Raypak 300, 850 Combustion Chamber Coil Cleaning Instructions, NIOSH stated First Aid

Page 51
NIOSH stated First Aid:

WARNING:

The combustion chamber insulation in this product contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded that “Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group1).”:

Avoid breathing dust and contact with skin and eyes.

Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at

http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and

phone numbers are also listed on this website.

Wear long-sleeved, loose fitting clothing, gloves, and eye protection.

Apply enough water to the combustion chamber lining to prevent dust

Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.

NIOSH stated First Aid:

Eye: Irrigate immediately

Breathing: Fresh air.

Combustion Chamber Coil Cleaning Instructions

Before beginning this procedure, you must have on hand the following items:

a nylon, stainless steel or brass brush (not steel)

“Rydlyme” (recommended for best results) or “CLR”

Gloves, eye protection

1.Shut down the XFyre boiler by using the following steps:

a.Close the gas valve, shut down the unit and wait for the unit to be cool to the touch.

b.Disconnect the condensate piping from the out- side connection, (not from the XFyre boiler side), so the flow from condensate reservoir can be observed.

c.Disconnect electrical connections from the gas valve, spark electrode and flame rectification probe and combustion blower.

d.Remove the (4) screws on the aluminum ¾” NPT connector on the right side of the gas valve.

e.Disconnect the wiring connected to the com- bustion blower motor.

f.Remove the (6) 10mm nuts from the burner plate assembly.

g.Pull the entire burner plate assembly (with blower still attached) towards you, while removing or pushing aside any wiring to allow the removal of the assembly.

2.Using a spray bottle filled with the recommended product “RYDLYME” or “CLR”, spray liberally on the coils, making sure the solution penetrates and fun- nels down through the condensate system. If the condensate system is blocked, let the chemical penetrate for at least 15 minutes or until it drains.

3.Use the nylon, stainless steel or brass brush (do not use steel) to scrub coils to remove any buildup, then vacuum the debris from the coils. Be sure to fol- low the precautions listed for working with ceramic fibers.

4.Spray the coils with clear water, making sure to con- fine the spray to the area being cleaned (Try to avoid getting the back ceramic wall of the unit wet). Flush the combustion chamber with fresh water until clear water runs from the condensate drain. At this point, the XFyre should be ready to be re- assembled.

a. Inspect gaskets.

b. Re-install the burner assembly.

