Utilities
Proximity to utilities and drains
Consider proximity to required utilities, such as power, water, and network connections. While required utilities can be brought to nearly any selected site, there is a potential for increased costs and decreased efficiency when the HP POD 240a is located further from the utility source.
For utility clearance information, see HP POD 240a dimensions and required clearances (on page 8).
System utilities
The site location must accommodate the following utilities:
Water supply (on page 15)
Drainage (on page 16)
Power (on page 17)
Water supply
The HP POD 240a requires supply water for the humidifier. The supply water must meet the following requirements:
Requirement | Specification |
|
|
Pressure | between 0.1 and 0.8 MPa (1 and |
| 8 bars) |
Temperature | between 1 and 40 °C |
Instant | no lower than the rated flow of the |
| fill solenoid valve |
|
|
Connection | G3/4M |
Hardness | no greater than 40°fH (equal to |
| 400 ppm of CaCO3) |
|
|
Conductivity | 125 to 1250 μS/cm |
Organic compounds | None |
Do not treat the water with softeners, because softeners might produce foam, which affects the operation of the unit.
Do not use well water, industrial water, water from cooling circuits, or water contaminated by any chemicals or bacteria.
Do not add disinfectants or