Carrier 48/50PD05 manual CCN Communication, Accessories

Page 8

Table 3 — Application Specific Configurations

ITEM

EXPANSION

DEFAULT

UNITS

DISPLACEMENT

SINGLE ZONE

VENTILATION

VAV

 

 

 

 

 

 

 

 

 

 

SASP

Cool Supply Air Setpoint

65

dF

65

55

 

 

 

 

 

 

FS.MX

Supply Fan Maximum Speed

100

%

100

100

 

 

 

 

 

 

FS.MN

Supply Fan Maximum Speed

20

%

20

70

 

 

 

 

 

 

FS.VM

Vent Mode Fan Speed

50

F

50

50

 

 

 

 

 

 

MIN.C

Min Compressor Capacity

70

%

15

70

 

 

 

 

 

 

FS.CD

Fan Speed Control Demand

3

F

3

3

 

 

 

 

 

 

SA.MU

SASP Maximum Reset Up

10

F

3

5

 

 

 

 

 

 

SA.MD

SASP Maximum Reset Down

---10

F

---3

---5

 

 

 

 

 

 

MP.MX

Econ Min at Max Fanspeed

30

%

30

30

 

 

 

 

 

 

PE1.C

Power Exhaust Stage 1 CFM

600

cfm

600

600

 

 

 

 

 

 

IDF.C

Indoor Fan Max Speed CFM

1600 (05)

cfm

1600 (05)

1600 (05)

2000 (06)

2000 (06)

2000 (06)

 

 

 

 

 

 

 

 

 

48/50PD

System Pilot - Communication Space Sensor

Install the System Pilot and connect the CCN communication bus from it to the units CCN connection on the low voltage terminal board. Configure the unit’s CCN communication element number, bus number, and baud rate. Refer to the System Pilot’s installation instructions for configuring it to be used as a space temperature and attaching it to a unit.

Gen III TEMP Monitor - Linkage Communication

Thermostat (33CSTMT-01)

Install the linkage thermostat. Connect the CCN communication bus from the Stat to the CCN terminals on the field connection terminal board located at the unit control box. Configure the unit’s CCN communication element number, bus number, and baud rate. Refer to the Linkage Thermostat’s installation instructions for configuring the Stat and additional information about it.

Space Humidistat Control

The humidistat input is provided on the field connection terminal

board. The Space Humidity Switch configuration, ConfigurationUNITRH.SW, identifies the normally open or normally closed status of this input at LOW humidity. Humidistat 1 terminal is the 24 VAC source for dry contact and the Humidistat 2 terminal is the signal input.

Relative Humidity Sensor Control

For units with the economizer option (with the ECB-economizer control board), the humidity sensor input is provided on the field connection terminal board. The sensor can be used in addition to or instead of a humidistat. The RH Sensor on OAQ Input configuration, ConfigurationUNITRH.S=YES, identifies that the sensor is being used instead of an OAQ sensor. Terminal 1 is the 24vdc loop power and Terminal 4 is the 4-20 mA signal input. Refer to the Field Installed Accessories for more information.

CCN Communication

Configure ConfigurationCCNCCN.A to desired element number (Default is 1). Configure ConfigurationCCNCCN.B to desired bus number (Default is 0). Configure ConfigurationCCNBAUD to desired code number for baud rate (Default is 3 = 9600 baud).

Accessories

Below are quick configuration settings for field installed accessories. If these accessories were installed by the factory, they will already be configured. See the Field-Installed Accessories section, third party control, control connection tables, and CCN or Display parameter tables for any accessories not mentioned below and any additional information on accessories.

Economizer

If an Economizer accessory was field installed, the unit must be configured for it by setting ConfigurationECONEC.EN to YES. The default settings for the other economizer configurations

should be satisfactory. If they need to be changed, additional information about these configuration settings can be found in the Economizer section.

Power Exhaust

If a Power Exhaust accessory was field installed, the unit must be configured for it by setting ConfigurationECONPE.EN to ENBL. The default settings for the other power exhaust configurations should be satisfactory. If they need to be changed, additional information about these configurations can be found in the Power Exhaust section.

Electric Heat

If an Electric Heat accessory was field installed, the unit must be configured for it by setting ConfigurationHEATHT.TY to a value of 2. The number of electric heat stages must be configured by setting ConfigurationHEATN.HTR per the installed heater.

Fire Shutdown

If a Fire Shutdown or Smoke Detector accessory was field installed, the unit must be configured for it by setting ConfigurationUNITFS.SW to normally open (1) or normally closed (2) when there is not a fire alarm. Normally open (1) is the preferred configuration.

IMPORTANT: On standard units, the fire shutdown input is the terminals Fire Shutdown 1 and 2.

Outdoor Enthalpy

If an Outdoor Enthalpy accessory was field installed, the unit must be configured for it by setting ConfigurationECONEN.SW, identifies the normally open or normally closed status of this input when the outdoor enthalpy is low.

IAQ Switch

If an IAQ Switch accessory was field installed, the unit must be configured for it by setting ConfigurationAIR.QII.CF, identifies the normally open or normally closed status of this input when the indoor air quality value is low (good) and also selects the unit response to this input.

IMPORTANT: An IAQ switch cannot be used if an enthalpy switch is already on this input.

