AEG TKS-CS operating instructions Maintenance Schedule, Ongoing, Monthly, Every 6 months

Page 34

Compact Station TKS-CS - Operating Instructions

10.4Maintenance Schedule

The maintenance schedule does not release the owner from his obligation to create his own maintenance and operating instructions for the location and to document them fully as quickly as possible.

Maintenance instructions supplied by component manufacturers must be included in the detailed specifications relating to the scope of maintenance work.

i

For recurrent measurements and measurements after repair

work as per BGV A3, compliance with the DIN VDE 0105-100

inspection intervals is mandatory.

Ongoing

Check the measured results of the equipment for plausibility.

Replace defective measuring instrumentation at the end of production.

Data bus:

Ongoing functional testing in operation.

Monthly

Test lamps and replace diodes if required.

Check the function of the system's internal measuring instrumentation by comparing the values during operation with the values displayed.

Check the function of the measuring instruments and accessory systems required for operation and servicing.

Check the interior area and equipment for moisture and, if necessary, establish the cause and dry the equipment.

Clean the interior areas of the compact station (operating area).

Every 6 months

Check the fastenings and function of the electrical connections of all components in the compact station.

Check the function of the fault current, differential current and fault voltage protective circuits.

Carry out recurrent measurements in accordance with DIN VDE 0105.

Check the axial ventilator for damage and whether it is working correctly (rotation), and repair or replace if necessary.

Check the axial ventilator and weather-proof cover for dirt, and clean if necessary.

Check the function of the overtemperature warning system by opening the sensor path.

Page 34 of 39

8000043213 BAL

Image 34
Contents TKS-CS Revision Service Status Revision Date NameTable of Contents Decommissioning and Dismantling Mailservice.aegpss@aegps.com Appropriate Use General InformationValidity List of AbbreviationsInstallation Location SafetyLightning Protection Scope of Delivery Available to orderEquipment Specifications StructureDimension DimensionsLow-Voltage Box AC Connections Low-voltage boxes exampleISO Small Distribution Box Communications Cabinet PV LoG-MH Central Earthing SystemMedium-Voltage System No. H07V-KNameTransformer 3 4 5 4Functional Description Transfer stationTransport Suspended loads during transportAssembly Setting in PlaceHinge side of the door when closing InstallationConnection Design Torque Communication Interface PV.LoG-MH Medium-voltage system example Medium-Voltage Transformer Tightening Torques for Screw Connections Operation Start-upWorking with voltages up to 1 kV Residual voltage from capacitors ServicingContact with voltage Contact with leakage currentHeat generation in resistors Insufficient ventilation of equipmentEntry of water into electrical equipment Obligation to Keep a Written Record Maintenance and Inspection Visual Inspection CleaningTesting/Measuring Functional TestReplacing the Axial Ventilator Care LubricationRotating parts Replacement Work Replacing the Transformer Testing after RepairsRepairs Roof structure Station frame Station roofReplacing the MV Switchgear Partial top view TKS-CS exampleMonthly Maintenance ScheduleOngoing Every 6 monthsEvery 2 years Storing Spare PartsAnnually Every 4 yearsRemoving Connection Cables Decommissioning and DismantlingDismantling Disposal Statutory Provisions Chemical System ComponentsCompact Station TKS-CS Operating Instructions List of Tables List of Figures