Compact Station
2 Safety
The qualified skilled personnel are responsible for safety.
The member of personnel who is responsible for the equipment must ensure that only suitably qualified persons are allowed access to the equipment.
To ensure safety in the electrical operating areas, these areas should be lockable; i.e. suitable locking systems should be installed by the owner on all exterior doors of the compact station.
2.1Installation Location
The equipment is intended for use outdoors as an enclosed electrical unit.
•Environmental conditions: ( technical data) in accordance with DIN EN
•Freely accessible air vents for heat dissipation.
•Ground pressure: min. 250 kN/m2 ( excavation plan) Refer to the technical data for additional criteria.
When selecting the installation location, regional regulations governing noise emissions must be taken into account.
Do not install the equipment in areas subject to flooding or those with a high groundwater level.
2.2Lightning Protection
The connection to the potential equalisation system of the foundation provides the equipment with effective protection against lightning strikes.
The manufacturer’s specifications must be implemented effectively in order to provide the photovoltaic system with suitable lightning protection measures.
Further safety information can be found in the Protect PV Inverter Operating Instructions (BAL).