Carrier 48/50PD05 manual Control SET Point and Configuration LOG, Indicate Unit Settings below

Page 101

CONTROL SET POINT AND CONFIGURATION LOG

Model Number: _____________________________

Software Versions: ___________________________

Serial Number: ______________________________

MBB: CESR131320-- _ _

Date: ______________________________________

ECB: CESR131249-- _ _

Technician: _________________________________

MARQ: CESR131171-- _ _

INDICATE UNIT SETTINGS BELOW

Control Type:

Thermostat/T55 Space Temp./T-56 Space Temp./T-58 Space Temp.

 

 

 

Set Points:

Cooling

Occupied: _______________

Unoccupied: __________________

 

 

 

Heating

Occupied: _______________

 

Unoccupied: __________________

 

 

 

 

 

Table 65 — MODE - CONFIGURATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ITEM

EXPANSION

 

RANGE

UNITS

 

DEFAULT

CCN

CCN POINT

ENTRY

 

 

TABLE/SUB---TABLE

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

 

 

 

 

 

 

 

SERVICE

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

 

 

DISP

Display Configuration

 

 

 

 

 

DISPLAY

 

 

METR

Metric Display

 

 

On/Off

 

 

Off

 

DISPUNIT

 

LANG

Language Selection

 

 

0=English

 

 

0

 

LANGUAGE

 

 

 

 

 

1=Spanish

 

 

 

 

 

 

 

 

 

 

2=French

 

 

 

 

 

 

 

 

 

 

3=Portuguese

 

 

 

 

 

 

PROT

Password Enable

 

 

Enable/Disable

 

 

Disable

 

PASS_EBL

 

PSWD

Service Password

 

 

0000 to 9999

 

 

1111

 

PASSWORD

 

TEST

Test Display LEDs

 

 

On/Off

 

 

Off

(display only, not in

DISPTEST

 

 

 

 

 

 

 

 

 

table)

 

 

UNIT

Unit Configuration

 

 

 

 

 

 

UNIT

 

 

S.DLY

Startup Delay

 

 

0 to 600

sec

 

30

 

STARTDLY

 

OC.FN

Fan On When Occupied

 

Yes/No

 

 

Yes

 

OCC_FAN

 

IDF.F

Shut Down on IDF Failure

 

Yes/No

 

 

Yes

 

FATALFAN

 

FS.MX

Supply Fan Maximum

 

80 to 100

%

 

100

 

SPEEDMAX

 

 

Speed

 

 

 

 

 

 

 

 

 

FS.MN

Supply Fan Minimum Speed

 

10 to 40

%

 

20

 

SPEEDMIN

 

FS.VM

Vent Mode Fan Speed

 

40 to 100

^F

 

50

 

SPEEDVNT

 

FN.SW

Fan Status Switch

 

 

0=No Switch

 

 

0: no FIOP

 

FANSTCFG

 

 

 

 

 

1=Normal Open

 

 

1: FIOP

 

 

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

 

FL.SW

Filter Status Switch

 

 

0=No Switch

 

 

0: no FIOP

 

FILSTCFG

 

 

 

 

 

1=Normal Open

 

 

1: FIOP

 

 

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

 

FS.SW

Fire Shutdown Switch

 

0=No Switch

 

 

0: no FIOP

 

SHTDNCFG

 

 

 

 

 

1=Normal Open

 

 

1: FIOP

 

 

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

 

RM.SW

Remote Occupancy Switch

 

0=No Switch

 

 

0

 

REMOCCFG

 

 

 

 

 

1=Normal Open

 

 

 

 

 

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

 

RH.S

RH Sensor on OAQ Input

 

Yes/No

 

 

No

 

RH_OAQ

 

RH.SW

Space Humidity Switch

 

0=No Switch

 

 

0

 

HUMSTCFG

 

 

 

 

 

1=Normal Open

 

 

 

 

 

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

 

TCS.C

Temp Cmp Strt Cool Factr

 

0 to 60

mins

 

0

 

TCSTCOOL

 

TCS.H

Temp Cmp Strt Heat Factr

 

0 to 60

mins

 

0

 

TCSTHEAT

 

COOL

Cooling Configuration

 

 

 

 

 

COOL_CFG

 

 

MIN.C

Min Compressor Capacity

 

15 to 80

%

 

70

 

MIN_CAPC

 

FS.CD

Fan Speed Control Demand

 

1 to 9.9

^F

 

3

 

SPEEDDMD

 

MRT.C

Compressor Min On Time

 

120 to 999

sec

 

180

 

MIN_ON

 

MOT.C

Compressor Min Off Time

 

300 to 999

sec

 

300

 

MIN_OFF

 

RST.C

Runtime to Reset Strikes

 

120 to 999

sec

 

300

 

MIN_ON_S

 

FOD.C

Fan---off Delay, Mech Cool

 

0 to 600

sec

 

60

 

COOL_FOD

 

CS.A1

Current Sensing A1

 

 

Enable/Disable

 

 

Disable: reserved for

 

A1_SENSE

 

 

 

 

 

 

 

 

future use

 

 

 

 

 

 

 

 

 

 

DO NOT ENABLE

 

 

 

C.LO

Compressor Lockout Temp

 

0 to 100F

dF

 

0

 

OATLCOMP

 

ALM.N

Alert Each Strike

 

 

Yes//No

 

 

