APPENDIX B - VFD INFORMATION (CONT)

VFD Operation

The VFD keypad is shown in Fig. 41. The function of SOFT KEYS 1 and 2 change depending on what is displayed on the screen. The function of SOFT KEY 1 matches the word in the lower left-hand box on the display screen. The function of SOFT KEY 2 matches the word in the lower right-hand box on the display screen. If the box is empty, then the SOFT KEY does not have a function on that specific screen. The UP and DOWN keys are used to navigate through the menus. The OFF key is used to turn off the VFD. The AUTO key is used to change control of the drive to automatic control. The HAND key is used to change control of the drive to local (hand held) control. The HELP button is used to access the help screens.

For the VFD to operate on the 48/50PD units, the drive must be set in AUTO mode. The word “AUTO” will appear in the upper left hand corner of the VFD display. Press the AUTO button to set the drive in AUTO mode.

C08675

Fig. 41 - VFD Keypad

Start Up with Assistant

Initial start-up has been performed at the factory. Use of the start up assistant will override factory VFD configurations. See below to check that all parameters listed in VFD Configurations table are correctly configured on the VFD.

Start Up by Changing Parameters Individually

Initial start-up is performed at the factory. To start up the VFD with by changing individual parameters, perform the following procedure:

1.Select MENU (SOFT KEY 2). The Main menu will be displayed.

2.Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2).

3.Use the UP or DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2).

4.Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2).

5.Use the UP or DOWN keys to change the value of the parameter.

6.Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed.

7.Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the parameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu.

IMPORTANT: The current parameter value appears above the highlight parameter. To view the default parameter value, press the UP and DOWN keys simultaneously. To restore the default factory settings, select the application macro “HVAC Default.”

VFD Modes

The VFD has several different modes for configuring, operating, and diagnosing the VFD. The modes are:

SStandard Display mode shows drive status information and

operates the drive

SParameters mode edits parameter values individually S Start-up Assistant mode guides the start up and

configuration

S Changed Parameters mode shows all changed parameters S Drive Parameter Backup mode stores or uploads the

parameters

S Clock Set mode sets the time and date for the drive S I/O Settings mode checks and edits the I/O settings

Standard Display Mode

Use the standard display mode to read information on the drive status and operate the drive. To reach the standard display mode, press EXIT until the LCD display shows status information as described below. See Fig. 42.

The top line of the LCD display shows the basic status information of the drive. The HAND icon indicates that the drive control is local from the control panel. The AUTO icon indicates that the drive is in remote control mode, such as the basic I/O (X1) or field bus.

The arrow icon indicates the drive and motor rotation status. A rotating arrow (clockwise or counterclockwise) indicates that the drive is running and at set point and the shaft direction is forward or reverse. A rotating blinking arrow indicates that the drive is running but not at set point. A stationary arrow indicates that the drive is stopped. For Carrier rooftop units, the correct rotation is counterclockwise.

The upper right corner shows the frequency set point that the drive will maintain.

Using parameter group 34, the middle of the LCD display can be configured to display 3 parameter values. The default display shows parameters 0103 (OUTPUT FREQ) in percentages, 0104 (CURRENT) in amperes, and 0120 (AI1) in milliamperes.

The bottom corners of the LCD display show the functions currently assigned to the two soft keys. The lower middle displays the current time (if configured to show the time).

The first time the drive is powered up, it is in the OFF mode. To switch to local hand-held control and control the drive using the control panel, press and hold the HAND button. Pressing the HAND button switches the drive to hand control while keeping the drive running. Press the AUTO button to switch to remote input control. To start the drive press the HAND or AUTO buttons, to stop the drive press the OFF button.

