Standby Battery Information
The Table and worksheet below provide the installer with the infor- mation necessary to determine the AH rating and battery require- ments for any particular installation.
Sierra Accessory Loading
Product current consumption |
| Max. Standby | Max. Active | |
|
|
|
| |
S5832 Control Panel |
| 125 mA | 125 mA | |
S5010 | Alpha Keypad |
| 30 mA | 50 mA |
S5020 LED Keypad |
| 30 mA | 50 mA | |
|
|
|
|
|
S5030 | Icon Keypad |
| 30 mA | 50 mA |
|
|
|
|
|
S5050 | REMM (up to 2) |
| 100 mA (each) | 100 mA |
S5058 ZEM (up to 3) |
| 40 mA (each) | 40 mA** | |
|
|
|
| |
S5070 |
| 35 mA | 60 mA | |
|
|
|
| |
| 35 mA | 70 mA | ||
|
|
|
| |
| 125 mA | 170 mA | ||
**ZEM VOUT terminals can supply up to 300 mA (max.) | ||||
|
|
|
| |
Table A - Standby Battery Loading |
|
|
AH Requirements for Backup
Product/Device | Qty | Total | |||
|
|
|
|
|
|
S5832SG | 0.5 AH | 3.0 AH | 9.0 AH |
|
|
S5010 | 0.12 AH | 0.72 AH | 2.16 AH |
|
|
|
|
|
|
|
|
S5020 | 0.12 AH | 0.72 AH | 2.16 AH |
|
|
|
|
|
|
|
|
S5030 | 0.12 AH | 0.72 AH | 2.16 AH |
|
|
S5050 | 0.4 AH | 2.4 AH | 7.2 AH |
|
|
|
|
|
|
|
|
S5058 | 0.16 AH | 0.96 AH | 2.88 AH |
|
|
|
|
|
|
|
|
0.14 AH | 0.84 AH | 2.52 AH |
|
| |
|
|
|
|
|
|
| 0.5 AH | 3.0 AH | 9.0 AH |
|
|
|
|
|
|
|
|
Sensor (10 mA) | 0.04 AH | 0.24 AH | 0.72 AH |
|
|
Sensor (25 mA) | 0.1 AH | 0.6 AH | 1.8 AH |
|
|
Bell/Siren (5 min) | 0.085 AH | 0.085 AH | 0.085 AH |
|
|
Bell/Siren (15 min) | 0.225 AH | 0.225 AH | 0.225 AH |
|
|
|
|
|
|
|
|
* Bell/Siren current may be 0.7 - 1.0 A | Total AH Required |
| |||
|
|
|
|
|
|
Table B - AH Requirements
Determining Standby Battery Requirements
To calculate the size (AH rating) of your system's Backup Battery, enter the Number (Qty) of devices of each type in the chart above. Multiply the number of devices times the AH rating for the desired backup period (Qty x AH = Total) and enter the total in the last column. To determine the total AH rating of the battery, add all values in the last column.
Total current from all sensors must be considered when calculat- ing AH rating. For example:
10 sensors @ 10 mA = 100 mA
4 sensors @ 25 mA = 100 mA Total current all sensors = 200 mA
i