Raypak 850, 300 operating instructions Gas Supply Connection, Gas Supply Pressure

Page 16
Gas Supply

Gas Supply

DANGER: Make sure the gas on which the heater will operate is the same type as specified on the rat- ing plate.

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve lo- cated outside the heater jacket. It is recommended that a union be installed in the gas supply piping adja- cent to the heater for servicing. The gas supply pressure to the heater must not exceed 10.5 in. WC for natural gas or 13.0 in. WC for propane gas. A pounds- to-inches regulator must be installed to reduce the gas supply pressure if it is higher than noted above. This regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls. Refer to Table J for maximum pipe lengths.

Gas Supply Connection

CAUTION: The heater must be disconnected from the gas supply during any pressure testing of the gas supply system at test pressures in excess of 1/2 psi (3.45 kPa).

The heater must be isolated from the gas supply pip- ing system by closing the upstream manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa). Relieve test pressure in the gas supply line prior to re-connecting the heater and its manual shut-off valve to the gas supply line. FAILURE

TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. Over-pressurized gas valves are not covered by warranty. The heater and its gas con- nections shall be leak-tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use an open flame.

CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with natural and propane gases is recommended. Apply sparingly only on male pipe ends, leaving the two end threads bare.

CAUTION: Support gas supply piping with hangers, not by the heater or its accessories. Make sure the gas piping is protected from physical damage and freezing, where required.

Gas Supply Pressure

A minimum of 4.0 in. WC and a maximum of 10.5 in. WC upstream gas pressure is required under load and no-load conditions for natural gas. A minimum of 4.0 in. WC and a maximum of 13.0 in. WC is required for propane gas. The gas pressure regulator(s) supplied on the heater is for low-pressure service. If upstream pressure exceeds these values, an intermediate gas pressure regulator, of the lockup type, must be installed.

When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to determine if it has adequate capacity for the combined load. The gas valve pressure regulator on the heater is nominally preset as noted in Table I.

During normal operation, carbon dioxide should be 8.5 to 9.0% at full fire for natural gas and between 9.0 and 9.5% for propane gas. Carbon monoxide should be ‹150 ppm.

Model

Manifold Pressure (in. WC)

Natural Gas

Propane Gas

No.

 

High

Low

High

Low

300

-0.2

-0.1

-0.2

-0.1

500

-0.3

-0.1

-0.3

-0.1

850

-3.2

-0.2

-2.7

-0.1

NOTE: Manifold pressures should be ±0.3 in. WC.

