Carrier 48/50PD05 manual Cooling Modes

Page 17

exceed Econ Min at Max Fan Speed (ConfigurationECONMP.MX) or IAQ Override Position (ConfigurationAIR.QOVR.P) to provide economizer cooling.

IA.CF = 3 (Control Minimum Position)

When IA.CF = 3, an external 4 to 20 mA source is used to set the minimum position. The 4mA signal corresponds to 0% and the 20 mA signal corresponds to 100%. In this mode, configuration such

as Econ Min at Max Fan Speed (ConfigurationECONMP.MX), Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) and the economizer minimum position and DCV minimum position curves in figure 3 are not used.

If the indoor fan is not operating, the economizer position will be zero. The damper position may exceed the economizer minimum position to provide economizer cooling.

IAQ (Switch Input)

Indoor air quality can also be measured using a switch input. For the purpose of specifying the type of switch input, low CO2 levels are considered normal. The IAQ switch input is defined by the IAQ Switch Input Config (ConfigurationAIR.QII.CF). Enthalpy and IAQ are controlled by the same switch input and therefore cannot be used simultaneously.

II.CF = 0 (NO IAQ)

The II.CF = 0, configuration signifies that there is no IAQ switch input. The damper will operate at the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) and corresponding damper position curve based on indoor fan speed when the space is occupied and the indoor fan is on.

II.CF = 1 (DCV Normally Open)

II.CF = 2 (DCV Normally Closed)

The Demand Control Ventilation (DCV) allows the economizer minimum position to be decreased when there is no IAQ problem. If IAQ is low, the economizer minimum position is Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) when the indoor fan is operating at Supply Fan Maximum Speed (ConfigurationUNITFS.MX). If IAQ is high, the economizer minimum position is Econ Min at Max Fan Speed (ConfigurationECONMP.MX) when the indoor fan is

operating at Supply Fan Maximum Speed (ConfigurationUNITFS.MX).

II.CF = 3 (Override Normally Open)

II.CF = 4 (Override Normally Closed)

The damper override function permits absolute positioning of the economizer damper for ventilation purposes. The override is active when IAQ is high and inactive when IAQ is low. The override position is configured by the IAQ Override Position (ConfigurationAIR.QOVR.P).

Outdoor Air Quality (Analog Input)

The ComfortLink TM control is configured for outdoor air quality sensors which provide a 4 to 20 mA signal corresponding to 0 to 2000 ppm CO2. If a field supplied sensor has a different range, the ppm display range must be reconfigured by entering new values

for the OAQ Sensor Value at 4mA (ConfigurationAIR.QO.4M) and OAQ Sensor Value at 20mA (ConfigurationAIR.QO.20M).

OA.CF = 0 (NO OAQ)

This signifies that there is no outdoor air sensor installed. The default value of OAQ is 400 ppm CO2.

OA.CF = 1 (DCV)

The outdoor air quality sensor analog input is the value of OAQ.

OA.CF = 2 (OAQ Lockout)

The outdoor air quality analog input is only used to lock out the outdoor ventilation. The economizer commanded position is set to 0% when the CO2 ppm exceeds the OAQ lockout value

configured for the OAQ Lockout Limit (ConfigurationAIR.QAQ.L). The default value for OAQ

Lockout Limit (ConfigurationAIR.QOAQ.L) is 600 ppm CO2.

Fan Enable (Analog IAQ Sensor)

The DCV algorithm will operate whenever the building is occupied and the indoor fan is operating or whenever the IAQ algorithm has caused the indoor fan to operate. The IAQ Analog

Fan Config (ConfigurationAIR.QIA.FN) determines whether or not the IAQ algorithm can turn on the indoor fan. If the indoor fan is not operating, the economizer position will be zero. The damper position may exceed Econ Min at Max Fan Speed (ConfigurationECONMP.MX) and corresponding damper position curve to provide economizer cooling.

IA.FN = 0 (Never)

When IA.FN =0, the IAQ algorithm can never turn on the fan.

IA.FN = 1 (Occupied)

When IA.FN =1, the IAQ algorithm will turn on the indoor fan whenever the building is occupied and IAQ/OAQ differential is

greater than the Fan On AQ Differential (ConfigurationAIR.QDF.ON). The indoor fan will turn off when the IAQ/OAQ differential is less than the Fan Off AQ Differential (ConfigurationAIR.QDF.OF).

IA.FN = 2 (Always)

The indoor fan operation for IA.FN =2, is the same as the operation when IA.FN =1, except the algorithm is not limited to the occupied periods only. The fan can be triggered on when the space is occupied or unoccupied.

Fan Enable (Analog Switch Input)

The DCV algorithm will operate whenever the building is occupied and the indoor fan is operating or whenever the IAQ algorithm has caused the indoor fan to operate. The IAQ Switch Fan Config (ConfigurationAIR.QII.FN) determines whether or not the IAQ algorithm can turn on the indoor fan. If the indoor fan is not operating, the economizer position will be zero. The damper position may exceed Econ Min at Max Fan Speed (ConfigurationECONMP.MX) and corresponding damper position curve to provide economizer cooling.

