Step 9 — Field Control Wiring
THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the Aquazone™ control board. See Fig.
COMPRESSOR CONTACTOR | CAPACITOR | COMPLETE C CONTROL |
NOTE: The A terminal should only be used with 24 volt signals — not line voltage signals.
WATER SOLENOID VALVES — An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water
LINE | LOAD |
|
TRANSFORMER
a50-8197
J1
Y
W | R | S1 |
| |
| CFM |
| ||
|
| SW1 |
| |
O |
| SW2 |
| |
G | SW3 |
| ||
|
| SW4 |
| |
|
| SW5 |
| |
Y2 | G | SW6 |
| |
|
| SW7 |
| |
|
| SW8 |
| |
Y1 | G | SW9 |
| |
OFF | ON | |||
|
| |||
G | G | G DEHUM |
|
| TB1 |
|
|
|
|
|
|
R | C | Y2 Y1 G | O | W | C | R DH AL1 A | A | AL1 |
THERMOSTAT CONNECTION
hammer. Figure 33 shows typical wiring for a
1. | The valve will remain open during a unit lockout. |
2. | The valve will draw approximately 25 to 35 VA through |
| the “Y” signal of the thermostat. |
NOTE: Low voltage connector may be removed for easy installation.
Fig. 31 — Low Voltage Field Wiring
WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at
a50- 6268tf.tif
AQUAZONE CONTROL (Complete C Control Shown)
Fig. 32 — Typical Aquazone™ Control Board
Jumper Locations
AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for
ACCESSORY CONNECTIONS — Terminal labeled A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 33. Refer to the specific unit wiring schematic for details.
TERMINAL STRIP P2
C
TYPICAL
24 VAC WATER VALVE
A
Fig. 33 — Typical Aquazone Accessory Wiring
(Control D Shown)
IMPORTANT: Connecting a water solenoid valve can overheat the anticipators of electromechanical thermo- stats. Only use relay based electronic thermostats.
C | Y1 |
a50-8441
| 2 | AMV |
1 | 3 | TACO VALVE |
| HEATER SWITCH |
|
C | Y1 |
|
THERMOSTAT |
|
Fig. 34 — AMV Valve Wiring
a50-8442
Fig. 35 — Taco SBV Valve Wiring
PRE-START-UP
System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:
1.Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for
2.Fuses, breakers and wire are correct size.
3.Low voltage wiring is complete.
4.Piping and system flushing is complete.
5.Air is purged from closed loop system.
6.System is balanced as required. Monitor if necessary.
7.Isolation valves are open.
8.Water control valves or loop pumps are wired.
17