Carrier 48/50PD05 manual Temperature Compensated Start, Setting Up the System

Page 22

48/50PD

will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control. When the indoor fan turns on after the 40 or 45 second delay the indoor fan will run at 100% fan speed.

Gas Heat Staging

When additional heat is required, power is supplied to the second stage of the main gas valve. When the space temperature is 0.5F above the Occupied Heat Set Point (SetpointOHSP) or Unoccupied Heat Set Point (SetpointUHSP) power is removed from the second stage of the main gas valve and to the IGC W1 terminal. Both stage 1 and stage 2 of the gas valve closes, interrupting the flow of gas to the main burners.

Gas Heat Shut Down

If power to the IGC W1 terminal lasted less than 1 minute, the heating cycle will not terminate until 1 minute after power is applied to the W1 terminal of the IGC board. If the over temperature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 minutes. Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control. A LED indicator is provided on the IGC to monitor operation. The IGC is located in the gas burner section and can be accessed by opening the gas access door. During normal operation, the LED is continuously on.

Gas Heat with Economizer

When there is a call for heat as described above the indoor fan will operate at the Supply Fan Maximum Speed (ConfigurationUNITFS.MX) configuration setting and the economizer outdoor air damper will move to the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) position. The economizer outdoor air damper is closed when the indoor fan is not operating.

Electric Heating Mode Using Space Temperature Sensor T55, T56, or T58 (50PD Units Only)

For electric heat units with factory installed electric heat, the Type of Heat Installed (ConfigurationHEATHT.TY) will be factory set to a value of 2 and the Number of Heat Stages (ConfigurationHEATN.HTR) will be factory set to match the installed heater. If electric heat is installed in the field the value for Number of Heat Stages (ConfigurationHEATN.HTR) must be changed to match the number of heat stages installed.

Heat will not operate if the outdoor temperature is greater that the value configured for the Heating Lockout Temperature (ConfigurationHEATHT.LO), Heat Minimum On Time (ConfigurationHEATMRT.H) and Heat Minimum Off Time (ConfigurationHEATMOT.H). Timeguards apply to both stages of heating. Factory defaults values are 2 minute s ON and 2 minutes OFF.

If the indoor fan control is configured to cycle with the heating demand by setting Fan ON When Occupied Heat Minimum On Time (ConfigurationUNITOC.FN) to NO, the fan will stop after a delay configured by Fan-off Delay, Elect Heat (ConfigurationHEATFOD.E). The factory default for Fan-off Delay, Elect Heat (ConfigurationHEATFOD.E) is 30 seconds.

The electronic control uses information from the space sensor to determine the number of heat stages required. Once the number of stages needed for heating is determined, either Heat Stage 1 Relay (OutputsHEATHT.1), or Heat Stage 1 Relay

(OutputsHEATHT.1) and Heat Stage 2 Relay

(OutputsHEATHT.2) outputs will be turned on. See Gas Heating Mode Using Space Temperature Sensor for more information.

Supply-Air Temperature Sensor (SAT)

The SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) affects the Supply Air Temperature (TemperaturesAIR.TSAT) value displayed. This configuration is accessible via the Scrolling Marquee on the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H).

When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) =DSBL, the Supply Air Temperature (TemperaturesAIR.TSAT) value on the Scrolling Marquee and the CCN tables will be forced to zero when heat outputs come ON and for 5 minutes after. The default Supply Air Temperature (TemperaturesAIR.TSAT) location is at the fan inlet, upstream of the heat section.

When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) = ENBL, the Supply Air Temperature (TemperaturesAIR.TSAT) sensor reading is displayed at the Scrolling Marquee and the CCN tables during heating mode. This setting should only be used if the original SAT sensor wires are removed from the Main Base Board (MBB) and replaced by an accessory SAT sensor located in the supply duct downstream of the heat section. There are then two supply air temperature limits that become active, the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L) the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U). Any time the supply air temperature rises above the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L) the heat staging will be limited to what is currently on and no additional stages can be added until the supply air temperature falls

below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L). If the supply air temperature rises above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then heating will be reduced by removing a heat stage. That stage can not be added

again until the Supply Air Temperature (TemperaturesAIR.TSAT) falls below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L). If the supply air temperature stays above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then another stage will be removed after the Heat Stage Decrease Time (ConfigurationHEATH.DEC).

Temperature Compensated Start

This logic is used when the unit is in the unoccupied state. The control will calculate early Start Bias time based on Space Temperature deviation from the occupied cooling and heating set points. This will allow the control to start the unit so that the space is at conditioned levels when the occupied period starts. This is required for ASHRAE 90.1 compliance.

Setting Up the System

The settings for temperature compensated start can be found in the local display under ConfigurationUNIT.

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

TCS.C

Temp.Cmp.Strt.Cool Factr

0 --- 60

min

TCSTCOOL

TCS.H

Temp.Cmp.Strt.Heat Factr

0 --- 60

min

TCSTHEAT

Temp Comp Strt Cool Factr (TCS.C)

This is the factor for the start time bias equation for cooling.

Temp Comp Strt Heat Factr (TCS.H)

This is the factor for the start time bias equation for heating.

IMPORTANT: Temperature compensated start is disabled when these factors are set to 0.

