APPENDIX B - VFD INFORMATION (CONT)

 

 

Table 42 — ALARM CODES

 

 

 

ALARM

ALARM NAME

DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION

CODE

IN PANEL

 

 

 

 

2001

---

Reserved

 

 

 

2002

---

Reserved

 

 

 

2003

---

Reserved

 

 

 

2004

DIR LOCK

The change in direction being attempted is not allowed. Do not attempt to change the direction of motor rotation, or

Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe).

 

 

 

 

 

2005

 

Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT

I/O COMM

TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on

 

 

line.

 

 

 

2006

Al1 LOSS

Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections. Check the

parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault operation (3001).

 

 

 

 

 

2007

Al2 LOSS

Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections. Check

parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation (3001).

 

 

 

 

 

 

 

Panel communication is lost and either the VFD is in local control mode (the control panel displays HAND), or the

2008

PANEL LOSS

VFD is in remote control mode (AUTO) and is parameterized to accept start/stop, direction or reference from the

control panel. To correct, check the communication lines and connections, Parameter 3002 PANEL LOSS, and

 

 

 

 

parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM).

 

 

 

2009

---

Reserved

 

 

 

2010

 

Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a Motor Overload

MOT OVERTEMP

fault trip may be near. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009).

 

 

Check the temperature sensors and Group 35 parameters.

 

 

 

2011

 

Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near. Check that the

UNDERLOAD

motor and drive ratings match (motor is NOT undersized for the drive). Check the settings on parameters 3013 to

 

 

3015.

 

 

 

2012

MOTOR STALL

Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near.

 

 

 

2013*

AUTORESET

This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To

control automatic reset, use parameter group 31 (AUTOMATIC RESET).

 

 

 

 

 

2014

AUTOCHANGE

This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81 (PFA) and the

Pump Alternation macro.

 

 

 

 

 

2015

PFA INTERLOCK

This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when

Autochange is used), or a speed regulated motor (when Autochange is not used).

 

 

 

 

 

2016

---

Reserved

 

 

 

2017*

OFF BUTTON

This alarm indicates that the OFF button has been pressed.

 

 

 

2018

PID SLEEP

This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID

sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122 through 4126.

 

 

 

 

 

2019

ID RUN

The VFD is performing an ID run.

 

 

 

2020

OVERRIDE

Override mode is activated.

 

 

 

2021

START ENABLE 1

This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use parameter 1608. To

MISSING

correct, check the digital input configuration and the communication settings.

 

 

 

 

2022

START ENABLE 2

This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use parameter1609. To

MISSING

correct, check the digital input configuration and the communication settings.

 

 

 

 

2023

EMERGENCY STOP

Emergency stop is activated.

 

 

 

*This alarm is not indicated by a relay output, even when the relay output is configured to indicate alarm conditions, parameter 1401 RELAY OUTPUT = 5 (ALARM) or 16 (FLT/ALARM).

48/50PD

Table 43 — MAINTENANCE INTERVALS

MAINTENANCE

INTERVAL

Heat sink temperature check and cleaning

Every 6 to 12 months (depending on the dustiness of the environment)

Main cooling fan replacement

Every five years

 

 

HVAC Control panel battery change

Every ten years

 

 

89

Image 89
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralCCN Tables and Display Scrolling Marquee Mode and Menu Display StructureSystem Pilott and Touch Pilot Devices START-UP Internal Wiring Power SupplyEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP CCN Communication AccessoriesFan Status Setting an Occupied Time Schedule Weekdays Only for 730 toFilter Status TimeclockProgramming Operating Schedules Service TestIndependent Outputs Fan TestControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationUnoccupied Free Cooling Outdoor Fan OperationEconomizer Operation Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point For all units with Economizers Ventilation ModeFor units with Enthalpy Control Demand Control VentilationHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATSetting Up the System Temperature Compensated StartTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HDemand Limit Carrier Comfort Network Ccnr ConfigurationAlarm Handling TroubleshootingRestart Procedure Complete Unit StoppageCommunication Failures Alarms and AlertsAlert Code T074 Space Temperature Thermistor Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingPhase Loss Protection Heating TroubleshootingVariable Frequency Drive VFD Troubleshooting IGC Service Analysis Logic Electric Heat Service Analysis IGC Board LED Alarm CodesLED FlashAir Temperatures Thermistor TroubleshootingRefrigerant Temperatures Thermistor/Temperature Sensor CheckSensor Trim Transducer TroubleshootingForcing Inputs and Outputs Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F General Major System ComponentsPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripField-Installed Accessories Accessory Navigatort DisplayScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Coil Maintenance and Cleaning Recommendation CleaningPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesFilters Condensate Drain PanOutdoor-Air Inlet Screens Main Burner 48PDLubrication Evaporator Fan Service and ReplacementEvaporator Fan Performance Adjustment Condenser-Fan Adjustment Evaporator Fan Belt Tension AdjustmentVariable Frequency Drive VFD Replacement Verify Sensor Performance Economizer Operation During Power FailureEvacuation Refrigerant ChargePuronR Refrigerant Gas Valve AdjustmentAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneMain Burners High AltitudeFilter Drier Protective DevicesDiagnostic LEDs Replacement PartsRelief Devices Compressor Sound ShieldAppendix a Local Display and CCN Tables Mode RUN StatusAlrmdisp = CCN StrtOnly Generic = CCNMode Pressures Mode Service TestMode Temperatures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration HTR HT.TYMRT.H MOT.HIA.FN IA.CFII.CF II.FNSPT.C TrimSPT.T SAT.CCCN only Tables Mode Time ClockMode Operating Modes ACT.H OK.HTEN.LO AQ.DVExpansion Range Default CCN CCN Point CCN Write Mode AlarmsExpansion Range Units TABLE/SUB---TABLE StatusVFD Terminal Designations Appendix B VFD InformationVFD Configurations VFD Operation Standard Display ModeVFD Modes Start Up with AssistantStart-Up Assistant Mode Parameters ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics Correcting Alarms VFD MaintenanceHistory Heat Sink201---206 Fault Codes101---105 1001 10001002 1003Maintenance Interval Alarm CodesMaintenance Intervals Battery Replacement Main Fan ReplacementControl Panel Cleaning Fan Performance 48PDD05 Vertical Units Appendix C START-UP DataFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Rpm Bhp 1500 Fan Performance 48PDE06 Vertical UnitsAvailable External Static Pressure in. wg CFMBhp Rpm Fan Performance 48PDD05 Horizontal UnitsFan Performance 48PDE05 Horizontal Units 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.