Carrier 48/50PD05 manual Digital Scroll Controller DSC Troubleshooting, Cooling Service Analysis

Page 31

Table 9 — Cooling Service Analysis

PROBLEM

CAUSE

REMEDY

Compressor and Fan Will Not Start

Power failure.

Call power company.

 

Fuse blown or circuit breaker tripped. Check CB1 and

Replace fuse or reset circuit breaker.

 

CB2.

 

 

Disconnect off.

Power disconnect.

 

Compressor time guard to prevent short cycling.

Check time guards using ComfortLinkt Scrolling

 

 

Marquee also the DSC has a 2 minute anti---short time

 

Occupancy schedule set point or supply set point not

Check cooling demand using ComfortLink Scrolling

 

calling for Cooling.

Marquee.

 

Outdoor temperature too low.

Check Compressor Lockout Temperature using

 

 

ComfortLink Scrolling Marquee.

 

Active alarm.

Check active alarms using ComfortLink Scrolling

 

 

Marquee and DSC alert flash codes

Compressor Cycles (other than

Insufficient line voltage.

Determine cause and correct.

normally satisfying demand).

 

 

Active alarm.

Check active alarms using ComfortLink Scrolling

 

 

Marquee and DSC alert flash codes

Compressor Operates

Unit undersized for load.

Decrease load or increase size of unit.

Continuously.

 

 

Occupancy schedule set point or supply set point too

Check and adjust set points if needed.

 

low. Compressor running at lowest capacity

 

 

Compressor contactor stuck on

Check cooling demand using ComfortLink Scrolling

 

 

Marquee and DSC alert flash codes.

 

Dirty air filters.

Replace filters.

 

Low refrigerant charge.

Check pressure, locate leak, repair, evacuate, and

 

 

recharge.

 

Condenser coil dirty or restricted.

Clean coil or remove restriction.

Excessive Condenser Pressures.

Loose condenser thermistors.

Tighten thermistors.

 

Dirty condenser coil.

Clean coil.

 

Refrigerant overcharge.

Recover excess refrigerant.

 

Faulty TXV.

1.Check TXV bulb mounting and secure tightly to suction

 

 

line and insulate.

 

 

2.Replace TXV (and filter drier) if stuck open or closed.

 

Condenser air restricted or air short cycling.

Determine cause and correct.

 

Restriction in liquid tube.

Remove restriction.

Condenser Fans Not Operating.

No Power to contactors.

Fuse blown or plug at motor loose.

Excessive Suction Pressure.

High heat load.

Check for sources and eliminate

 

Faulty TXV.

1.Check TXV bulb mounting and secure tightly to suction

 

 

line and insulate.

 

 

2.Replace TXV (and filter drier) if stuck open or closed.

 

Refrigerant overcharged.

Recover excess refrigerant.

Suction Pressure Too Low.

Dirty air filters.

Replace air filters.

 

Low refrigerant charge.

Check pressure, locate leak, repair, evacuate, and

 

 

recharge.

 

Faulty TXV.

1.Check TXV bulb mounting and secure tightly to suction

 

 

line and insulate.

 

 

2.Replace TXV (and filter drier) if stuck open or closed.

 

Insufficient evaporator airflow.

Check belt tension. Check for other restrictions.

 

Indoor Fan Running to slow or off while compressor is

Check VFD display is illuminated and shows Auto

 

on

mode. Power supplied to VFD. Check 0---10vdc signal

 

 

present at AUX1 board.

 

Temperature too low in conditioned area (low

Reset thermostat or occupancy schedule.

 

return---air temperature).

 

LEGEND

 

 

CB - Circuit Breaker

 

 

DSC - Digital Scroll Controller

 

 

TXV - Thermostatic Expansion Valve

 

 

VFD - Variable Frequency Drive

 

 

48/50PD

Digital Scroll Controller (DSC) Troubleshooting

The 48/50PD units are equipped with a digital scroll compressor. The compressor has a solenoid unloader that is controlled by the digital scroll controller (DSC). This DSC turns the unloader on and off within a 20 second window. The amount of time the unloader is on verses off within that 20 seconds depends on the desired capacity. This means that the ComfortLink control does not have direct control of the compressor, but it does however control the power to the DSC and the signal for commanded capacity.

The DSC has three LED lights to help during troubleshooting; green, yellow, and red The DSC will run the compressor unloaded for a half a second on start up and one second on shutdown to prevent reverse rotation. A two minute anti-short time guard is applied by the DSC after shutting the compressor off. The DSC has an alarm relay output that is connected to the MBB. When this MBB input switch is closed, the MBB activates the T051 alert. Check the LED status on the DSC for flash alarm

codes and correct any problems. Table 10 shows the DSC’s Red LED flash codes.

