Carrier 50VQP084-300 specifications Aquazone Deluxe D Control LED Indica, Service

Page 39

Retry Mode — In Retry mode, the status LED will start to flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to again satisfy the thermostat used to terminal Y. Once the ther- mostat input calls are satisfied, the control will continue normal operation.

NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.

Aquazone™ Deluxe D Control LED Indica-

tors — There are 3 LED indicators on the Deluxe D control:

STATUS LED — Status LED indicates the current status or mode of the Deluxe D control. The Status LED light is green. TEST LED — Test LED will be activated any time the De- luxe D control is in Test mode. The Test LED light is yellow.

FAULT LED — Fault LED light is red. The fault LED will always flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 and appear as 1 fast flash alternating with a 10-second pause. See Table 22.

SERVICE

Perform the procedures outlined below periodically, as indicated.

IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the com- pressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.

IMPORTANT: All refrigerant discharged from this unit must be recovered without exception. Technicians must fol- low industry accepted guidelines and all local, state and fed- eral statutes for the recovery and disposal of refrigerants.

IMPORTANT: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians which meet local, state and federal proficiency requirements.

IMPORTANT: To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect switch before servicing unit.

Filters — Filters must be clean for maximum performance. Inspect filters every month under normal operating conditions. replace when necessary.

IMPORTANT: Units should never be operated with- out a filter.

Water Coil — Keep all air out of the water coil. Check open loop systems to be sure the well head is not allowing air to infiltrate the water line. Always keep lines airtight.

Inspect heat exchangers regularly, and clean more frequent- ly if the unit is located in a “dirty” environment. The heat exchanger should be kept full of water at all times. Open loop systems should have an inverted P trap placed in the discharge line to keep water in the heat exchanger during off cycles. Closed loop systems must have a minimum of 100 kPa during the summer and 275 kPa during the winter.

Check P trap frequently for proper operation.

IMPORTANT: To avoid fouled machinery and extensive unit clean-up, DO NOT operate units without filters in place. DO NOT use equipment as a temporary heat source during construction.

Condensate Drain Pans — Check condensate drain pans for algae growth twice a year. If algae growth is apparent, consult a water treatment specialist for proper chemical treat- ment. The application of an algaecide every three months will typically eliminate algae problems in most locations.

Refrigerant System — Verify air and water flow rates are at proper levels before servicing. To maintain sealed circuit- ry integrity, do not install service gages unless unit operation appears abnormal.

Condensate Drain Cleaning — Clean the drain line and unit drain pan at the start of each cooling season. Check flow by pouring water into drain. Be sure trap is filled to main- tain an air seal.

Air Coil Cleaning — Remove dirt and debris from evap- orator coil as required by condition of the coil. Clean coil with a stiff brush, vacuum cleaner, or compressed air. Use a fin comb of the correct tooth spacing when straightening mashed or bent coil fins.

Condenser Cleaning — Water-cooled condensers may require cleaning of scale (water deposits) due to improperly maintained closed-loop water systems. Sludge build-up may need to be cleaned in an open water tower system due to induced contaminants.

Local water conditions may cause excessive fouling or pitting of tubes. Condenser tubes should therefore be cleaned at least once a year, or more often if the water is contaminated.

Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information.

CAUTION

Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturer’s instructions. Fail- ure to follow these safety precautions could result in per- sonal injury or equipment or property damage.

Clean condensers with an inhibited hydrochloric acid solu- tion. The acid can stain hands and clothing, damage concrete, and, without inhibitor, damage steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.

Warm solution acts faster, but cold solution is just as effec- tive if applied for a longer period.

GRAVITY FLOW METHOD — Do not add solution faster than vent can exhaust the generated gases.

When condenser is full, allow solution to remain overnight, then drain condenser and flush with clean water. Follow acid manufacturer’s instructions. See Fig. 36.

FORCED CIRCULATION METHOD — Fully open vent pipe when filling condenser. The vent may be closed when condenser is full and pump is operating. See Fig. 37.

Regulate flow to condenser with a supply line valve. If pump is a nonoverloading type, the valve may be fully closed while pump is running.

For average scale deposit, allow solution to remain in con- denser overnight. For heavy scale deposit, allow 24 hours.

39

Image 39
Contents Safety Considerations ContentsGeneral Installation782 50VQP Unit Physical Data406 442A50-8436 50VQP084-150 Unit DimensionsA50-8437 50VQP168-300 Unit DimensionsA50-8466 A50-8467A50-8468 A50-8472 A50-8469A50-8470 A50-8471A50-8479 A50-8476A50-8477 A50-8478A50-8484 A50-8482A50-8485 A50-8483Trap Condensate Drain A50-8486Field Power Supply Wiring Water Quality Guidelines 50VQP084-168 Unit with Complete C Control Typical A50-843850VQP084-168 with Deluxe D Control Typical A50-8439AL1 J6J5J1 J8 50VQP Unit Electrical Data Standard Unit 50VQP Unit Electrical Data Dual Point Power UnitA50-8441 Field Control WiringPRE-START-UP A50- 6268tf.tifPage 50VQP084 Blower Performance Data 50VQP096 Blower Performance Data 456 495 529 561 595 625 656 685 712 741 767 412 455 492 526 563 595 628 658 687 718 745421 459 499 533 569 600 633 663 691 722 749 441 478 513 549 581 614 644 672 703 730 75950VQP120 Blower Performance Data 555 589 618 646 676 702 728 753 779 803 827 850 875 898 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897526 561 592 621 649 679 706 732 758 785 809 833 857 882 544 575 605 633 661 691 717 742 767 794 818 842 867 89050VQP150 Blower Performance Data 618 647 678 708 738 766 793 819 844 867 891 914 937 959 980 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958598 623 656 687 715 744 772 799 825 850 872 896 919 942 963 605 637 666 697 727 755 783 809 835 858 882 905 928 951 97350VQP168 Blower Performance Data 50VQP192 Blower Performance Data BkW 3020.8 Sheave/Mtr 50VQP240 Blower Performance Data 605 633 660 689 714 739 763 790 813 836 858 882 904 50VQP300 Blower Performance Data 581 613 646 678 706 735 763 791 817 842 867 889 538 574 609 640 673 703 733 761 788 812 838 863 888 912553 588 620 653 685 715 744 771 796 822 847 872 896 568 602 633 666 697 726 755 782 806 832 857 881 904Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UP50VQP Unit Operating Limits Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Water Temperature Change Through Heat ExchangerCoaxial Water Pressure Drop Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume OperationUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlComplete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica ServiceTroubleshooting Refrigerant ChargingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location A50-8163Troubleshooting Unit Does Not Operate Page Page Catalog No Form 50VQP-C1SI 11-10 Copyright 2010 Carrier CorporationForm 62AQ-1SI Pg CL-1 Replaces New Tab 50VQP START-UP ChecklistII. START-UP Book Catalog NoCooling Cycle Analysis Heating Cycle Analysis