Carrier 48/50PD05 Condensate Drain Pan, Filters, Outdoor-Air Inlet Screens, Main Burner 48PD

Page 61

!CAUTION

UNIT RELIABILITY HAZARD

Failure to follow this caution may result in reduced unit performance.

High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop.

Totaline Environmentally Sound Coil Cleaner Application Instructions

1.Proper eye protection such as safety glasses is recommended during mixing and application.

2.Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.

3.Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.

4.Mix Totaline environmentally sound coil cleaner in a 21/2 gallon garden sprayer according to the instructions included with the cleaner. The optimum solution temperature is 100_F.

IMPORTANT: Do NOT USE water in excess of 130_F, as the enzymatic activity will be destroyed.

5.Thoroughly apply Totalineenvironmentally sound coil cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.

6.Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage.

7.Ensure cleaner thoroughly penetrates deep into finned areas.

8.Interior and exterior finned areas must be thoroughly cleaned.

9.Finned surfaces should remain wet with cleaning solution for 10 minutes.

10.Ensure surfaces are not allowed to dry before rinsing. Reapplying cleaner as needed to ensure 10-minute saturation is achieved.

11.Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle.

Condensate Drain Pan

Check and clean each year at the start of the cooling season. In winter, keep drains and traps dry.

To clean the condensate pan:

1.Disconnect condensate drain system from side or bottom drain connection.

2.Remove and clean trap.

3.Remove 4 screws securing condensate pan access cover to unit. Save screws and panel.

4.Slide condensate pan out from unit and clean. Pan is made of non-corrosive plastic. Use a mild cleaner to remove heavy deposits of dirt and grime.

5.Replace pan in unit.

6.Replace condensate pan access cover with 4 screws saved from Step 3.

7.Re-attach and prime condensate trap.

8.Connect condensate drainage system.

ROLLOUT

 

INDUCED

 

SWITCH

 

DRAFT

 

 

 

MOTOR

 

 

 

COMBUSTION

 

 

 

FAN HOUSING

 

SECTION

MAIN BURNER SECTION

MAIN GAS

48/50PD

VALVE

 

 

 

HEAT EXCHANGER

 

 

 

 

 

C07037

 

Fig. 28 - Typical Gas Heating Section

Filters

Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to unit Installation Instructions for type and size.

Outdoor-Air Inlet Screens

Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens. See unit installation instructions for quantity and size.

Main Burner (48PD)

At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames. Refer to Main Burners section.

Flue Gas Passageways (48PD)

The flue collector box and heat exchanger cells may be inspected by opening heat section access door, flue box cover, and main burner assembly. (See Fig. 28.) Refer to Main Burners section for burner removal sequence. If cleaning is required, clean tubes with a wire brush. Use Caution with ceramic heat exchanger baffles. When installing retaining clip, be sure the center leg of the clip extends inward toward baffle. (See Fig. 29.)

CERAMIC

BAFFLE

CLIP

NOTE: One baffle and clip will be in each upper tube of the heat exchanger.

C07260

Fig. 29 - Removing Heat Exchanger Ceramic

Baffles and Clips

Combustion-Air Blower (48PD)

Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency.

61

Image 61
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralSystem Pilott and Touch Pilot Devices Scrolling Marquee Mode and Menu Display StructureCCN Tables and Display START-UP Internal Wiring Power SupplyEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP CCN Communication AccessoriesFan Status Setting an Occupied Time Schedule Weekdays Only for 730 toFilter Status TimeclockProgramming Operating Schedules Service TestIndependent Outputs Fan TestControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationEconomizer Operation Outdoor Fan OperationUnoccupied Free Cooling Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point For all units with Economizers Ventilation ModeFor units with Enthalpy Control Demand Control VentilationHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATSetting Up the System Temperature Compensated StartTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HDemand Limit Carrier Comfort Network Ccnr ConfigurationAlarm Handling TroubleshootingRestart Procedure Complete Unit StoppageCommunication Failures Alarms and AlertsAlert Code T074 Space Temperature Thermistor Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingVariable Frequency Drive VFD Troubleshooting Heating TroubleshootingPhase Loss Protection IGC Service Analysis Logic Electric Heat Service Analysis IGC Board LED Alarm CodesLED FlashAir Temperatures Thermistor TroubleshootingRefrigerant Temperatures Thermistor/Temperature Sensor CheckForcing Inputs and Outputs Transducer TroubleshootingSensor Trim Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F General Major System ComponentsPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripField-Installed Accessories Accessory Navigatort DisplayScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Coil Maintenance and Cleaning Recommendation CleaningPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesFilters Condensate Drain PanOutdoor-Air Inlet Screens Main Burner 48PDEvaporator Fan Performance Adjustment Evaporator Fan Service and ReplacementLubrication Variable Frequency Drive VFD Replacement Evaporator Fan Belt Tension AdjustmentCondenser-Fan Adjustment Verify Sensor Performance Economizer Operation During Power FailureEvacuation Refrigerant ChargePuronR Refrigerant Gas Valve AdjustmentAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneMain Burners High AltitudeFilter Drier Protective DevicesDiagnostic LEDs Replacement PartsRelief Devices Compressor Sound ShieldAppendix a Local Display and CCN Tables Mode RUN StatusAlrmdisp = CCN StrtOnly Generic = CCNMode Temperatures Mode Service TestMode Pressures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration HTR HT.TYMRT.H MOT.HIA.FN IA.CFII.CF II.FNSPT.C TrimSPT.T SAT.CCCN only Tables Mode Time ClockMode Operating Modes ACT.H OK.HTEN.LO AQ.DVExpansion Range Default CCN CCN Point CCN Write Mode AlarmsExpansion Range Units TABLE/SUB---TABLE StatusVFD Terminal Designations Appendix B VFD InformationVFD Configurations VFD Operation Standard Display ModeVFD Modes Start Up with AssistantStart-Up Assistant Mode Parameters ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics Correcting Alarms VFD MaintenanceHistory Heat Sink101---105 Fault Codes201---206 1001 10001002 1003Maintenance Intervals Alarm CodesMaintenance Interval Control Panel Cleaning Main Fan ReplacementBattery Replacement Fan Performance 48PDD05 Vertical Units Appendix C START-UP DataFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Rpm Bhp 1500 Fan Performance 48PDE06 Vertical UnitsAvailable External Static Pressure in. wg CFMFan Performance 48PDE05 Horizontal Units Fan Performance 48PDD05 Horizontal UnitsBhp Rpm 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.