Yes

 

ALM_NOW

 

SAT

Supply Air Temperature

 

 

 

 

 

 

 

 

SASP

Cool Supply Air Setpoint

 

45 to 75

dF

 

65

 

SASP

 

SA.MU

SASP Maximum Reset Up

 

0 to 20

^F

 

10

 

SASPMAXU

 

SA.MD

SASP Maximum Reset

 

---20 to 0

^F

 

---10

 

SASPMAXD

 

 

Down

 

 

 

 

 

 

 

 

 

SAT.U

Minimum SAT Upper Level

 

35.0 to 65.0

dF

 

60

 

SATMIN_H

 

SAT.L

Minimum SAT Lower Level

 

35.0 to 65.0

dF

 

45

 

SATMIN_L

 

SST

Low Suction Control

 

 

 

 

 

 

 

 

 

SST.O

Suction OK Temperature

 

10 to 50

dF

 

18

 

SSTOK

 

SST.1

Low Suction --- Level 1

 

10 to 50

dF

 

20

 

SSTLEV1

 

SST.2

Low Suction --- Level 2

 

5 to 50

dF

 

15

 

SSTLEV2

 

SST.3

Low Suction --- Level 3

 

0 to 50

dF

 

10

 

SSTLEV3

 

PSI.D

Ckt A Minimum Pressure

 

0 to 500

psig

 

20

 

DELTAP_A

 

OFC

Outdoor Fan Control

 

 

 

 

 

 

 

 

1.MXP

Fan Lev1 Max Pressure

 

100 to 500

psig

 

450

 

LEV1MAXP

 

2.MNP

Fan Lev2 Min Pressure

 

100 to 500

psig

 

200

 

LEV2MINP

 

2.ON

Fan Lev2 On Temperature

 

0 to 100

F

 

55

 

LEV2ON

 

2.OFF

Fan Lev2 Off Temperature

 

0 to 100

F

 

45

 

LEV2OFF

 

48/50PD

101

Image 101
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralCCN Tables and Display Scrolling Marquee Mode and Menu Display StructureSystem Pilott and Touch Pilot Devices START-UP Internal Wiring Power SupplyEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP CCN Communication AccessoriesFan Status Setting an Occupied Time Schedule Weekdays Only for 730 toFilter Status TimeclockProgramming Operating Schedules Service TestIndependent Outputs Fan TestControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationUnoccupied Free Cooling Outdoor Fan OperationEconomizer Operation Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point For all units with Economizers Ventilation ModeFor units with Enthalpy Control Demand Control VentilationHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATSetting Up the System Temperature Compensated StartTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HDemand Limit Carrier Comfort Network Ccnr ConfigurationAlarm Handling TroubleshootingRestart Procedure Complete Unit StoppageCommunication Failures Alarms and AlertsAlert Code T074 Space Temperature Thermistor Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingPhase Loss Protection Heating TroubleshootingVariable Frequency Drive VFD Troubleshooting IGC Service Analysis Logic Electric Heat Service Analysis IGC Board LED Alarm CodesLED FlashAir Temperatures Thermistor TroubleshootingRefrigerant Temperatures Thermistor/Temperature Sensor CheckSensor Trim Transducer TroubleshootingForcing Inputs and Outputs Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F General Major System ComponentsPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripField-Installed Accessories Accessory Navigatort DisplayScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Coil Maintenance and Cleaning Recommendation CleaningPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesFilters Condensate Drain PanOutdoor-Air Inlet Screens Main Burner 48PDLubrication Evaporator Fan Service and ReplacementEvaporator Fan Performance Adjustment Condenser-Fan Adjustment Evaporator Fan Belt Tension AdjustmentVariable Frequency Drive VFD Replacement Verify Sensor Performance Economizer Operation During Power FailureEvacuation Refrigerant ChargePuronR Refrigerant Gas Valve AdjustmentAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneMain Burners High AltitudeFilter Drier Protective DevicesDiagnostic LEDs Replacement PartsRelief Devices Compressor Sound ShieldAppendix a Local Display and CCN Tables Mode RUN StatusAlrmdisp = CCN StrtOnly Generic = CCNMode Pressures Mode Service TestMode Temperatures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration HTR HT.TYMRT.H MOT.HIA.FN IA.CFII.CF II.FNSPT.C TrimSPT.T SAT.CCCN only Tables Mode Time ClockMode Operating Modes ACT.H OK.HTEN.LO AQ.DVExpansion Range Default CCN CCN Point CCN Write Mode AlarmsExpansion Range Units TABLE/SUB---TABLE StatusVFD Terminal Designations Appendix B VFD InformationVFD Configurations VFD Operation Standard Display ModeVFD Modes Start Up with AssistantStart-Up Assistant Mode Parameters ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics Correcting Alarms VFD MaintenanceHistory Heat Sink201---206 Fault Codes101---105 1001 10001002 1003Maintenance Interval Alarm CodesMaintenance Intervals Battery Replacement Main Fan ReplacementControl Panel Cleaning Fan Performance 48PDD05 Vertical Units Appendix C START-UP DataFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Rpm Bhp 1500 Fan Performance 48PDE06 Vertical UnitsAvailable External Static Pressure in. wg CFMBhp Rpm Fan Performance 48PDD05 Horizontal UnitsFan Performance 48PDE05 Horizontal Units 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.