22

Image 22
Contents Table of Contents Safety Considerations What to do if you smell gasGeneral Basic Control UsageSystem Pilott and Touch Pilot Devices Scrolling Marquee Mode and Menu Display StructureCCN Tables and Display START-UP Evaporator Fan Power SupplyInternal Wiring Condenser Fans and MotorsControls Quick SET-UP Accessories CCN CommunicationFilter Status Setting an Occupied Time Schedule Weekdays Only for 730 toFan Status TimeclockIndependent Outputs Service TestProgramming Operating Schedules Fan TestThird Party Control Controls OperationUnit Configuration ModesGeneral Operating Sequence Occupancy DeterminationCompressor Operation Indoor Fan OperationEconomizer Operation Outdoor Fan OperationUnoccupied Free Cooling Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point For units with Enthalpy Control Ventilation ModeFor all units with Economizers Demand Control VentilationHeating Modes Supply-Air Temperature Sensor SAT Gas Heat Start-UpTemp Comp Strt Cool Factr TCS.C Temperature Compensated StartSetting Up the System Temp Comp Strt Heat Factr TCS.HCarrier Comfort Network Ccnr Configuration Demand LimitRestart Procedure TroubleshootingAlarm Handling Complete Unit StoppageAlarms and Alerts Communication FailuresAlert Code T075 Supply Air Temperature Thermistor Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T074 Space Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code A200 Linkage Timeout Comm Failure Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code A404 Fire ShutdownAlert Code T415 IAQ Input Out of Range Alert Code T416 OAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Digital Scroll Controller DSC Troubleshooting Cooling Service AnalysisFlash Code 4 ⎯ Locked Rotor DSC Red LED Flash CodesEconomizer Troubleshooting Economizer Service AnalysisVariable Frequency Drive VFD Troubleshooting Heating TroubleshootingPhase Loss Protection IGC Service Analysis Logic LED IGC Board LED Alarm CodesElectric Heat Service Analysis FlashRefrigerant Temperatures Thermistor TroubleshootingAir Temperatures Thermistor/Temperature Sensor CheckForcing Inputs and Outputs Transducer TroubleshootingSensor Trim Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F Pressure Voltage Major System ComponentsGeneral Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Setting Main Base Board MBBMBB Connections FIL.SCenter of the board. Do not change this setting Economizer Control Board ECBECB Connections RM.OCModulation Board AUX1 CommunicationDigital Scroll Control Board DSC CMP.AVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardLow Voltage Terminal Strip TB1Scrolling Marquee Display Accessory Navigatort DisplayField-Installed Accessories Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor T-58 Space Temperature Sensor AveragingSpace Temperature Sensor Averaging Service Periodic Clean Water Rinse CleaningCoil Maintenance and Cleaning Recommendation Routine Cleaning of Round-Tube Coil SurfacesOutdoor-Air Inlet Screens Condensate Drain PanFilters Main Burner 48PDEvaporator Fan Performance Adjustment Evaporator Fan Service and ReplacementLubrication Variable Frequency Drive VFD Replacement Evaporator Fan Belt Tension AdjustmentCondenser-Fan Adjustment Evacuation Economizer Operation During Power FailureVerify Sensor Performance Refrigerant ChargeAltitude Compensation 48PG03-07 Gas Valve AdjustmentPuronR Refrigerant Elevation Natural GAS PropaneFilter Drier High AltitudeMain Burners Protective DevicesRelief Devices Replacement PartsDiagnostic LEDs Compressor Sound ShieldMode RUN Status Appendix a Local Display and CCN TablesOnly StrtAlrmdisp = CCN Generic = CCNMode Temperatures Mode Service TestMode Pressures Mode SET Points Mode InputsMode Outputs OutputsMode Configuration MRT.H HT.TYHTR MOT.HII.CF IA.CFIA.FN II.FNSPT.T TrimSPT.C SAT.CMode Time Clock CCN only TablesMode Operating Modes EN.LO OK.HTACT.H AQ.DVExpansion Range Units Mode AlarmsExpansion Range Default CCN CCN Point CCN Write TABLE/SUB---TABLE StatusAppendix B VFD Information VFD Terminal DesignationsVFD Configurations VFD Modes Standard Display ModeVFD Operation Start Up with AssistantChanged Parameters Mode Parameters ModeStart-Up Assistant Mode Drive Parameter Backup ModeVFD Diagnostics History VFD MaintenanceCorrecting Alarms Heat Sink101---105 Fault Codes201---206 1002 10001001 1003Maintenance Intervals Alarm CodesMaintenance Interval Control Panel Cleaning Main Fan ReplacementBattery Replacement Fan Performance 48PDE05 Vertical Units Appendix C START-UP DataFan Performance 48PDD05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Available External Static Pressure in. wg Fan Performance 48PDE06 Vertical UnitsRpm Bhp 1500 CFMFan Performance 48PDE05 Horizontal Units Fan Performance 48PDD05 Horizontal UnitsBhp Rpm Fan Performance 48PDD06 Horizontal Units 1026 1086 1144 1199 1253Fan Performance 48PDE06 Horizontal Units Fan Performance 50PD05 Vertical Units Fan Performance 50PD06 Vertical UnitsFan Performance 50PD05 Horizontal Units Bhp Rpm 1500General Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Control SET Point and Configuration LOG Indicate Unit Settings belowCCN Point Entry 103 104 Unit START-UP Checklist PRE-START-UP106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.