Sierra S5832SG installation instructions Block 7 Auxiliary Devices Programming

Page 35

Block 7 - Auxiliary Devices Programming

The Auxiliary Devices Programming Block has a total of 79 Command Locations (CL 001 - 079). Each of the first 11 commands has an input range of 1 - 82. Additional relay Options are provided for setting up specific timing operations.

On Board Relay

Cmd Loc 001

Default 1

Range 1 - 82

Relay #1 - REMM #1

Cmd Loc 002

Default 1

Range 1 - 82

Relay #2 - REMM #1

Cmd Loc 003

Default 1

Range 1 - 82

Relay #3 - REMM #1

Cmd Loc 004

Default 1

Range 1 - 82

Relay #4 - REMM #1

Cmd Loc 005

Default 1

Range 1 - 82

Relay #5 - REMM #1

Cmd Loc 006

Default 1

Range 1 - 82

Relay #1 - REMM #2

Cmd Loc 007

Default 1

Range 1 - 82

Relay #2 - REMM #2

Cmd Loc 008

Default 1

Range 1 - 82

Relay #3 - REMM #2

Cmd Loc 009

Default 1

Range 1 - 82

Relay #4 - REMM #2

Cmd Loc 010

Default 1

Range 1 - 82

Relay #5 - REMM #2

Cmd Loc 011

Default 1

Range 1 - 82

Options:

1 Disabled, relay open

2Close on SN “Door” button (keypad or re- mote) activation

3 Closed when entire system armed

4 Closed when entire system disarmed

50.5 sec on/off (3x) when keyswitch or Spread- Net arming; 1.5 sec on for keyswitch or SpreadNet disarming (ignores timer)

6 Close on any tamper

7 Close when phone line cut

8 Close when comm fail occurs

93-sec toggle to activate listen-in (ignores timer)

10 Follow keypad audible sounder (exit/entry de- lays, area 1 only) (ignores timer)

11 Close on fault (except 24-hr. zone); open when faulted zone is bypassed, restored, system armed, or timer

12 Close on any alarm

13 Close on fire alarm

14 Close on burglar alarm

15 Close on panic/holdup

16 Close in installer programming mode

17 Activated by Commander II (RPS)

18 Close at end of exit delay (all areas armed), open at start of entry delay

19 Close on area 1 alarm

20 Close on area 2 alarm

21 Close on area 3 alarm

22 Close on area 4 alarm

23 Close on area 5 alarm

24 Close on area 6 alarm

25 Close on area 7 alarm

26 Close on area 8 alarm

27 Close when area 1 armed

28 Close when area 2 armed

29 Close when area 3 armed

30 Close when area 4 armed

31 Close when area 5 armed

32 Close when area 6 armed

33 Close when area 7 armed

34 Close when area 8 armed

35 Close when armed, oscillate at 0.5 Hz when home armed (area 1)

36 Close when armed, oscillate at 0.5 Hz when home armed (area 2)

37 Close when armed, oscillate at 0.5 Hz when home armed (area 3)

38 Close when armed, oscillate at 0.5 Hz when home armed (area 4)

39 Close when armed, oscillate at 0.5 Hz when home armed (area 5)

40 Close when armed, oscillate at 0.5 Hz when home armed (area 6)

41 Close when armed, oscillate at 0.5 Hz when home armed (area 7)

42 Close when armed, oscillate at 0.5 Hz when home armed (area 8)

43Close on relay user code 14 entry

44Close on relay user code 18 entry

45Close on relay user code 22 entry

46Close on relay user code 26 entry

47Close on relay user code 30 entry

48Close on relay user code 34 entry

49Close on relay user code 38 entry

50Close on relay user code 42 entry

51Close on user code entry (area 1)

52Close on user code entry (area 2)

53Close on user code entry (area 3)

54Close on user code entry (area 4)

55Close on user code entry (area 5)

56Close on user code entry (area 6)

57Close on user code entry (area 7)

58Close on user code entry (area 8)

59Close on duress (area 1), open on next area 1 user code entry (except Duress code)

60Close on duress (area 2), open on next area 2 user code entry (except Duress code)

61Close on duress (area 3), open on next area 3 user code entry (except Duress code)

62Close on duress (area 4), open on next area 4 user code entry (except Duress code)

63Close on duress (area 5), open on next area 5 user code entry (except Duress code)

64Close on duress (area 6), open on next area 6 user code entry (except Duress code)

65Close on duress (area 7), open on next area 7 user code entry (except Duress code)

66Close on duress (area 8), open on next area 8 user code entry (except Duress code)

67Relay status #1 (see below) (ignores timer)

68Relay status #2 (see below) (ignores timer)

69Close on bell supervision trouble

70Close on keypad/accessory trouble or tamper

71Close on Medical alarm

723-sec toggle for annunciator shutoff (ignores timer)

733-sec toggle on local bell test (ignores timer)

74Close on alarm associated with zone activated relay (see Block 7, CL 035 - 066)

75Close on AC fail

76Close on low battery

77Close on chime zone fault

78Close on system trouble

79Close on Pre-set Timer #1 (Block 7, CL 067 - 069)

80Close on Pre-set Timer #2 (Block 7, CL 070 - 072)

81Close on Pre-set Timer #3 (Block 7, CL 073 - 075)

82Close on Pre-set Timer #4 (Block 7, CL 076 - 078)

NOTE: All relays may be programmed to open ac- cording to a timer (Block 7, CL 013 - 034), unless otherwise indicated. For additional information, refer to the S5090 Reference Manual.

