Raypak 850, 300 operating instructions Wiring the Outdoor Sensor, Wiring the Indirect Sensor

Page 20
Wiring the Outdoor Sensor

Wiring the Outdoor Sensor

1.There is no connection required if an outdoor sen- sor is not used in this installation.

2.If using an Outdoor Sensor, connect the wires for sensor to the terminals marked OUTDOOR SEN (shown in Fig. 16) in the electrical junction box. Caution should be used to ensure neither of these terminals becomes connected to ground.

3.Use a minimum 22 AWG wire for runs of 100 feet or less, and minimum 18 AWG wire for runs of up to 150 feet.

4.Mount the outdoor sensor on an exterior surface of the building, preferably on the north side in an area that will not be affected by direct sunlight and that will be exposed to varying weather conditions.

Wiring the Indirect Sensor

1.There is no indirect sensor connection required if an indirect water heater is not used in the installa- tion.

2.The XFyre boiler will operate an indirect fired water heater with either a thermostat type aquas- tat installed in the indirect tank or a Raypak tank sensor. When a tank sensor is used, the XFyre control will automatically detect its presence and a demand for heat from the indirect water heater will be generated when the tank temperature falls below the user settable setpoint by more than the user selectable offset. The demand will continue until the sensor measures that the indirect water heater temperature is above the setpoint.

3.Connect the indirect tank sensor to the terminals marked DHW SENSOR (shown in Fig. 16) in the electrical junction box. Caution should be used to ensure neither of these terminals becomes con- nected to ground.

Wiring the Optional 0–10 Volt Building Control Signal

1.A signal from a building management system may be connected to the XFyre boiler to enable remote control. This signal should be a 0–10 volt positive DC signal. When this input is enabled using the installer menu, a building control system can be used to control either the setpoint temperature or the heat output of the XFyre boiler. The control interprets the 0–10 volt signal as follows. When the signal is between 0 and 1 volt, the XFyre boiler will be in stand by mode, not firing. When the signal rises above 1 volt, the XFyre boiler will ignite. As the signal continues to rise towards its maximum of 10 volts, the XFyre boiler will increase either in setpoint temperature or firing rate, depending on the setting of screen 17 in the installer menu. See the Installer Menu section for details on the setting of screens 16 and 17 for this option.

2.Connect a building management system or other auxiliary control signal to the terminals marked +0–10 V and -0–10 V in the electrical junction box (shown in Fig. 16) Caution should be used to ensure that the +0–10 V connection does not become connected to ground.

Wiring the Cascade System Communication Bus

1.Use standard CAT3 or CAT5 computer network patch cables to connect the communication bus between each of the boilers. These cables are readily available at any office supply, computer, electronic, department or discount home supply store in varying lengths.

2.It is recommended that the shortest length cable possible be used to reach between the boilers and create a neat installation. Do not run unprotected cables across the floor or where they will become wet or damaged. Avoid running communication cables parallel with, or close to or against, high voltage (120 volt or greater) wiring. Raypak rec- ommends that the total maximum length of communication bus cables not exceed 200 feet.

