Carrier 48/50PD05 manual Verify Sensor Performance, Economizer Operation During Power Failure

Page 64

48/50PD

C08570

Fig. 33 - Condenser-Fan Adjustment

Verify Sensor Performance

Verify that thermistor, transducer, and switch inputs are reading correctly. These values can be accessed through the Scrolling Marquee display in the Temperatures, Pressures, and Inputs menus. Some values will depend on configuration choices. Refer to the Control Set Up Checklist completed for the specific unit installation and to the configuration tables in Appendix A.

Economizer Operation During Power Failure

Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Do not manually operate damper motor.

Evacuation

Proper evacuation of the system will remove noncondensables and ensure a tight, dry system before charging. Evacuate from both high and low side ports. Never use the system compressor as a vacuum pump. Refrigerant tubes and indoor coil should be evacuated to 500 microns. Always break a vacuum with dry nitrogen. The two possible methods are the deep vacuum method and the triple evacuation method.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a minimum vacuum of 500 microns and a vacuum gauge capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 34.)

 

5000

 

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

LEAK IN

 

3500

 

 

 

 

 

 

MICRONS

 

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

VACUUM TIGHT

 

 

 

 

 

 

 

TOO WET

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

TIGHT

 

 

 

 

 

 

 

DRY SYSTEM

 

 

 

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

 

MINUTES

 

 

 

 

 

 

 

 

 

 

 

C06264

Fig. 34 - Deep Vacuum Graph

Triple Evacuation Method

The triple evacuation method should only be used when vacuum pump is capable of pumping down to 28-in. of mercury and system does not contain any liquid water. Proceed as follows:

1.Pump system down to 28-in. of mercury and allow pump to continue operating for an additional 15 minutes.

2.Close service valves and shut off vacuum pump.

3.Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.

4.Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system, absorbing moisture.

5.Repeat this procedure. System will then contain minimal amounts of contaminants and water vapor.

Refrigerant Charge

Amount of refrigerant charge is listed on unit nameplate. Refer to Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during charging procedure.

Puron(R-410A) refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.

!WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personal injury, death and/or equipment damage.

Puron (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment. Gauge set, hoses, and recovery system must be designed to handle Puron refrigerant. If unsure about equipment, consult the equipment manufacturer.

IMPORTANT: Do not use recycled refrigerant as it may contain contaminants.

No Charge in the System

Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to unit nameplate). Verify charge using the charging chart via “Charge in the System.”

Charge in the System

IMPORTANT: The circuit must be running in normal cooling mode with the compressor capacity at 100%. The VFD must be running at max fan speed and indoor airflow must be within specified air quantity limits for cooling (See Appendix D). All outdoor fans must be on and running at high speed. Use the Cooling Service Test Outdoor Fan Override function to start all outdoor fans.

An accurate pressure gauge and temperature-sensing device is required. Charging is accomplished by ensuring the proper amount of liquid subcooling. Connect pressure gauge to the compressor discharge service valve. Connect temperature sensing device to the liquid line between the condenser and the TXV (thermostatic expansion valve), and insulate it so that ambient temperature does not affect reading. Use the cooling charging chart (Fig. 35-36) to determine if additional charge is needed or if some charge needs to be removed from the system.

To Use the Cooling Charging Chart

Use the temperature and pressure readings, and find the intersection point on the cooling charging chart. If intersection point on chart is above line, add refrigerant. If intersection point on chart is below line, carefully recover some of the charge. Recheck suction pressure as charge is adjusted.

