Nordyne G6RC 90+, G6RL 90+, G6RD 93+ Furnace Fails to Operate, Twinning of Two Furnaces, Fan Mode

Page 34

Fan Mode:

1.On a call for fan operation, the thermostat applies 24 VAC to the G terminal on the furnace control board.

2.The circulating air blower is energized im- mediately on the heating speed.

3.If the furnace is operated in the continuous ON position at the thermostat and is then switched to AUTO, the circulating blower will operate for a specified delay (factory set at 120 seconds).

Furnace Fails to Operate

If the furnace does not operate check the follow- ing:

1.Is the thermostat operating properly?

2.Are the blower compartment door(s) in place?

3.Is the furnace disconnect closed?

4.Has the circuit breaker tripped or the control board fuse burned open?

5.Is the gas turned on?

6.Are any manual reset switches open?

7.Is the filter dirty or plugged?

8.Is the flame sensor coated? (Remove and clean with emery cloth.)

If the furnace locks out after 5 attempts for ignition, it will try again every hour if a call for heat remains. If the inducer and circulating air blowers are operating, and items 1 through 8 have been checked, press the red reset button on the vent safety switch. (See Figure 28.) If the furnace operates after depressing the reset button, contact a qualified serviceman to identify and repair the problem.

If the furnace continues to not operate, depress the red reset buttons on the flame rollout switches. (See Figure 28.) If the furnace operates after depressing the reset buttons, contact a qualified servicemen to identify and repair the problem.

Twinning of Two Furnaces

The control board on these furnaces is capable of being twinned to another G6 furnace, pro- vided the circuit boards are both UTEC type. If using UTEC control boards, leave the fuses installed on each board. The thermostat wires and the 1/4 inch quick-connect terminals marked "TWIN" on the furnace controls must be con- nected together for twinning. (See Figure 29.)

Thermostat

W G Y R

R

C

Y

G

W

Twin Terminal

R

C

Y

G W

Twin Terminal

A/C

Unit

Figure 29. Twinning

34

Image 34
Contents Installation Instructions What to do if YOU Smell GASPage Table of Contents Dimensions Upflow G6RC & G6RD FurnacesDownflow G6RL Furnace Furnace Airflow Data High 1910 1860 1780 1700 1620 1520 1420Model Input Motor Number Btuh Speed Installation Requirements Requirements and Codes Clearances to Combustible MaterialsLocation Horizontal InstallationsSupply AIR Plenum Installation Downflow Warning G6RL ModelsCirculating AIR Supply Furnace on a Concrete SlabReturn Air Venting and Combustion AIR RequirementsFree Area Minimum40,000 100 sq. 60,000 80,000 Installation In a Confined Space Air Requirements For One-Pipe InstallationInstallation In An Unconfined Space Air From InsideVent Pipe Length and Diameter Venting RequirementsVent Pipe Material Air Directly Through An Exterior WallExample Vent Pipe InstallationSolution Pipe Routing and SupportG6RC & G6RD Upflow Furnaces G6RL Downflow FurnacesG6RL Downflow Furnaces G6RC & G6RD UpflowFurnaces G6RC & G6RD Upflow FurnacesLocation of Outdoor Terminations Vent Termination ClearancesAlternate Horizontal Vent Installation Horizontal VentingVent Freezing Protection Vertical VentingConcentric Vent Termination Drainage of Condensate from Furnace Vertical Vent TerminationGAS Supply and Piping Leak CheckNatural Gas High Altitude Conversion ConversionHigh Altitude Application LP/Propane Gas Sea Level and High Altitude ConversionElectrical Wiring Line Voltage WiringFurnace Rating Orifice Drill Size Plate Input Btu/h Nat START-UP and AdjustmentsLow Voltage Wiring Above Sea LevelVerifying and Adjusting Firing Rate Start-Up ProcedureElectrical Data Verifying and Adjusting Temperature Rise Verifying Burner OperationGAS Flow Rate Cubic Feet PER Hour Gas Flow RateVerifying Operation of the Supply Air Limit Switch Description of ComponentsG6RC, G6RD and G6RL Integrated Control Board System Diagram For G6RC, G6RD and G6RL Residential FurnacesMaintenance System Operation InformationG6RL Downflow Furnace Location of Major ComponentsCooling Mode Heating ModeSequence of Operation Furnace Fails to Operate Fan ModeTwinning of Two Furnaces INSTALLATION/PERFORMANCE Check List Fuel Type¢707931*¤