Sierra S5832SG Backup Battery, AH Requirements for Backup, Sierra Accessory Loading, AC Power

Page 7

Backup Battery

The system employs one or more 6.5 AH (Model 1265) or 7.0 AH (Model 1270) sealed lead-acid storage battery. Connect the battery to the control panel PCB via the red (+) and black (-) leads. The battery should be replaced every 3 - 5 years.

When connecting two or more batteries in parallel, use the Model S5054 Auxiliary Battery Harness. Both batteries must have the same AH (Ampere-Hour) rating and should have the same lot number or date code. Figure 4, below, shows correct method for wiring the batteries in parallel.

NOTE: Up to 2 batteries may be connected in parallel to obtain the desired standby (backup) time.

 

Self-resetting

To S5053 LSM

circuit

 

or S5832SG

 

Control Panel

 

AH Requirements for Backup

Product/Device

4-Hour

24-Hour

72-Hour

Qty.

Total

S5832SG

0.5

AH

3.0 AH

9.0 AH

 

 

S5010

0.12 AH

0.72 AH

2.16 AH

 

 

S5020

0.12 AH

0.72 AH

2.16 AH

 

 

S5030

0.12 AH

0.72 AH

2.16 AH

 

 

S5050

0.4

AH

2.4 AH

7.2 AH

 

 

S5058

0.16 AH

0.96 AH

2.88 AH

 

 

S5070 (-2)

0.14 AH

0.84 AH

2.52 AH

 

 

SN915-BUS

0.5

AH

3.0 AH

9.0 AH

 

 

Sensor (10 mA)

0.04 AH

0.24 AH

0.72 AH

 

 

Sensor (25 mA)

0.1

AH

0.6 AH

1.8 AH

 

 

Bell/Siren (5 min)

0.085 AH

0.085 AH

0.085 AH

 

 

Bell/Siren (15 min)

0.225 AH

0.225 AH

0.225 AH

 

 

* Bell/Siren current may be

0.7 – 1.0 A

Total AH Required

 

Table 2 - AH Requirements

Determining Standby Battery Requirements

C & K Model 1265 or 1270

Figure 4

Connecting two Batteries in Parallel

Sierra Accessory Loading

C & K Model 1265 or 1270

To calculate the size (AH rating) of your system's Backup Battery, enter the Number (Qty) of devices of each type in the chart above. Multiply the number of devices times the AH rating for the desired backup period (Qty x AH = Total) and enter the total in the last column. To determine the total AH rating of the battery, add all values in the last column.

Total current from all sensors must be considered when calculating AH rating. For example:

Product Current Consumption

Max. Standby

Max. Active

S5832SG Control Panel

125 mA

125 mA

S5010

Alpha Keypad

30 mA

50 mA

S5020

Icon Keypad

30 mA

50 mA

S5030 LED Keypad

30 mA

50 mA

S5050

REMM (up to 2)

100 mA (each)

100 mA

(Relay/Event Memory Module)

 

 

S5058

ZEM (up to 3)

40 mA (each)

40 mA**

(Zone Expansion Module)

 

 

S5070 Single-line Digital

35 mA

60 mA

 

Communicator

 

 

S5070-2 Dual-line Digital

35 mA

70 mA

 

Communicator

 

 

SN915-BUS RF Receiver

125 mA

170 mA

 

** ZEM VOUT Terminals can supply up to 300 mA (max.)

Table 1 - Standby Battery Loading

 

Table 1 shows the current requirements for the Sierra S5832SG control panel and accessories. Additional infor- mation about Standby Battery requirements and Audible times may be found in Table 2 - AH Requirements, at the top of the next column.

10 sensors @ 10 mA = 100 mA

4 sensors @ 25 mA = 100 mA Total current all sensors = 200 mA

AC Power

The Sierra S5832SG receives its power from a 16.5 VAC 40 VA transformer. Connect the transformer to the AC In termi- nals on TB1 of the PCB (see Figure 1), using 18 AWG (1.02

mm)wire. (Some systems may have the transformer and mains fuse block installed and pre-wired from the factory.)

Connect the AC transformer to an unswitched receptacle. Do not share the secondary of the transformer with other devices.

