Carrier 48/50PD05 manual Communication Failures, Alarms and Alerts

Page 25

AUX1 is not blinking, check the DIP switch positions on the board. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. A blinking red LED at the rate of once per second means that software is not loaded on the board. Also, be sure that the board is supplied with the current software. If necessary, reload current software. A board LED that is lit continuously should be replaced.

Green LED

The MBB, ECB and AUX1 each have one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. If LEN LED is not blinking, check LEN connections for potential communication errors (MBB J3, J4, and J5). Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB also provides both power and communication directly to the Scrolling Marquee display. The J5

connector on the MBB provides a LEN interface at the field connection terminal (TB).

Yellow LED

The MBB has one yellow LED which is used to indicate CCN communication activity. The Carrier Comfort Network(CCN) LED will blink during times of network communication.

Communication Failures

If the Scrolling Marquee or Navigator display Communication Failure or the green or yellow LED’s do not flash on the boards then the problem could be the communication chip on one of the control boards (MBB, ECB or AUX1). Use an ohm meter to measure the resistance on the communication pins of the boards to determine if the board is bad. If the reading is less than half the value indicated in Table 7, then the board needs to be replaced.

Table 7 — LEN and CCN Communication Resistances

 

Board Serial

(LEN) Resistance between Pins/

(CCN) Resistance between Pins/

Device

 

Connector

 

 

Connector

 

Number

 

 

 

 

 

Pins 1 to 3

Pins 1 to 2

Pins 2 to 3

Pins 5 to 7

Pins 5 to 6

Pins 6 to 7

 

 

 

Prior to 4702N

15K

7.5K

7.5K

15K

7.5K

7.5K

 

J3, J4, & J5

J3, J4, & J5

J3, J4, & J5

J5

J5

J5

MBB

 

Starting 4702N

18.9K

9.9K

9.9K

18.9K

9.9K

9.9K

 

 

J3, J4, & J5

J3, J4, & J5

J3, J4, & J5

J5

J5

J5

 

 

 

Prior to 0803N

5.9K

5.2K

5K

---

---

---

 

J2

J2

J2

ECB

 

 

 

 

Starting 0803N

18.9K

9.9K

9.9K

---

---

---

 

 

J2

J2

J2

 

 

 

 

 

AUX1

---

29K

16K

13.5K

---

---

---

J9

J9

J9

 

 

 

 

 

IMPORTANT: The resistive values should be read when the board is powered off and the unit is locked out.

48/50PD

Alarms and Alerts

Viewing and Clearing Unit Alarms

Presence of active alarms will be indicated on the Scrolling Marquee display by the Alarm Status light turning on and by the number of active alarms being displayed in the automatic View of Run Status. Presence of active alarms may also be signaled on the Alarm Output terminals. Each alarm may also be broadcast on the CCN network. Active alarms and past alarm history can be reviewed and cleared via the local display or a CCN device. The following menu locations are used for the local display:

AlarmsR.CURR (Reset All Current Alarms)

Change to YES to reset all active alarms. Turning unit power off will also reset all current alarms.

AlarmsR.HIST (Reset Alarm History)

Change to YES to reset the alarm history. Turning unit power off will not reset the alarm history.

AlarmsCURR (Currently Active Alarms)

Use the ENTER key, then scroll through any alarm numbers using the up and down arrow keys. Alarms are displayed in numerical order.

AlarmsHIST (Alarm History)

Use the ENTER key, then scroll through any alarm numbers using the up and down arrow keys. Up to 20 alarms are displayed in order of occurrence, with time and date.

The description for an alarm can be viewed on the Scrolling Marquee display by pressing ESCAPE and ENTER keys simultaneously while displaying the alarm code number. Be sure to expand description for each code, because in some cases there are different possible descriptions and causes for the same code number.

Diagnostic Alarm Codes and Possible Causes

Alert Code T051

There are 5 different texts for this alert code. There are three different alerts, two of which have corresponding test mode alerts indicated with “Service Test” in the expanded text. Pressing enter and esc on the marquee or navigator to expand the T051 alert will show you one of the below alerts. Make sure the expanded text is read correctly before troubleshooting.

SDigital Compressor Control Board Alarm

This alert occurs when the Digital Scroll Controller (DSC) energizes its alarm relay. Refer to the DSC’s LED diagnostic to determine which of the nine codes are present. Power cycle will

clear the DSC’s LED code. When the DSC’s alarm clears, this alert will automatically clear.