51

Image 51
Contents Models 300, 500 & Types H & W WHAT TO DO IF YOU SMELL GASDo not try to light any appliance INSTALLATION & OPERATING INSTRUCTIONSPage WIRING DIAGRAM START-UP CONTENTSBEFORE INSTALLATION GENERAL SAFETY INSTALLATIONPay Attention to These Terms WARNINGSModel Identification BEFORE INSTALLATIONInstallations at Elevation Product ReceiptGeneral Information Component LocationsTime/Temperature Relationships in Scalds GENERAL SAFETYOutdoor Installations INSTALLATIONInstallation Codes Indoor InstallationsIndoor Units Combustion and Ventilation AirU.S. Installations1 Canadian Installations2Table F Vent/Air Inlet Termination Clearances Direct Vent U.S. InstallationsConventional Combustion Air Supply Combustion Air FilterCanadian Installations Water PipingGeneral Hydrostatic Test Relief Valve Installation and PipingHydronic Heating Temperature & Pressure GaugeAir-Separation/ExpansionTank Three-WayValvesDomestic Hot Water Potable Water and Space Heating Gas Supply Connection Gas SupplyGas Supply Pressure Electrical Power Connections Check the Power Source Making the Electrical ConnectionsField-ConnectedControllers Wiring the Thermostat Field Wiring ConnectionsWiring the Outdoor Sensor Wiring the Indirect SensorWiring the Cascade System Communication Bus 3.Create a hole to route the communication cables through where the dimples are in the side of the cabinet see Fig. 15, or route the wires to the rear junction box and out of the cabinet Cascade Master Pump and Sensor Wiring Cascade Follower Pump and Sensor Wiring VentingGeneral Combustion Support of Vent StackVent Terminal Location ConfigurationVenting Installation Tips Venting ConfigurationsVertical Venting Category Combustion Vent Size Volume ofCommon Venting Model NoFig. 22 Horizontal Through-the-WallVenting Horizontal Through-the-WallDirectVenting Category Fig. 21 Typical Common VentingApproved Intakes InstallationTermination Model NoDirect Vent-Vertical Freeze Protection Outdoor InstallationIgnition Control Functions High Limit - Manual ResetHigh Limit - Auto Reset Optional ControlsLow Water Cut-OffOptional Flow SwitchHigh & Low Gas Pressure Switches Optional Blocked Vent SwitchUser Menu Adjusting the XFyre SetpointOperating Instructions Blocked Condensate Drain SensorStatus Menu Service ModeStatus Menu 1 Items Status Menu 2 Items Installer Menu Items continued Installer Menu WIRING DIAGRAM Pre Start-upCheck For Your SafetySTART-UP Pre Start-upPreparation Start-UpBlower Check Follow-Up Safety InspectionManifold Check FinishingOPERATION Lighting InstructionsPost Start-UpCheck Heater Faults TROUBLESHOOTINGXFyre Error Codes Heater ErrorsXFyre Fault Text FLUE / GAS PRESS F01 RemedyOutdoor Sensor Resistance ValuesTemperature Sensors Resistance ohmsDaily MAINTENANCESuggested Minimum Maintenance Schedule Preventive Maintenance ScheduleAs Required WeeklySemi-Annually AnnuallyNIOSH stated First Aid Combustion Chamber Coil Cleaning InstructionsInside Air Contamination APPENDIX248 CMR 5.082a1 through SCOPE LIMITED PARTS WARRANTY XFYRE - TYPE H and WHEAT EXCHANGER WARRANTY MODELSGAS SUPPLY DATA START-UPCHECKLIST FOR THE XFYREEMISSIONS SETTINGS AND TEST INFORMATION Nominal Factory Recommended Settings
Related manuals
Manual 8 pages 63.38 Kb Manual 8 pages 12.19 Kb

300, 850 specifications

Raypak is a renowned name in the heating industry, particularly known for its high-quality pool and spa heaters. Among their extensive product line, the Raypak 850, 500, 300, 400, and 700 models stand out for their reliability, efficiency, and cutting-edge technologies. Each model is designed to cater to different needs and applications while maintaining Raypak’s commitment to performance.

The Raypak 850 is designed for larger commercial pools or residential setups requiring high output. With a powerful heat exchanger made from copper and bronze, it ensures superior heat transfer and longevity. Its digital control system provides precise temperature regulation, enhancing user experience. Moreover, it features a durable construction with weather-resistant materials, ensuring lasting performance in various environments.

The Raypak 500 model offers a balance between efficiency and compactness. It features eco-friendly technology that reduces energy consumption without sacrificing performance. The integrated thermostat allows users to maintain consistent water temperatures, making it ideal for residential pools. This model is well-regarded for its user-friendly digital display, simplifying operation and monitoring.

For those needing a more moderate capacity, the Raypak 300 is an efficient choice. It combines robust engineering with an easy-to-use interface. Its advanced ignition system improves reliability while minimizing energy waste. The Raypak 300’s compact design allows for easy installation in various spaces, making it an excellent option for smaller pools.

The Raypak 400 heats water quickly and efficiently, making it suitable for both residential pools and spas. It features a high-capacity heating system that ensures optimal performance. With a clear LED display, users can easily monitor their settings, while the integrated diagnostics provide real-time feedback for maintenance and troubleshooting.

Lastly, the Raypak 700 model is known for its versatility and robust performance. It is equipped with advanced safety features, including a high limit switch and water flow detection mechanism, to ensure safe operation. The model's energy-efficient design enhances its eco-friendliness, making it a popular choice among environmentally conscious users.

Collectively, these Raypak models exemplify superior engineering, performance, and user-friendliness. Their innovative features ensure that they meet the varied demands of pool owners while providing reliable heating solutions for leisure and relaxation. Whether for commercial or residential use, the Raypak 850, 500, 300, 400, and 700 offer unmatched quality and efficiency.