NOTE: AC input requirements may vary by country. Refer to the Compliance section for additional wiring information.

3

Image 7
Contents Installation Instructions Page Table of Contents Singapore Sierra Accessory LoadingAH Requirements for Backup Country Specific Compliance InformationEarth Ground Panel Setup and InstallationIntroduction Mounting the PanelWiring Knock-outs Top AC Power Backup BatteryAH Requirements for Backup Sierra Accessory LoadingOutput Terminals Keypad WiringKeypad Wiring Sierra Accessory Wiring DistancesS5050 Relay/Event Memory Module AccessoriesZone Terminals On-Board Relay Terminals TB2S5058 Zone Expansion Module Digital Communicator Connections SN915-BUS SpreadNet ReceiverSN990/991 SpreadNet Keypad/Remote SN961 SpreadNet KeyfobRemote Programming RPS Programming the PanelTerminal Connections Zone LEDs Cmd Loc Data Value Press Home to activate the RPS featureProgramming With an LED Keypad ValueProgramming With an Icon Keypad Quick Programming ModeMenu Programming Mode Programming With an Alpha KeypadInstaller Walk-Test Installer Mode Options, BlockEvent Memory Battery Test Bypass 0 Home CancelEntry Delay Test Exit Delay TestBlock 1 Code Option Programming Block 2 Zone Configuration Programming Audible Cadence Zones 1 Chime Enable ZonesZone Bypass Enable Zones Zone Response Time Zones 1Block 3 Armed System Programming Low Battery Arming Comments Options Quick Bypass Enable CommentsHome Arm Exit Delay Enable 4X Exit Delay Extension Enable Comments OptionsSwinger Alarm Lockout Limit Comments Auto-Arming Enable AreaAuto-Disarming Enable Area Comments Auto-Disarming Enable Day of WeekDuress Active Only When Area Armed Sounder Turn-On Delay Following Alarm Seconds CommentsStrobe/Siren Disable with Low Battery Comments Options Soak Mode Learning Period Duration DaysHome Arming Enable Comments Options Keypad Tamper Switch Enable By Address Keypad #External Bell Reverse Enable Comments Options Sounder Bell Test Enable By Area CommentsBlock 4 Digital Communicator Programming Account #6 Account #3Account #4 Account #5Hour Zone Dial Delay Comments Options RPS Callback Enable CommentsKeypad RPS Enable Comments Alarm Dialing Delay Seconds CommentsKeypad and Accessory Tamper Report Routing Comments Power Supply Report RoutingInstaller Programming Report Routing Comments SpreadNet Transmitter Low Battery Report Routing CommentsBlock 5 Reporting Digits Programming Report Code, Tamper Zones 1 Report Code, Restoral Zones 1Report Code, Zone Bypass Zones 1 Comments Report Code, Trouble Zones 1 CommentsReport Code, Low Battery Report Code, Cancel Users 1 User #Report Code, AC Power Loss Report Code, AC Power RestoralReport Code, Ground Fault Restoral Report Code, Installer Programming StartReport Code, Installer Programming Complete Report Code, Ground FaultReport Code, Accessory Tamper Restoral Report Code, SpreadNet Keypad/Keyfob Low BatteryReport Code, SpreadNet Keypad/Keyfob Low Battery Restoral Report Code, Accessory TamperBlock 6 Real Time Clock Programming Block 7 Auxiliary Devices Programming Timer Units Remm #1, Relay #1 Exit Delay TerminatorTimer Units On Board Relay Timer Count On Board RelayTimer Count Remm #2, Relay #2 Timer Units Remm #2, Relay #1Timer Count Remm #2, Relay #1 Timer Units Remm #8, Relay #2Timed Relay Closing Timer #2 Day of Week Timed Relay Closing Timer #1 Day of WeekTimed Relay Closing Timer #1 Hours Timed Relay Closing Timer #1 MinutesBlock 9 Partition Area Programming Block 8 SpreadNet ProgrammingArea Assignments SpreadNet Keypads 1 Area Access by User Number User # 1First to Open/Last to Close Enable Comments Options Keypad Assignments to Areas Keypads 1Block 10 User Code Programming Area Access SN Keyfob/Remote # 1User Codes User # 1 User Codes User Codes Comments