20

Image 20
Contents WHAT TO DO IF YOU SMELL GAS Do not try to light any applianceINSTALLATION & OPERATING INSTRUCTIONS Models 300, 500 & Types H & WPage CONTENTS BEFORE INSTALLATIONGENERAL SAFETY INSTALLATION WIRING DIAGRAM START-UPWARNINGS Pay Attention to These TermsBEFORE INSTALLATION Installations at ElevationProduct Receipt Model IdentificationComponent Locations General InformationGENERAL SAFETY Time/Temperature Relationships in ScaldsINSTALLATION Installation CodesIndoor Installations Outdoor InstallationsCombustion and Ventilation Air Indoor UnitsTable F Vent/Air Inlet Termination Clearances U.S. Installations1Canadian Installations2 U.S. Installations Conventional Combustion Air SupplyCombustion Air Filter Direct VentGeneral Canadian InstallationsWater Piping Relief Valve Installation and Piping Hydronic HeatingTemperature & Pressure Gauge Hydrostatic TestDomestic Hot Water Air-Separation/ExpansionTankThree-WayValves Potable Water and Space Heating Gas Supply Pressure Gas Supply ConnectionGas Supply Electrical Power Connections Field-ConnectedControllers Check the Power SourceMaking the Electrical Connections Field Wiring Connections Wiring the ThermostatWiring the Cascade System Communication Bus Wiring the Outdoor SensorWiring the Indirect Sensor 3.Create a hole to route the communication cables through where the dimples are in the side of the cabinet see Fig. 15, or route the wires to the rear junction box and out of the cabinet Cascade Master Pump and Sensor Wiring General Cascade Follower Pump and Sensor WiringVenting Support of Vent Stack Vent Terminal LocationConfiguration CombustionVertical Venting Category Venting Installation TipsVenting Configurations Combustion Volume of Common VentingModel No Vent SizeHorizontal Through-the-WallDirect Venting CategoryFig. 21 Typical Common Venting Fig. 22 Horizontal Through-the-WallVentingInstallation TerminationModel No Approved IntakesDirect Vent-Vertical Outdoor Installation Freeze ProtectionHigh Limit - Manual Reset High Limit - Auto Reset OptionalControls Ignition Control FunctionsFlow Switch High & Low Gas Pressure Switches OptionalBlocked Vent Switch Low Water Cut-OffOptionalAdjusting the XFyre Setpoint Operating InstructionsBlocked Condensate Drain Sensor User MenuService Mode Status MenuStatus Menu 1 Items Status Menu 2 Items Installer Menu Items continued Installer Menu WIRING DIAGRAM For Your Safety START-UPPre Start-up Pre Start-upCheckBlower Check PreparationStart-Up Safety Inspection Manifold CheckFinishing Follow-UpPost Start-UpCheck OPERATIONLighting Instructions TROUBLESHOOTING XFyre Error CodesHeater Errors Heater FaultsXFyre Fault Text Remedy FLUE / GAS PRESS F01Sensor Resistance Values Temperature SensorsResistance ohms OutdoorMAINTENANCE Suggested Minimum Maintenance SchedulePreventive Maintenance Schedule DailyWeekly Semi-AnnuallyAnnually As RequiredCombustion Chamber Coil Cleaning Instructions NIOSH stated First AidAPPENDIX Inside Air Contamination248 CMR 5.082a1 through LIMITED PARTS WARRANTY XFYRE - TYPE H and W HEAT EXCHANGER WARRANTYMODELS SCOPESTART-UPCHECKLIST FOR THE XFYRE EMISSIONS SETTINGS AND TEST INFORMATIONNominal Factory Recommended Settings GAS SUPPLY DATA
Related manuals
Manual 8 pages 63.38 Kb Manual 8 pages 12.19 Kb

300, 850 specifications

Raypak is a renowned name in the heating industry, particularly known for its high-quality pool and spa heaters. Among their extensive product line, the Raypak 850, 500, 300, 400, and 700 models stand out for their reliability, efficiency, and cutting-edge technologies. Each model is designed to cater to different needs and applications while maintaining Raypak’s commitment to performance.

The Raypak 850 is designed for larger commercial pools or residential setups requiring high output. With a powerful heat exchanger made from copper and bronze, it ensures superior heat transfer and longevity. Its digital control system provides precise temperature regulation, enhancing user experience. Moreover, it features a durable construction with weather-resistant materials, ensuring lasting performance in various environments.

The Raypak 500 model offers a balance between efficiency and compactness. It features eco-friendly technology that reduces energy consumption without sacrificing performance. The integrated thermostat allows users to maintain consistent water temperatures, making it ideal for residential pools. This model is well-regarded for its user-friendly digital display, simplifying operation and monitoring.

For those needing a more moderate capacity, the Raypak 300 is an efficient choice. It combines robust engineering with an easy-to-use interface. Its advanced ignition system improves reliability while minimizing energy waste. The Raypak 300’s compact design allows for easy installation in various spaces, making it an excellent option for smaller pools.

The Raypak 400 heats water quickly and efficiently, making it suitable for both residential pools and spas. It features a high-capacity heating system that ensures optimal performance. With a clear LED display, users can easily monitor their settings, while the integrated diagnostics provide real-time feedback for maintenance and troubleshooting.

Lastly, the Raypak 700 model is known for its versatility and robust performance. It is equipped with advanced safety features, including a high limit switch and water flow detection mechanism, to ensure safe operation. The model's energy-efficient design enhances its eco-friendliness, making it a popular choice among environmentally conscious users.

Collectively, these Raypak models exemplify superior engineering, performance, and user-friendliness. Their innovative features ensure that they meet the varied demands of pool owners while providing reliable heating solutions for leisure and relaxation. Whether for commercial or residential use, the Raypak 850, 500, 300, 400, and 700 offer unmatched quality and efficiency.