Carrier 48/50PD05 manual Supply-Air Temperature Sensor SAT, Gas Heat Start-Up

Page 21

be extended by 15 seconds. The maximum delay is 3 minutes. Once modified by the IGC, the fan off delay will not change back to the configured Fan-off Delay, Gas Heat (ConfigurationHEATFOD.G) unless power is reset to the control.

A light emitting diode (LED) is provided on the IGC to indicate status. During normal operation the LED is continuously on. See the Troubleshooting section if the LED is off or flashing. The IGC is located behind the gas section access panel door. See Figure 8 or 9 for location.

The 48/50PD unit control will switch automatically between cooling and heating to maintain space temperature. To minimize unnecessary changes there is a 10 minute Mode Select Timeguard (Operating ModesHEATMS.TG) after the last stage of cooling turns off and before the heating is allowed.

The unit tries to maintain the space temperature at the Occupied Heat Setpoint (SetpointOHSP) or the Unoccupied Heat Setpoint (SetpointUHSP). See the Occupancy Determination section for factors that affect the Currently Occupied (Run StatusVIEWOCC) parameter. Heating Demand (Operating ModesHEATSPTDMD.H) is equal to the occupied or unoccupied set point minus the Space Temperature (Operating ModesHEATSPTSPT) [DMD.H = Setpoint - SPT].

Two methods are used to add and remove stages of heating for 48PD units. The first method causes the unit to operate around its steady state number of stages. For example, if the correct number of stages is between 0 and 1, this method will cause the first stage to cycle. If the correct number of stages is between 1 and 2, this method will cause the second stage to cycle. The second method causes the unit to find the steady-state number of stages. Details of these methods are provided below.

The control uses two methods to add a stage of heating. The first method will add a stage of heating when the Heating Demand (Operating ModesHEATSPTDMD.H) plus the change in Spacetemp Trend (Operating ModesHEATSPTTRND) times the Heat Thermal Lag Factor (Operating ModesHEATSPTH.LAG) is greater than the SPT Heat Demand (+) Level (Operating ModesHEATSPTHT.PD) [DMD.H + change TRND * H.LAG > HT.PD].

The second method will add a stage of heating when Heat Demand (Operating ModesHEATSPTDMD.H) is greater that the

SPT Heat Demand (+) Level (Operating ModesHEATSPTHT.PD) plus 0.5 degrees F [DMD.H > HT.PD + 0.5] and the heat demand is changing at a rate greater than 0.3 degrees F per minute.

The control uses two methods to remove a stage of heating. The first method will remove a stage of heating when the Heating Demand (Operating ModesHEATSPTDMD.H) plus the

change in Spacetemp Trend (Operating ModesHEATSPTTRND) times the Heat Thermal Lag Factor (Operating ModesHEATSPTH.LAG) is less than the SPT Heat Demand (-) Level (Operating ModesHEATSPTHT.ND) [DMD.H + change TRND * H.LAG < HT.ND].

The second method will remove a stage of heating when Heat Demand (Operating ModesHEATSPTDMD.H) is less that the SPT Heat Demand (-) Level (Operating ModesHEATSPTHT.ND) minus 0.5 degrees F [DMD.H < HT.PD - 0.5] and the heat demand is changing at a rate greater than 0.3 degrees F per minute.

Configurable delays also apply when adding stages per Heat Stage Increase Time (ConfigurationHEATH.INC) or removing

stages per Heat Stage Decrease Time (ConfigurationHEATH.DEC). Heat Minimum On Time (ConfigurationHEATMRT.H) and Heat Minimum Off Time (ConfigurationHEATMOT.H) also apply.

Supply-Air Temperature Sensor (SAT)

The SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) affects the Supply Air Temperature (TemperaturesAIR.TSAT) value displayed. This configuration is accessible via the Scrolling Marquee on the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H).

When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) =DSBL, the Supply Air Temperature (TemperaturesAIR.TSAT) value on the Scrolling Marquee and the CCN tables will be forced to zero when heat outputs come ON and for 5 minutes after. The default Supply Air Temperature (TemperaturesAIR.TSAT) location is at the fan inlet, upstream of the heat section.

When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) =ENBL, the Supply Air Temperature (TemperaturesAIR.TSAT) sensor reading is displayed at the Scrolling Marquee and the CCN tables during heating mode. This setting should only be used if the original SAT sensor wires are removed from the Main Base Board (MBB) and replaced by an accessory SAT sensor located in the supply duct downstream of the heat section. There are then two supply air temperature limits that become active, the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L) the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U). Any time the supply air temperature rises above the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L) the heat staging will be limited to what is currently on and no additional stages can be added until the supply air temperature falls

below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L). If the supply air temperature rises above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then heating will be reduced by removing a heat stage. That stage can not be added

again until the Supply Air Temperature (TemperaturesAIR.TSAT) falls below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L). If the supply air temperature stays above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then another stage will be removed after the Heat Stage Decrease Time (ConfigurationHEATH.DEC).