POWER LED (green) indicates voltage is present at the 24VAC power terminal. When the 2 minute anti-short cycle timer is active, the green LED will flash.

UNLOADED LED (yellow) indicates the unloader solenoid status. The LED is on when the unloader solenoid is energized.

ALERT LED (red) communicates an abnormal system condition through a unique flash code.

All LEDs Flashing at the Same Rate indicates 24VAC supply is too low for operation.

All LEDs On Solid at the Same Time indicates Digital Scroll Controller failure.

Flash Code 1 Reserved for future use

Flash Code 2 High Discharge Temperature

This occurs when the discharge temperature thermistor (DTT) has

31

Image 31
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralSystem Pilott and Touch Pilot Devices Scrolling Marquee Mode and Menu Display StructureCCN Tables and Display START-UP Condenser Fans and Motors Power SupplyInternal Wiring Evaporator FanControls Quick SET-UP CCN Communication AccessoriesTimeclock Setting an Occupied Time Schedule Weekdays Only for 730 toFan Status Filter StatusFan Test Service TestProgramming Operating Schedules Independent OutputsControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationEconomizer Operation Outdoor Fan OperationUnoccupied Free Cooling Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point Demand Control Ventilation Ventilation ModeFor all units with Economizers For units with Enthalpy ControlHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATTemp Comp Strt Heat Factr TCS.H Temperature Compensated StartSetting Up the System Temp Comp Strt Cool Factr TCS.CDemand Limit Carrier Comfort Network Ccnr ConfigurationComplete Unit Stoppage TroubleshootingAlarm Handling Restart ProcedureCommunication Failures Alarms and AlertsAlarm Code A154 Serial Eeprom Hardware Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T074 Space Temperature Thermistor Failure Alert Code T075 Supply Air Temperature Thermistor FailureAlarm Code A404 Fire Shutdown Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code A200 Linkage Timeout Comm FailureAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingVariable Frequency Drive VFD Troubleshooting Heating TroubleshootingPhase Loss Protection IGC Service Analysis Logic Flash IGC Board LED Alarm CodesElectric Heat Service Analysis LEDThermistor/Temperature Sensor Check Thermistor TroubleshootingAir Temperatures Refrigerant TemperaturesForcing Inputs and Outputs Transducer TroubleshootingSensor Trim Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F Psig Major System ComponentsGeneral Pressure Voltage48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripCarrier Comfort Network Ccnr Interface Accessory Navigatort DisplayField-Installed Accessories Scrolling Marquee DisplaySpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Routine Cleaning of Round-Tube Coil Surfaces CleaningCoil Maintenance and Cleaning Recommendation Periodic Clean Water RinseMain Burner 48PD Condensate Drain PanFilters Outdoor-Air Inlet ScreensEvaporator Fan Performance Adjustment Evaporator Fan Service and ReplacementLubrication Variable Frequency Drive VFD Replacement Evaporator Fan Belt Tension AdjustmentCondenser-Fan Adjustment Refrigerant Charge Economizer Operation During Power FailureVerify Sensor Performance EvacuationElevation Natural GAS Propane Gas Valve AdjustmentPuronR Refrigerant Altitude Compensation 48PG03-07Protective Devices High AltitudeMain Burners Filter DrierCompressor Sound Shield Replacement PartsDiagnostic LEDs Relief DevicesAppendix a Local Display and CCN Tables Mode RUN StatusGeneric = CCN StrtAlrmdisp = CCN OnlyMode Temperatures Mode Service TestMode Pressures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration MOT.H HT.TYHTR MRT.HII.FN IA.CFIA.FN II.CFSAT.C TrimSPT.C SPT.TCCN only Tables Mode Time ClockMode Operating Modes AQ.DV OK.HTACT.H EN.LOTABLE/SUB---TABLE Status Mode AlarmsExpansion Range Default CCN CCN Point CCN Write Expansion Range UnitsVFD Terminal Designations Appendix B VFD InformationVFD Configurations Start Up with Assistant Standard Display ModeVFD Operation VFD ModesDrive Parameter Backup Mode Parameters ModeStart-Up Assistant Mode Changed Parameters ModeVFD Diagnostics Heat Sink VFD MaintenanceCorrecting Alarms History101---105 Fault Codes201---206 1003 10001001 1002Maintenance Intervals Alarm CodesMaintenance Interval Control Panel Cleaning Main Fan ReplacementBattery Replacement Airflow Appendix C START-UP DataFan Performance 48PDD05 Vertical Units Fan Performance 48PDE05 Vertical UnitsFan Performance 48PDD06 Vertical Units CFM Fan Performance 48PDE06 Vertical UnitsRpm Bhp 1500 Available External Static Pressure in. wgFan Performance 48PDE05 Horizontal Units Fan Performance 48PDD05 Horizontal UnitsBhp Rpm 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.