64

Image 64
Contents Table of Contents Safety Considerations What to do if you smell gasGeneral Basic Control UsageSystem Pilott and Touch Pilot Devices Scrolling Marquee Mode and Menu Display StructureCCN Tables and Display START-UP Power Supply Internal WiringEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP Accessories CCN CommunicationSetting an Occupied Time Schedule Weekdays Only for 730 to Fan StatusFilter Status TimeclockService Test Programming Operating SchedulesIndependent Outputs Fan TestThird Party Control Controls OperationUnit Configuration ModesGeneral Operating Sequence Occupancy DeterminationCompressor Operation Indoor Fan OperationEconomizer Operation Outdoor Fan OperationUnoccupied Free Cooling Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point Ventilation Mode For all units with EconomizersFor units with Enthalpy Control Demand Control VentilationHeating Modes Supply-Air Temperature Sensor SAT Gas Heat Start-UpTemperature Compensated Start Setting Up the SystemTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HCarrier Comfort Network Ccnr Configuration Demand LimitTroubleshooting Alarm HandlingRestart Procedure Complete Unit StoppageAlarms and Alerts Communication FailuresAlert Code T073 Outdoor Air Temperature Thermistor Failure Alert Code T074 Space Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code T155 Serial Eeprom Storage Failure Error Alarm Code A156 Critical Serial Eeprom Storage Fail ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T415 IAQ Input Out of Range Alert Code T416 OAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Digital Scroll Controller DSC Troubleshooting Cooling Service AnalysisFlash Code 4 ⎯ Locked Rotor DSC Red LED Flash CodesEconomizer Troubleshooting Economizer Service AnalysisVariable Frequency Drive VFD Troubleshooting Heating TroubleshootingPhase Loss Protection IGC Service Analysis Logic IGC Board LED Alarm Codes Electric Heat Service AnalysisLED FlashThermistor Troubleshooting Air TemperaturesRefrigerant Temperatures Thermistor/Temperature Sensor CheckForcing Inputs and Outputs Transducer TroubleshootingSensor Trim Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F Major System Components GeneralPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Setting Main Base Board MBBMBB Connections FIL.SCenter of the board. Do not change this setting Economizer Control Board ECBECB Connections RM.OCModulation Board AUX1 CommunicationDigital Scroll Control Board DSC CMP.AVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardLow Voltage Terminal Strip TB1Accessory Navigatort Display Field-Installed AccessoriesScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor T-58 Space Temperature Sensor AveragingSpace Temperature Sensor Averaging Service Cleaning Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesCondensate Drain Pan FiltersOutdoor-Air Inlet Screens Main Burner 48PDEvaporator Fan Performance Adjustment Evaporator Fan Service and ReplacementLubrication Variable Frequency Drive VFD Replacement Evaporator Fan Belt Tension AdjustmentCondenser-Fan Adjustment Economizer Operation During Power Failure Verify Sensor PerformanceEvacuation Refrigerant ChargeGas Valve Adjustment PuronR RefrigerantAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneHigh Altitude Main BurnersFilter Drier Protective DevicesReplacement Parts Diagnostic LEDsRelief Devices Compressor Sound ShieldMode RUN Status Appendix a Local Display and CCN TablesStrt Alrmdisp = CCNOnly Generic = CCNMode Temperatures Mode Service TestMode Pressures Mode SET Points Mode InputsMode Outputs OutputsMode Configuration HT.TY HTRMRT.H MOT.HIA.CF IA.FNII.CF II.FNTrim SPT.CSPT.T SAT.CMode Time Clock CCN only TablesMode Operating Modes OK.HT ACT.HEN.LO AQ.DVMode Alarms Expansion Range Default CCN CCN Point CCN WriteExpansion Range Units TABLE/SUB---TABLE StatusAppendix B VFD Information VFD Terminal DesignationsVFD Configurations Standard Display Mode VFD OperationVFD Modes Start Up with AssistantParameters Mode Start-Up Assistant ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics VFD Maintenance Correcting AlarmsHistory Heat Sink101---105 Fault Codes201---206 1000 10011002 1003Maintenance Intervals Alarm CodesMaintenance Interval Control Panel Cleaning Main Fan ReplacementBattery Replacement Appendix C START-UP Data Fan Performance 48PDD05 Vertical UnitsFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Fan Performance 48PDE06 Vertical Units Rpm Bhp 1500Available External Static Pressure in. wg CFMFan Performance 48PDE05 Horizontal Units Fan Performance 48PDD05 Horizontal UnitsBhp Rpm Fan Performance 48PDD06 Horizontal Units 1026 1086 1144 1199 1253Fan Performance 48PDE06 Horizontal Units Fan Performance 50PD05 Vertical Units Fan Performance 50PD06 Vertical UnitsFan Performance 50PD05 Horizontal Units Bhp Rpm 1500General Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Control SET Point and Configuration LOG Indicate Unit Settings belowCCN Point Entry 103 104 Unit START-UP Checklist PRE-START-UP106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.