In heating mode the PD control will maintain the Occupied Heat Set Point (SetpointOHSP) or the Unoccupied Heat Set Point (SetpointUHSP) by turning on or off the Stage 1 and Stage 2 Gas Heat at the Supply Fan Minimum Speed (ConfigurationUNITFS.MN).

When the space temperature sensor detects the space temperature below the Occupied Heat Set Point (SetpointOHSP) or Unoccupied Heat Set Point (SetpointUHSP) and power is sent to the Integrated Gas Unit Controller (IGC) board. The heat staging is determined as described above and the Integrated Gas Controller (IGC) initiates the gas heat module start-up.

Gas Heat Start-Up

An LED (light-emitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed and the induced-draft motor is running. The induced-draft motor is then energized, and when speed is proven with the Hall Effect sensor on the motor, the ignition activation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out. When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the Hall Effect sensor, as well as the flame sensor. If for some reason the over temperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas

48/50PD

21

Image 21
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralScrolling Marquee Mode and Menu Display Structure System Pilott and Touch Pilot DevicesCCN Tables and Display START-UP Internal Wiring Power SupplyEvaporator Fan Condenser Fans and MotorsControls Quick SET-UP CCN Communication AccessoriesFan Status Setting an Occupied Time Schedule Weekdays Only for 730 toFilter Status TimeclockProgramming Operating Schedules Service TestIndependent Outputs Fan TestControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationOutdoor Fan Operation Economizer OperationUnoccupied Free Cooling Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point For all units with Economizers Ventilation ModeFor units with Enthalpy Control Demand Control VentilationHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATSetting Up the System Temperature Compensated StartTemp Comp Strt Cool Factr TCS.C Temp Comp Strt Heat Factr TCS.HDemand Limit Carrier Comfort Network Ccnr ConfigurationAlarm Handling TroubleshootingRestart Procedure Complete Unit StoppageCommunication Failures Alarms and AlertsAlert Code T074 Space Temperature Thermistor Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T075 Supply Air Temperature Thermistor Failure Alarm Code A154 Serial Eeprom Hardware FailureAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A200 Linkage Timeout Comm Failure Alarm Code A404 Fire ShutdownAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingHeating Troubleshooting Variable Frequency Drive VFD TroubleshootingPhase Loss Protection IGC Service Analysis Logic Electric Heat Service Analysis IGC Board LED Alarm CodesLED FlashAir Temperatures Thermistor TroubleshootingRefrigerant Temperatures Thermistor/Temperature Sensor CheckTransducer Troubleshooting Forcing Inputs and OutputsSensor Trim Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F General Major System ComponentsPressure Voltage Psig48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripField-Installed Accessories Accessory Navigatort DisplayScrolling Marquee Display Carrier Comfort Network Ccnr InterfaceSpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Coil Maintenance and Cleaning Recommendation CleaningPeriodic Clean Water Rinse Routine Cleaning of Round-Tube Coil SurfacesFilters Condensate Drain PanOutdoor-Air Inlet Screens Main Burner 48PDEvaporator Fan Service and Replacement Evaporator Fan Performance AdjustmentLubrication Evaporator Fan Belt Tension Adjustment Variable Frequency Drive VFD ReplacementCondenser-Fan Adjustment Verify Sensor Performance Economizer Operation During Power FailureEvacuation Refrigerant ChargePuronR Refrigerant Gas Valve AdjustmentAltitude Compensation 48PG03-07 Elevation Natural GAS PropaneMain Burners High AltitudeFilter Drier Protective DevicesDiagnostic LEDs Replacement PartsRelief Devices Compressor Sound ShieldAppendix a Local Display and CCN Tables Mode RUN StatusAlrmdisp = CCN StrtOnly Generic = CCNMode Service Test Mode TemperaturesMode Pressures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration HTR HT.TYMRT.H MOT.HIA.FN IA.CFII.CF II.FNSPT.C TrimSPT.T SAT.CCCN only Tables Mode Time ClockMode Operating Modes ACT.H OK.HTEN.LO AQ.DVExpansion Range Default CCN CCN Point CCN Write Mode AlarmsExpansion Range Units TABLE/SUB---TABLE StatusVFD Terminal Designations Appendix B VFD InformationVFD Configurations VFD Operation Standard Display ModeVFD Modes Start Up with AssistantStart-Up Assistant Mode Parameters ModeChanged Parameters Mode Drive Parameter Backup ModeVFD Diagnostics Correcting Alarms VFD MaintenanceHistory Heat SinkFault Codes 101---105201---206 1001 10001002 1003Alarm Codes Maintenance IntervalsMaintenance Interval Main Fan Replacement Control Panel CleaningBattery Replacement Fan Performance 48PDD05 Vertical Units Appendix C START-UP DataFan Performance 48PDE05 Vertical Units AirflowFan Performance 48PDD06 Vertical Units Rpm Bhp 1500 Fan Performance 48PDE06 Vertical UnitsAvailable External Static Pressure in. wg CFMFan Performance 48PDD05 Horizontal Units Fan Performance 48PDE05 Horizontal UnitsBhp Rpm 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.