SCompressor A1 Safety Trip

This Alert indicates that Current Sensing A1 (CS.A1) has been enabled. The unit does not support the use of a current sensor at this time. Change the CS.A1 to disable and this alert will clear and not return.

(ConfigurationCOOLCS.A1)

SCompressor A1 Current Detected After Turnoff

This Alert indicates that Current Sensing A1 (CS.A1) has been enabled. The unit does not support the use of a current sensor at this time. Change the CS.A1 to disable and this alert will clear and not return.

(ConfigurationCOOLCS.A1)

Alert Code T064 - Circuit A Saturated Condensing Temperature Thermistor Failure

This alert occurs when the temperature is outside the range -40_to 240_F (-40_to 116_C). When this occurs, the control will use

25

Image 25
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralSystem Pilott and Touch Pilot Devices Scrolling Marquee Mode and Menu Display StructureCCN Tables and Display START-UP Internal Wiring Power SupplyEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP CCN Communication AccessoriesFan Status Setting an Occupied Time Schedule Weekdays Only for 730 toFilter Status TimeclockProgramming Operating Schedules Service TestIndependent Outputs Fan TestControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationEconomizer Operation Outdoor Fan OperationUnoccupied Free Cooling Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point For all units with Economizers Ventilation ModeFor units with Enthalpy Control Demand Control VentilationHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATSetting Up the System Temperature Compensated StartTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HDemand Limit Carrier Comfort Network Ccnr ConfigurationAlarm Handling TroubleshootingRestart Procedure Complete Unit StoppageCommunication Failures Alarms and AlertsAlert Code T074 Space Temperature Thermistor Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingVariable Frequency Drive VFD Troubleshooting Heating TroubleshootingPhase Loss Protection IGC Service Analysis Logic Electric Heat Service Analysis IGC Board LED Alarm CodesLED FlashAir Temperatures Thermistor TroubleshootingRefrigerant Temperatures Thermistor/Temperature Sensor CheckForcing Inputs and Outputs Transducer TroubleshootingSensor Trim Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F General Major System ComponentsPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripField-Installed Accessories Accessory Navigatort DisplayScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Coil Maintenance and Cleaning Recommendation CleaningPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesFilters Condensate Drain PanOutdoor-Air Inlet Screens Main Burner 48PDEvaporator Fan Performance Adjustment Evaporator Fan Service and ReplacementLubrication Variable Frequency Drive VFD Replacement Evaporator Fan Belt Tension AdjustmentCondenser-Fan Adjustment Verify Sensor Performance Economizer Operation During Power FailureEvacuation Refrigerant ChargePuronR Refrigerant Gas Valve AdjustmentAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneMain Burners High AltitudeFilter Drier Protective DevicesDiagnostic LEDs Replacement PartsRelief Devices Compressor Sound ShieldAppendix a Local Display and CCN Tables Mode RUN StatusAlrmdisp = CCN StrtOnly Generic = CCNMode Temperatures Mode Service TestMode Pressures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration HTR HT.TYMRT.H MOT.HIA.FN IA.CFII.CF II.FNSPT.C TrimSPT.T SAT.CCCN only Tables Mode Time ClockMode Operating Modes ACT.H OK.HTEN.LO AQ.DVExpansion Range Default CCN CCN Point CCN Write Mode AlarmsExpansion Range Units TABLE/SUB---TABLE StatusVFD Terminal Designations Appendix B VFD InformationVFD Configurations VFD Operation Standard Display ModeVFD Modes Start Up with AssistantStart-Up Assistant Mode Parameters ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics Correcting Alarms VFD MaintenanceHistory Heat Sink101---105 Fault Codes201---206 1001 10001002 1003Maintenance Intervals Alarm CodesMaintenance Interval Control Panel Cleaning Main Fan ReplacementBattery Replacement Fan Performance 48PDD05 Vertical Units Appendix C START-UP DataFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Rpm Bhp 1500 Fan Performance 48PDE06 Vertical UnitsAvailable External Static Pressure in. wg CFMFan Performance 48PDE05 Horizontal Units Fan Performance 48PDD05 Horizontal UnitsBhp Rpm 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.