Nordyne G6RD 93+ Venting Requirements, Vent Pipe Material, Vent Pipe Length and Diameter

Page 14

inches of free area. See Figure 9. For example, if the combined input rate of all appliances is less than or equal to 100,000 Btuh, each opening must have a free area of at least 100 square inches. If the combined input rate of all appli- ances is 120,000 Btuh, each opening must have a free area of at least 120 square inches.

Air Directly Through An Exterior Wall

If combustion air is provided directly through an exterior wall, the two openings must each have free area of at least one square inch per 4000 Btuh of total appliance input. (See Figure 10.)

Outdoor Air Through Vertical Openings or Ducts If combustion air is provided through vertical ducts or openings to attics or crawl spaces, the two openings must each have free area of at least one square inch per 4000 Btuh of total appliance input. Ducts must have cross-sec- tional areas at least as large as the free area of their respective openings to the furnace space. Attics or crawl spaces must communicate freely with the outdoors if they are the source of air for combustion and ventilation. (See Figures 11 and 12.)

Outdoor Air Through Horizontal

Openings or Ducts

If combustion air is taken from outdoors through horizontal ducts, the openings must each have free area of at least one square inch per 2000 Btuh of total appliance input. Ducts must have cross-sectional area at least as large as the free area of their respective openings to the furnace space. (See Figure 13.)

!CAUTION:

Do not supply combustion air from an attic space that is equipped with power ventilation or any other device that may produce a negative pressure.

VENTING REQUIREMENTS

This section specifies installation requirements for vent and "2-pipe" combustion air piping. For "one pipe" installations, install vent piping per this section and provide air for combustion and ventilation per the previous section. The capac- ity table provided in this section applies to the total of vent and combustion air piping for either type of installation.

NORDYNE condensing furnaces are classified as "Category IV" appliances, which require spe- cial venting materials and installation proce- dures. Category IV appliances operate with positive vent pressure and therefore require vent systems which are thoroughly sealed. They also produce combustion condensate, which is slightly acidic and can cause severe corrosion of ordinary venting materials. Furnace operation can be adversely affected by restrictive vent and combustion air piping. Therefore, vent and com- bustion air piping lengths must conform com- pletely to the requirements of Table 5.

The furnace must be vented to the outdoors. It must not be vented in common with any other appliance, even if that appliance is of the con- densing type. Common venting can result in severe corrosion of other appliances or their venting and can allow combustion gases to escape through such appliances or vents. Do not vent the furnace to a fireplace chimney or building chase.

!WARNING:

FURNACE MUST NOT BE COMMON VENTED WITH OTHER APPLIANCES.

Vent Pipe Material

Vent and combustion air pipe and fittings must be one of the following materials and must conform to the indicated ANSI/ASTM standards:

Material

Standard

Schedule 40 PVC

D1785

PVC-DWV

D2665

SDR-21*

D2241

& SDR-26*

 

ABS-DWV

D2661

Schedule 40 ABS

F628

Cement and primer must conform to ATSM Standard D2564 for PVC and Standard D2235 for ABS. When joining PVC piping to ABS, use PVC solvent cement. (See procedure specified in ASTM Standard D3138.)

Vent Pipe Length and Diameter

In order for the furnace to operate properly, the combustion air and vent piping must not be exces- sively restrictive. To ensure this use Table 5, which indicates the maximum allowable piping length for a furnace of specified input rate, when installed

14

Image 14
Contents Installation Instructions What to do if YOU Smell GASPage Table of Contents Dimensions Upflow G6RC & G6RD FurnacesDownflow G6RL Furnace Furnace Airflow Data High 1910 1860 1780 1700 1620 1520 1420Model Input Motor Number Btuh Speed Installation Requirements Requirements and Codes Clearances to Combustible MaterialsLocation Horizontal InstallationsSupply AIR Plenum Installation Downflow Warning G6RL ModelsCirculating AIR Supply Furnace on a Concrete Slab Return Air Venting and Combustion AIR Requirements40,000 100 sq. 60,000 80,000 MinimumFree Area Installation In a Confined Space Air Requirements For One-Pipe InstallationInstallation In An Unconfined Space Air From InsideVent Pipe Length and Diameter Venting RequirementsVent Pipe Material Air Directly Through An Exterior WallExample Vent Pipe InstallationSolution Pipe Routing and SupportG6RC & G6RD Upflow Furnaces G6RL Downflow FurnacesG6RL Downflow Furnaces G6RC & G6RD UpflowFurnaces G6RC & G6RD Upflow FurnacesLocation of Outdoor Terminations Vent Termination ClearancesAlternate Horizontal Vent Installation Horizontal VentingConcentric Vent Termination Vertical VentingVent Freezing Protection Drainage of Condensate from Furnace Vertical Vent TerminationGAS Supply and Piping Leak CheckNatural Gas High Altitude Conversion ConversionHigh Altitude Application LP/Propane Gas Sea Level and High Altitude ConversionElectrical Wiring Line Voltage WiringFurnace Rating Orifice Drill Size Plate Input Btu/h Nat START-UP and AdjustmentsLow Voltage Wiring Above Sea LevelElectrical Data Start-Up ProcedureVerifying and Adjusting Firing Rate Verifying and Adjusting Temperature Rise Verifying Burner OperationGAS Flow Rate Cubic Feet PER Hour Gas Flow RateVerifying Operation of the Supply Air Limit Switch Description of ComponentsG6RC, G6RD and G6RL Integrated Control Board System Diagram For G6RC, G6RD and G6RL Residential FurnacesMaintenance System Operation InformationG6RL Downflow Furnace Location of Major ComponentsSequence of Operation Heating ModeCooling Mode Twinning of Two Furnaces Fan ModeFurnace Fails to Operate INSTALLATION/PERFORMANCE Check List Fuel Type¢707931*¤