Relay status #1

 

 

Relay status #2

 

 

 

 

 

 

 

 

 

System Status

Alarms?

Relay State

System Status

 

Alarms?

Relay State

Disarmed

No

Closed

Disarmed

 

No

Open

Disarmed

Yes

Open

Disarmed

 

Yes

Open

Armed

No

Closed

Armed

 

No

Closed

Armed

Yes

Open

Armed

 

Yes

Open

NOTE: Relays are open when de-energized.

31

Image 35
Contents Installation Instructions Page Table of Contents Singapore Sierra Accessory LoadingAH Requirements for Backup Country Specific Compliance InformationEarth Ground Panel Setup and InstallationIntroduction Mounting the PanelWiring Knock-outs Top AC Power Backup BatteryAH Requirements for Backup Sierra Accessory LoadingOutput Terminals Keypad WiringKeypad Wiring Sierra Accessory Wiring DistancesS5050 Relay/Event Memory Module AccessoriesZone Terminals On-Board Relay Terminals TB2S5058 Zone Expansion Module Digital Communicator Connections SN915-BUS SpreadNet ReceiverSN990/991 SpreadNet Keypad/Remote SN961 SpreadNet KeyfobTerminal Connections Programming the PanelRemote Programming RPS Zone LEDs Cmd Loc Data Value Press Home to activate the RPS featureProgramming With an LED Keypad ValueProgramming With an Icon Keypad Quick Programming ModeMenu Programming Mode Programming With an Alpha KeypadEvent Memory Installer Mode Options, BlockInstaller Walk-Test Battery Test Bypass 0 Home CancelEntry Delay Test Exit Delay TestBlock 1 Code Option Programming Block 2 Zone Configuration Programming Audible Cadence Zones 1 Chime Enable ZonesZone Bypass Enable Zones Zone Response Time Zones 1Block 3 Armed System Programming Low Battery Arming Comments Options Quick Bypass Enable CommentsHome Arm Exit Delay Enable 4X Exit Delay Extension Enable Comments OptionsSwinger Alarm Lockout Limit Comments Auto-Arming Enable AreaAuto-Disarming Enable Area Comments Auto-Disarming Enable Day of WeekDuress Active Only When Area Armed Sounder Turn-On Delay Following Alarm Seconds CommentsStrobe/Siren Disable with Low Battery Comments Options Soak Mode Learning Period Duration DaysHome Arming Enable Comments Options Keypad Tamper Switch Enable By Address Keypad #External Bell Reverse Enable Comments Options Sounder Bell Test Enable By Area CommentsBlock 4 Digital Communicator Programming Account #6 Account #3Account #4 Account #5Hour Zone Dial Delay Comments Options RPS Callback Enable CommentsKeypad RPS Enable Comments Alarm Dialing Delay Seconds CommentsKeypad and Accessory Tamper Report Routing Comments Power Supply Report RoutingInstaller Programming Report Routing Comments SpreadNet Transmitter Low Battery Report Routing CommentsBlock 5 Reporting Digits Programming Report Code, Tamper Zones 1 Report Code, Restoral Zones 1Report Code, Zone Bypass Zones 1 Comments Report Code, Trouble Zones 1 CommentsReport Code, Low Battery Report Code, Cancel Users 1 User #Report Code, AC Power Loss Report Code, AC Power RestoralReport Code, Ground Fault Restoral Report Code, Installer Programming StartReport Code, Installer Programming Complete Report Code, Ground FaultReport Code, Accessory Tamper Restoral Report Code, SpreadNet Keypad/Keyfob Low BatteryReport Code, SpreadNet Keypad/Keyfob Low Battery Restoral Report Code, Accessory TamperBlock 6 Real Time Clock Programming Block 7 Auxiliary Devices Programming Timer Units Remm #1, Relay #1 Exit Delay TerminatorTimer Units On Board Relay Timer Count On Board RelayTimer Count Remm #2, Relay #2 Timer Units Remm #2, Relay #1Timer Count Remm #2, Relay #1 Timer Units Remm #8, Relay #2Timed Relay Closing Timer #2 Day of Week Timed Relay Closing Timer #1 Day of WeekTimed Relay Closing Timer #1 Hours Timed Relay Closing Timer #1 MinutesBlock 9 Partition Area Programming Block 8 SpreadNet ProgrammingArea Assignments SpreadNet Keypads 1 Area Access by User Number User # 1First to Open/Last to Close Enable Comments Options Keypad Assignments to Areas Keypads 1User Codes User # 1 Area Access SN Keyfob/Remote # 1Block 10 User Code Programming User Codes User Codes Comments