C08676

Fig. 42 - Standard Display Example

48/50PD

83

Image 83
Contents Table of Contents What to do if you smell gas Safety ConsiderationsBasic Control Usage GeneralCCN Tables and Display Scrolling Marquee Mode and Menu Display StructureSystem Pilott and Touch Pilot Devices START-UP Condenser Fans and Motors Power SupplyInternal Wiring Evaporator FanControls Quick SET-UP CCN Communication AccessoriesTimeclock Setting an Occupied Time Schedule Weekdays Only for 730 toFan Status Filter StatusFan Test Service TestProgramming Operating Schedules Independent OutputsControls Operation Third Party ControlModes Unit ConfigurationOccupancy Determination General Operating SequenceIndoor Fan Operation Compressor OperationUnoccupied Free Cooling Outdoor Fan OperationEconomizer Operation Indoor Air Quality IAQ Cooling Modes Cool Supply Air Set Point Demand Control Ventilation Ventilation ModeFor all units with Economizers For units with Enthalpy ControlHeating Modes Gas Heat Start-Up Supply-Air Temperature Sensor SATTemp Comp Strt Heat Factr TCS.H Temperature Compensated StartSetting Up the System Temp Comp Strt Cool Factr TCS.CDemand Limit Carrier Comfort Network Ccnr ConfigurationComplete Unit Stoppage TroubleshootingAlarm Handling Restart ProcedureCommunication Failures Alarms and AlertsAlarm Code A154 Serial Eeprom Hardware Failure Alert Code T073 Outdoor Air Temperature Thermistor FailureAlert Code T074 Space Temperature Thermistor Failure Alert Code T075 Supply Air Temperature Thermistor FailureAlarm Code A404 Fire Shutdown Alarm Code T155 Serial Eeprom Storage Failure ErrorAlarm Code A156 Critical Serial Eeprom Storage Fail Error Alarm Code A200 Linkage Timeout Comm FailureAlert Code T416 OAQ Input Out of Range Alert Code T415 IAQ Input Out of RangeComfortLink Alarm Codes Cooling Troubleshooting Cooling Service Analysis Digital Scroll Controller DSC TroubleshootingDSC Red LED Flash Codes Flash Code 4 ⎯ Locked RotorEconomizer Service Analysis Economizer TroubleshootingPhase Loss Protection Heating TroubleshootingVariable Frequency Drive VFD Troubleshooting IGC Service Analysis Logic Flash IGC Board LED Alarm CodesElectric Heat Service Analysis LEDThermistor/Temperature Sensor Check Thermistor TroubleshootingAir Temperatures Refrigerant TemperaturesSensor Trim Transducer TroubleshootingForcing Inputs and Outputs Temp Voltage Resistance Drop Temp Voltage Resistance Temp F Drop Degree C Degree F Psig Major System ComponentsGeneral Pressure Voltage48PD Control Wiring Schematic 50PD Control Wiring Schematic 48/50PD Power Wiring Schematic and Legend Typical Unit Component Arrangement Main Base Board MBB SettingFIL.S MBB ConnectionsEconomizer Control Board ECB Center of the board. Do not change this settingRM.OC ECB ConnectionsCommunication Modulation Board AUX1CMP.A Digital Scroll Control Board DSCVariable Frequency Drive VFD Variable Frequency Drive VFDIntegrated Gas Control IGC Board Integrated Gas Control IGC BoardTB1 Low Voltage Terminal StripCarrier Comfort Network Ccnr Interface Accessory Navigatort DisplayField-Installed Accessories Scrolling Marquee DisplaySpace Temperature Sensor Averaging Space Temperature Sensor T-58Space Temperature Sensor Averaging Service Routine Cleaning of Round-Tube Coil Surfaces CleaningCoil Maintenance and Cleaning Recommendation Periodic Clean Water RinseMain Burner 48PD Condensate Drain PanFilters Outdoor-Air Inlet ScreensLubrication Evaporator Fan Service and ReplacementEvaporator Fan Performance Adjustment Condenser-Fan Adjustment Evaporator Fan Belt Tension AdjustmentVariable Frequency Drive VFD Replacement Refrigerant Charge Economizer Operation During Power FailureVerify Sensor Performance EvacuationElevation Natural GAS Propane Gas Valve AdjustmentPuronR Refrigerant Altitude Compensation 48PG03-07Protective Devices High AltitudeMain Burners Filter DrierCompressor Sound Shield Replacement PartsDiagnostic LEDs Relief DevicesAppendix a Local Display and CCN Tables Mode RUN StatusGeneric = CCN StrtAlrmdisp = CCN OnlyMode Pressures Mode Service TestMode Temperatures Mode Inputs Mode SET PointsOutputs Mode OutputsMode Configuration MOT.H HT.TYHTR MRT.HII.FN IA.CFIA.FN II.CFSAT.C TrimSPT.C SPT.TCCN only Tables Mode Time ClockMode Operating Modes AQ.DV OK.HTACT.H EN.LOTABLE/SUB---TABLE Status Mode AlarmsExpansion Range Default CCN CCN Point CCN Write Expansion Range UnitsVFD Terminal Designations Appendix B VFD InformationVFD Configurations Start Up with Assistant Standard Display ModeVFD Operation VFD ModesDrive Parameter Backup Mode Parameters ModeStart-Up Assistant Mode Changed Parameters ModeVFD Diagnostics Heat Sink VFD MaintenanceCorrecting Alarms History201---206 Fault Codes101---105 1003 10001001 1002Maintenance Interval Alarm CodesMaintenance Intervals Battery Replacement Main Fan ReplacementControl Panel Cleaning Airflow Appendix C START-UP DataFan Performance 48PDD05 Vertical Units Fan Performance 48PDE05 Vertical UnitsFan Performance 48PDD06 Vertical Units CFM Fan Performance 48PDE06 Vertical UnitsRpm Bhp 1500 Available External Static Pressure in. wgBhp Rpm Fan Performance 48PDD05 Horizontal UnitsFan Performance 48PDE05 Horizontal Units 1026 1086 1144 1199 1253 Fan Performance 48PDD06 Horizontal UnitsFan Performance 48PDE06 Horizontal Units Fan Performance 50PD06 Vertical Units Fan Performance 50PD05 Vertical UnitsBhp Rpm 1500 Fan Performance 50PD05 Horizontal UnitsGeneral Notes for FAN Performance Data Tables Appendix D Additional START-UP Data Indicate Unit Settings below Control SET Point and Configuration LOGCCN Point Entry 103 104 PRE-START-UP Unit START-UP Checklist106

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.