The REMM also has five independently programmable re- lays. The relay programming options are explained in the programming summary, Block 7.
The AUX terminal on the S5050 REMM is capable of supply- ing up to 100 mA of output current to power sensors and other devices.
NOTE: Total combined current from the relays and AUX output terminal may not exceed 100 mA.
Refer to the S5050 REMM Installation Instructions (P/
N
Figure 8
The S5050 Relay/Event Memory Module (REMM) PCB Layout
Switch Settings
The S5050 REMM has five (5) dip switches
With the switch in the ON position, the +12 VDC AUX power is applied to the respective Relay switched (S) out- put terminal (see Figure 9, below).
Switch Configuration
Figure 9, below, shows the relationship of the switches to the relays on the REMM.
S2-2 is used to address the REMM. Leave S2-2 in the ON position for REMM #1. Change S2-2 to the OFF position to address REMM #2.
S5058 Zone Expansion Module
The Sierra S5832SG control panel has eight hardwired zones and may be expanded up to 32 zones. Eight addi- tional hardwire zones are obtained by connecting an S5058 Zone Expansion Module to the keypad data bus. Up to three S5058 ZEMs may be connected, providing a total of 24 additional zones.
NOTE: Trouble conditions and tampers, if enabled, are re- ported via the keypad bus. The report routing is defined in Block 4, CL 158 and 159, respectively.
Power is supplied by connecting the KPWR terminal on the S5058 ZEM PCB to the KPWR or AUX terminal on the control panel and the C terminal on the ZEM to the C ter- minal on the control panel. The GND terminal on the ZEM PCB is for connecting earth ground to the ZEM.
There are two VOUT terminals (connected in parallel), which can provide up to 300 mA of output current to power sensors or other devices.
Each S5058 ZEM will support up to 8 hardwired zones. If a zone is programmed as a SpreadNet zone (see Block 2, CL 111 - 142), it is not available for use as a hardwired zone.
Additional setup and wiring information is available in the S5058 Zone Expansion Module Installation Instruc- tions (P/N
Figure 10
S5058 Zone Expansion Module (ZEM) PCB Layout
ZEM Addressing
Switch | Relay |
|
|
|
|
R1S |
| |
R2S |
| |
|
|
|
R3S | ON | |
R4S |
| |
|
|
|
R5S |
|
Switch | REMM |
|
|
ON = REMM #1 | |
OFF = REMM #2 | |
|
|
Figure 11, below, shows the switch settings to address the ZEMs. ZEM #1 is used to add zones 9 - 16; ZEM #2 adds zones 17 - 24; and ZEM #3 adds zones 25 - 32.
|
|
|
|
| ON | |||||||
|
|
|
|
|
|
|
|
| ||||
Addr. | Zones |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||||
1 | on | off | 9 | - 16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
2 | off | on | 17 | - 24 |
|
|
|
|
|
|
|
|
3 | on | on | 25 | - 32 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 11
Addressing the ZEM
Figure 9
REMM Switch Settings (shown in default position)
6