Exit Delay Terminator
Cmd Loc 012
Default 1
Range 1 - 2
Block 7 - Auxiliary Devices Programming (cont.)
Comments | Options: | ||
If enabled, jumps to the last 5 seconds of the exit delay, | |||
1 | No | ||
then arms the system. Requires a normally open switch | |||
2 | Yes | ||
connected to keypad (TXD and C terminals). | |||
|
|
Timer Units (On Board Relay)
Cmd Loc 013
Default 2
Range 1 - 5
Timer Count (On Board Relay)
Cmd Loc | 014 |
Default | 30 |
Range | 1 - 255 |
Timer Units (REMM #1, Relay #1)
Cmd Loc 015
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #1)
Cmd Loc | 016 |
Default | 30 |
Range | 1 - 255 |
Timer Units (REMM #1, Relay #2)
Cmd Loc 017
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #2)
Cmd Loc 018
Default 30
Range 1 - 255
Timer Units (REMM #1, Relay #3)
Cmd Loc 019
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #3)
Cmd Loc | 020 |
Default | 30 |
Range | 1 - 255 |
Timer Units (REMM #1, Relay #4)
Cmd Loc 021
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #4)
Cmd Loc | 022 |
Default | 30 |
Range | 1 - 255 |
Timer Units (REMM #1, Relay #5)
Cmd Loc 023
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #5)
Cmd Loc | 024 |
Default | 30 |
Range | 1 - 255 |
Comments | Options: | |
Each relay has its own independent countdown timer. | 1 | Latched |
The timer consists of two parts: the Units and the Counter. | 2 | Seconds |
The countdown timer determines the amount of time a | 3 | Minutes |
relay will remain closed. For the | 4 | Hours |
stores the units, while CL 014 stores the starting count. | 5 | Days |
The timer will count backwards and when it reaches 0, |
|
|
the respective relay will open. |
|
|
NOTE: The timer function is ignored if the Relay option (Block 7, CL 001 -
011)is programmed for SpreadNet Arming/Disarming (option #5),
Comments
For REMM #1, Relay #1, CL 015 stores the units, while CL 016 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.
Comments
For REMM #1, Relay #2, CL 017 stores the units, while CL 018 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.
Comments
For REMM #1, Relay #3, CL 019 stores the units, while CL 020 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.
Comments
For REMM #1, Relay #4, CL 021 stores the units, while CL 022 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.
Comments
For REMM #1, Relay #5, CL 023 stores the units, while CL 024 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.
32