Table I: Manifold Gas Pressure Settings

Fig. 10: Gas Supply Connection

16

Image 16
Contents WHAT TO DO IF YOU SMELL GAS Do not try to light any applianceINSTALLATION & OPERATING INSTRUCTIONS Models 300, 500 & Types H & WPage CONTENTS BEFORE INSTALLATIONGENERAL SAFETY INSTALLATION WIRING DIAGRAM START-UPWARNINGS Pay Attention to These TermsBEFORE INSTALLATION Installations at ElevationProduct Receipt Model IdentificationComponent Locations General InformationGENERAL SAFETY Time/Temperature Relationships in ScaldsINSTALLATION Installation CodesIndoor Installations Outdoor InstallationsCombustion and Ventilation Air Indoor UnitsCanadian Installations2 U.S. Installations1Table F Vent/Air Inlet Termination Clearances U.S. Installations Conventional Combustion Air SupplyCombustion Air Filter Direct VentWater Piping Canadian InstallationsGeneral Relief Valve Installation and Piping Hydronic HeatingTemperature & Pressure Gauge Hydrostatic TestThree-WayValves Air-Separation/ExpansionTankDomestic Hot Water Potable Water and Space Heating Gas Supply Gas Supply ConnectionGas Supply Pressure Electrical Power Connections Making the Electrical Connections Check the Power SourceField-ConnectedControllers Field Wiring Connections Wiring the ThermostatWiring the Indirect Sensor Wiring the Outdoor SensorWiring the Cascade System Communication Bus 3.Create a hole to route the communication cables through where the dimples are in the side of the cabinet see Fig. 15, or route the wires to the rear junction box and out of the cabinet Cascade Master Pump and Sensor Wiring Venting Cascade Follower Pump and Sensor WiringGeneral Support of Vent Stack Vent Terminal LocationConfiguration CombustionVenting Configurations Venting Installation TipsVertical Venting Category Combustion Volume of Common VentingModel No Vent SizeHorizontal Through-the-WallDirect Venting CategoryFig. 21 Typical Common Venting Fig. 22 Horizontal Through-the-WallVentingInstallation TerminationModel No Approved IntakesDirect Vent-Vertical Outdoor Installation Freeze ProtectionHigh Limit - Manual Reset High Limit - Auto Reset OptionalControls Ignition Control FunctionsFlow Switch High & Low Gas Pressure Switches OptionalBlocked Vent Switch Low Water Cut-OffOptionalAdjusting the XFyre Setpoint Operating InstructionsBlocked Condensate Drain Sensor User MenuService Mode Status MenuStatus Menu 1 Items Status Menu 2 Items Installer Menu Items continued Installer Menu WIRING DIAGRAM For Your Safety START-UPPre Start-up Pre Start-upCheckStart-Up PreparationBlower Check Safety Inspection Manifold CheckFinishing Follow-UpLighting Instructions OPERATIONPost Start-UpCheck TROUBLESHOOTING XFyre Error CodesHeater Errors Heater FaultsXFyre Fault Text Remedy FLUE / GAS PRESS F01Sensor Resistance Values Temperature SensorsResistance ohms OutdoorMAINTENANCE Suggested Minimum Maintenance SchedulePreventive Maintenance Schedule DailyWeekly Semi-AnnuallyAnnually As RequiredCombustion Chamber Coil Cleaning Instructions NIOSH stated First AidAPPENDIX Inside Air Contamination248 CMR 5.082a1 through LIMITED PARTS WARRANTY XFYRE - TYPE H and W HEAT EXCHANGER WARRANTYMODELS SCOPESTART-UPCHECKLIST FOR THE XFYRE EMISSIONS SETTINGS AND TEST INFORMATIONNominal Factory Recommended Settings GAS SUPPLY DATA
Related manuals
Manual 8 pages 63.38 Kb Manual 8 pages 12.19 Kb

300, 850 specifications

Raypak is a renowned name in the heating industry, particularly known for its high-quality pool and spa heaters. Among their extensive product line, the Raypak 850, 500, 300, 400, and 700 models stand out for their reliability, efficiency, and cutting-edge technologies. Each model is designed to cater to different needs and applications while maintaining Raypak’s commitment to performance.

The Raypak 850 is designed for larger commercial pools or residential setups requiring high output. With a powerful heat exchanger made from copper and bronze, it ensures superior heat transfer and longevity. Its digital control system provides precise temperature regulation, enhancing user experience. Moreover, it features a durable construction with weather-resistant materials, ensuring lasting performance in various environments.

The Raypak 500 model offers a balance between efficiency and compactness. It features eco-friendly technology that reduces energy consumption without sacrificing performance. The integrated thermostat allows users to maintain consistent water temperatures, making it ideal for residential pools. This model is well-regarded for its user-friendly digital display, simplifying operation and monitoring.

For those needing a more moderate capacity, the Raypak 300 is an efficient choice. It combines robust engineering with an easy-to-use interface. Its advanced ignition system improves reliability while minimizing energy waste. The Raypak 300’s compact design allows for easy installation in various spaces, making it an excellent option for smaller pools.

The Raypak 400 heats water quickly and efficiently, making it suitable for both residential pools and spas. It features a high-capacity heating system that ensures optimal performance. With a clear LED display, users can easily monitor their settings, while the integrated diagnostics provide real-time feedback for maintenance and troubleshooting.

Lastly, the Raypak 700 model is known for its versatility and robust performance. It is equipped with advanced safety features, including a high limit switch and water flow detection mechanism, to ensure safe operation. The model's energy-efficient design enhances its eco-friendliness, making it a popular choice among environmentally conscious users.

Collectively, these Raypak models exemplify superior engineering, performance, and user-friendliness. Their innovative features ensure that they meet the varied demands of pool owners while providing reliable heating solutions for leisure and relaxation. Whether for commercial or residential use, the Raypak 850, 500, 300, 400, and 700 offer unmatched quality and efficiency.