IAQ Sensor

If an CO2 Sensor accessory was field installed, the unit must be configured for it by setting ConfigurationAIR.QIA.CF selects the unit response to this input. Default conversion to 0 to 2000 ppm.

OAQ Sensor

If an Outdoor Air Quality Sensor accessory was field installed, the unit must be configured for it by setting ConfigurationAIR.Q OA.CF selects the unit response to this input. Default conversion to 0 to 2000 ppm.

8

Image 8
Contents Table of Contents Safety Considerations What to do if you smell gasGeneral Basic Control UsageCCN Tables and Display Scrolling Marquee Mode and Menu Display StructureSystem Pilott and Touch Pilot Devices START-UP Power Supply Internal WiringEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP Accessories CCN CommunicationSetting an Occupied Time Schedule Weekdays Only for 730 to Fan StatusFilter Status TimeclockService Test Programming Operating SchedulesIndependent Outputs Fan TestThird Party Control Controls OperationUnit Configuration ModesGeneral Operating Sequence Occupancy DeterminationCompressor Operation Indoor Fan OperationUnoccupied Free Cooling Outdoor Fan OperationEconomizer Operation Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point Ventilation Mode For all units with EconomizersFor units with Enthalpy Control Demand Control VentilationHeating Modes Supply-Air Temperature Sensor SAT Gas Heat Start-UpTemperature Compensated Start Setting Up the SystemTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HCarrier Comfort Network Ccnr Configuration Demand LimitTroubleshooting Alarm HandlingRestart Procedure Complete Unit StoppageAlarms and Alerts Communication FailuresAlert Code T073 Outdoor Air Temperature Thermistor Failure Alert Code T074 Space Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code T155 Serial Eeprom Storage Failure Error Alarm Code A156 Critical Serial Eeprom Storage Fail ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T415 IAQ Input Out of Range Alert Code T416 OAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Digital Scroll Controller DSC Troubleshooting Cooling Service AnalysisFlash Code 4 ⎯ Locked Rotor DSC Red LED Flash CodesEconomizer Troubleshooting Economizer Service AnalysisPhase Loss Protection Heating TroubleshootingVariable Frequency Drive VFD Troubleshooting IGC Service Analysis Logic IGC Board LED Alarm Codes Electric Heat Service AnalysisLED FlashThermistor Troubleshooting Air TemperaturesRefrigerant Temperatures Thermistor/Temperature Sensor CheckSensor Trim Transducer TroubleshootingForcing Inputs and Outputs Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F Major System Components GeneralPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Setting Main Base Board MBBMBB Connections FIL.SCenter of the board. Do not change this setting Economizer Control Board ECBECB Connections RM.OCModulation Board AUX1 CommunicationDigital Scroll Control Board DSC CMP.AVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardLow Voltage Terminal Strip TB1Accessory Navigatort Display Field-Installed AccessoriesScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor T-58 Space Temperature Sensor AveragingSpace Temperature Sensor Averaging Service Cleaning Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesCondensate Drain Pan FiltersOutdoor-Air Inlet Screens Main Burner 48PDLubrication Evaporator Fan Service and ReplacementEvaporator Fan Performance Adjustment Condenser-Fan Adjustment Evaporator Fan Belt Tension AdjustmentVariable Frequency Drive VFD Replacement Economizer Operation During Power Failure Verify Sensor PerformanceEvacuation Refrigerant ChargeGas Valve Adjustment PuronR RefrigerantAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneHigh Altitude Main BurnersFilter Drier Protective DevicesReplacement Parts Diagnostic LEDsRelief Devices Compressor Sound ShieldMode RUN Status Appendix a Local Display and CCN TablesStrt Alrmdisp = CCNOnly Generic = CCNMode Pressures Mode Service TestMode Temperatures Mode SET Points Mode InputsMode Outputs OutputsMode Configuration HT.TY HTRMRT.H MOT.HIA.CF IA.FNII.CF II.FNTrim SPT.CSPT.T SAT.CMode Time Clock CCN only TablesMode Operating Modes OK.HT ACT.HEN.LO AQ.DVMode Alarms Expansion Range Default CCN CCN Point CCN WriteExpansion Range Units TABLE/SUB---TABLE StatusAppendix B VFD Information VFD Terminal DesignationsVFD Configurations Standard Display Mode VFD OperationVFD Modes Start Up with AssistantParameters Mode Start-Up Assistant ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics VFD Maintenance Correcting AlarmsHistory Heat Sink201---206 Fault Codes101---105 1000 10011002 1003Maintenance Interval Alarm CodesMaintenance Intervals Battery Replacement Main Fan ReplacementControl Panel Cleaning Appendix C START-UP Data Fan Performance 48PDD05 Vertical UnitsFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Fan Performance 48PDE06 Vertical Units Rpm Bhp 1500Available External Static Pressure in. wg CFMBhp Rpm Fan Performance 48PDD05 Horizontal UnitsFan Performance 48PDE05 Horizontal Units Fan Performance 48PDD06 Horizontal Units 1026 1086 1144 1199 1253Fan Performance 48PDE06 Horizontal Units Fan Performance 50PD05 Vertical Units Fan Performance 50PD06 Vertical UnitsFan Performance 50PD05 Horizontal Units Bhp Rpm 1500General Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Control SET Point and Configuration LOG Indicate Unit Settings belowCCN Point Entry 103 104 Unit START-UP Checklist PRE-START-UP106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.