A50-8471 A50-8472A50-8477 A50-8476A50-8478 A50-8479A50-8485 A50-8482A50-8483 A50-8484Trap Condensate Drain A50-8486Field Power Supply Wiring Water Quality Guidelines 50VQP084-168 Unit with Complete C Control Typical A50-843850VQP084-168 with Deluxe D Control Typical A50-8439J1 J8 AL1J6J5 50VQP Unit Electrical Data Standard Unit 50VQP Unit Electrical Data Dual Point Power UnitPRE-START-UP Field Control WiringA50- 6268tf.tif A50-8441Page 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 421 459 499 533 569 600 633 663 691 722 749 412 455 492 526 563 595 628 658 687 718 745441 478 513 549 581 614 644 672 703 730 759 456 495 529 561 595 625 656 685 712 741 76750VQP120 Blower Performance Data 526 561 592 621 649 679 706 732 758 785 809 833 857 882 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897544 575 605 633 661 691 717 742 767 794 818 842 867 890 555 589 618 646 676 702 728 753 779 803 827 850 875 89850VQP150 Blower Performance Data 598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958605 637 666 697 727 755 783 809 835 858 882 905 928 951 973 618 647 678 708 738 766 793 819 844 867 891 914 937 959 98050VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 553 588 620 653 685 715 744 771 796 822 847 872 896 538 574 609 640 673 703 733 761 788 812 838 863 888 912568 602 633 666 697 726 755 782 806 832 857 881 904 581 613 646 678 706 735 763 791 817 842 867 889Field Selectable Inputs Complete C Control Jumper Settings See FigDeluxe D Control Jumper Settings See Fig DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Heating Mode Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger 50VQP Unit Operating LimitsAntifreeze Percentages by Volume Approximate Fluid Volume L Per 30 M of PipeOperation Coaxial Water Pressure DropComplete C and Deluxe D Board System Test Units with Aquazone Complete C ControlUnits with Aquazone Deluxe D Control Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceAir Coil Fan Motor Removal TroubleshootingRefrigerant Charging FP1 and FP2 Thermistor Location A50-8163Troubleshooting Unit Does Not Operate Page Page Catalog No Form 50VQP-C1SI 11-10 Copyright 2010 Carrier CorporationII. START-UP 50VQP START-UP ChecklistBook Catalog No Form 62AQ-1SI Pg CL-1 Replaces New TabCooling Cycle Analysis Heating Cycle Analysis