II.FN = 0 (Never)

When II.FN =0, the IAQ algorithm can never turn on the fan.

II.FN = 1 (Occupied)

When II.FN =1, the IAQ algorithm will turn on the indoor fan whenever the building is occupied and IAQ is high. The indoor fan will turn off when the IAQ returns to normal.

II.FN = 2 (Always)

The indoor fan operation for II.FN =2, is the same as the operation when IA.FN =1, except the algorithm is not limited to the occupied periods only. The fan can be triggered on when the space is occupied or unoccupied.

Cooling Modes

Cooling Mode Using Space Temperature Sensor T55, T56, T58 or T59

In cooling mode the PD control will maintain the Occupied Cool Set Point (SetpointOCSP) or the Unoccupied Cool Set Point (SetpointsUCSP) by modulating the indoor fan speed to supply more or less airflow to the conditioned space at the Supply Air Temperature (TemperaturesAIR.TSAT).

Cooling Supply Air Set Point

The Cool Supply Air Set Point (SetpointSASP)can be configured between 45F and 75F. The compressor modulates to

maintain a Supply Air Temperature (TemperaturesAIR.TSAT)at the Cool Supply Air Set Point (SetpointSASP).

Cooling Speed Demand Window

When the temperature in the conditioned space is higher than the Occupied Cool Set Point (SetpointsOCSP) plus the Fan Speed Control Demand (ConfigurationCOOL?FS.CD) configuration

48/50PD

17

Image 17
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralCCN Tables and Display Scrolling Marquee Mode and Menu Display StructureSystem Pilott and Touch Pilot Devices START-UP Internal Wiring Power SupplyEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP CCN Communication AccessoriesFan Status Setting an Occupied Time Schedule Weekdays Only for 730 toFilter Status TimeclockProgramming Operating Schedules Service TestIndependent Outputs Fan TestControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationUnoccupied Free Cooling Outdoor Fan OperationEconomizer Operation Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point For all units with Economizers Ventilation ModeFor units with Enthalpy Control Demand Control VentilationHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATSetting Up the System Temperature Compensated StartTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HDemand Limit Carrier Comfort Network Ccnr ConfigurationAlarm Handling TroubleshootingRestart Procedure Complete Unit StoppageCommunication Failures Alarms and AlertsAlert Code T074 Space Temperature Thermistor Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingPhase Loss Protection Heating TroubleshootingVariable Frequency Drive VFD Troubleshooting IGC Service Analysis Logic Electric Heat Service Analysis IGC Board LED Alarm CodesLED FlashAir Temperatures Thermistor TroubleshootingRefrigerant Temperatures Thermistor/Temperature Sensor CheckSensor Trim Transducer TroubleshootingForcing Inputs and Outputs Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F General Major System ComponentsPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripField-Installed Accessories Accessory Navigatort DisplayScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Coil Maintenance and Cleaning Recommendation CleaningPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesFilters Condensate Drain PanOutdoor-Air Inlet Screens Main Burner 48PDLubrication Evaporator Fan Service and ReplacementEvaporator Fan Performance Adjustment Condenser-Fan Adjustment Evaporator Fan Belt Tension AdjustmentVariable Frequency Drive VFD Replacement Verify Sensor Performance Economizer Operation During Power FailureEvacuation Refrigerant ChargePuronR Refrigerant Gas Valve AdjustmentAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneMain Burners High AltitudeFilter Drier Protective DevicesDiagnostic LEDs Replacement PartsRelief Devices Compressor Sound ShieldAppendix a Local Display and CCN Tables Mode RUN StatusAlrmdisp = CCN StrtOnly Generic = CCNMode Pressures Mode Service TestMode Temperatures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration HTR HT.TYMRT.H MOT.HIA.FN IA.CFII.CF II.FNSPT.C TrimSPT.T SAT.CCCN only Tables Mode Time ClockMode Operating Modes ACT.H OK.HTEN.LO AQ.DVExpansion Range Default CCN CCN Point CCN Write Mode AlarmsExpansion Range Units TABLE/SUB---TABLE StatusVFD Terminal Designations Appendix B VFD InformationVFD Configurations VFD Operation Standard Display ModeVFD Modes Start Up with AssistantStart-Up Assistant Mode Parameters ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics Correcting Alarms VFD MaintenanceHistory Heat Sink201---206 Fault Codes101---105 1001 10001002 1003Maintenance Interval Alarm CodesMaintenance Intervals Battery Replacement Main Fan ReplacementControl Panel Cleaning Fan Performance 48PDD05 Vertical Units Appendix C START-UP DataFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Rpm Bhp 1500 Fan Performance 48PDE06 Vertical UnitsAvailable External Static Pressure in. wg CFMBhp Rpm Fan Performance 48PDD05 Horizontal UnitsFan Performance 48PDE05 Horizontal Units 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.