A routine maintenance should be carried out at least once a year. Contact your local, certified service company for maintenance.
Problem |
| Cause |
| Solution |
Burners do | a. | No gas flow. | a. | Make sure that all gas valves are |
not ignite. |
|
|
| open and that gas is reaching unit. |
| b. | Gas container too cold | b. | Remove and control the gas valve |
|
| especially with butane. |
| at the connection (manual) or the |
|
| Water in gas freezes |
| LPG pressure regulator. Contact |
|
| in gas regulator. |
| gas company or distributor. |
|
|
|
|
|
Pilot burner | a. | Thermocouple tip is not | a. | Adjust thermocouple position. |
ignites. Main |
| enveloped by pilot flame. |
|
|
burner initially | b. | Thermocouple is not | b. | Only the themocouple tip should be |
ignites, but |
| heated enough by flame or |
| enveloped by the pilot flame and |
then goes out. |
| it is being heated along the |
| heated. The pilot flame must be |
|
| entire length too much. |
| strong and blue in color. |
| c. | Primary air intake blocked | c. | Clean or adjust opening according |
|
| or must be adjusted. |
| to table in page 9. |
| d. | Thermocouple is loose at | d. | Tighten all thermocouple |
|
| one of the connections. |
| connections. |
| e. | Defective thermocouple. | e. | Replace thermocouple (service co.). |
Burners too | a. | Gas pressure too low. | a. | Contact service or gas company. |
weak. | b. | Wrong orifice size. | b. | Install correct orifices. |
|
|
|
|
|
Burner |
| Too much primary air. |
| Adjust the primary air intake. |
|
|
| (contact service company) | |
Pilot flame | a. | Flames on pipe burners | a. | Block off holes on the main burner |
does not stay |
| disrupting pilot flame. |
| pipe directly below the pilot burner. |
on. | b. | Defective thermocouple. | b. | Replace thermocouple (service co.). |
|
|
|
|
|
1.12Testing or checking for safety
After a conversion, a new installation, or after a repair, it is important that the unit be tested to insure that it operates properly. This should include the following:
Test for gas leaks.
Check that the unit has enough clearance behind and to the sides.
Check that enough primary and secondary air is available (strong blue flames). Check for potentially flammable objects or potential flammability problems. Check the gas distribution systems.
Check for proper ventilation and exhaust. Check for proper room ventilation.