Nordyne G6RL 90+, G6RC 90+, G6RD 93+ Location of Outdoor Terminations, Vent Termination Clearances

Page 18

Piping must be mechanically supported so that its weight does not bear on the furnace. Sup- ports must be at intervals no greater than five feet, and at smaller intervals if necessary to ensure that there are no sagging sections to trap water. (See Figures 14 and 15.)

Figure 16 illustrates vent and combustion air pipe sizes exiting the furnace. Transition to the correct pipe size must be done close to the furnace so that the full length of pipe is of proper size.

Straight neoprene couplings are supplied with the downflow furnaces only. These couplings are to be installed in the combustion air inlet (if present) and exhaust vent piping at the furnace as shown in Figures 13 and 14. For an upflow furnace installation, if breakable connections are required in the combustion air inlet (if present) and exhaust vent piping, then straight neoprene couplings for 2” or 3” piping with hose clamps can be used. These couplings can be ordered through your local furnace distributor.

To install a coupling, slide the rubber coupling over the end of the pipe that is attached to the furnace and secure it with one of the hose clamps. Then slide the other end of the rubber coupling onto the other pipe from the vent and secure the coupling with the second hose clamp. Ensure that the connection is tight and leak free.

NORDYNE condensing furnaces have been certified for installation with zero clearance be-

tween vent piping and combustible surfaces. However, it is good practice to allow space for convenience in installation and service.

Location of Outdoor Terminations

Vent and combustion air intake terminations must be located to ensure proper furnace opera- tion and to conform to applicable codes. Figure

16illustrates necessary distances from the vent termination to windows and building air intakes.

In Canada, the Canadian Fuel Gas Code takes precedence over these instructions. Specifically, all minimum distance require- ments with respect to termination of the vent piping listed below (items 1 through 8).

The following list is a summary of vent terminal location requirements:

1.The termination must be 12 inches above snow level or grade level whichever is higher. See Figure 18 for alternate method to achieve 12" above snow level.

2.The minimum distance for a (1-pipe instal- lation) from any door, (openable) window, or gravity air inlet is 4 ft. below, 4 ft. horizon- tally, or 1 ft. above.

3.The minimum distance for a direct vent (2- pipe) installation) from any door, (openable) window, or air gravity inlet is 1 ft. below, 1 ft. horizontally, or 1 ft. above.

4.For one-pipe installations the recommended minimum distance from an inside corner formed by two exterior walls is 6 feet, but is not required.

Direct vent terminal 50,000 Btuh or less

9 in.

12

in.

4 ft. min

 

 

 

 

 

 

ft.

 

 

min

 

4

min

 

 

 

 

 

 

 

 

 

 

Mechanical

12

in.

 

 

 

 

 

 

 

draft vent

 

 

 

min

 

 

 

 

 

terminal

Mechanical

 

Mechanical

 

draft vent

draft vent

 

 

terminal

terminal

 

 

 

 

 

 

 

 

Less

 

 

 

than 10 ft.

 

.min

 

3 ft. min.

in

 

12

 

 

 

 

 

 

Grade

.min

 

Forced

in

 

Air Inlet

12

.min

 

 

12

in

Direct vent

 

terminal -

 

 

more than 50,000 Btuh

Figure 17. Vent Termination Clearances

18

Image 18
Contents Installation Instructions What to do if YOU Smell GASPage Table of Contents Dimensions Upflow G6RC & G6RD FurnacesDownflow G6RL Furnace Furnace Airflow Data High 1910 1860 1780 1700 1620 1520 1420Model Input Motor Number Btuh Speed Installation Requirements Requirements and Codes Clearances to Combustible MaterialsLocation Horizontal InstallationsSupply AIR Plenum Installation Downflow Warning G6RL ModelsCirculating AIR Supply Furnace on a Concrete SlabReturn Air Venting and Combustion AIR RequirementsMinimum Free Area40,000 100 sq. 60,000 80,000 Installation In a Confined Space Air Requirements For One-Pipe InstallationInstallation In An Unconfined Space Air From InsideVent Pipe Length and Diameter Venting RequirementsVent Pipe Material Air Directly Through An Exterior WallExample Vent Pipe InstallationSolution Pipe Routing and SupportG6RC & G6RD Upflow Furnaces G6RL Downflow FurnacesG6RL Downflow Furnaces G6RC & G6RD UpflowFurnaces G6RC & G6RD Upflow FurnacesLocation of Outdoor Terminations Vent Termination ClearancesAlternate Horizontal Vent Installation Horizontal VentingVertical Venting Vent Freezing ProtectionConcentric Vent Termination Drainage of Condensate from Furnace Vertical Vent TerminationGAS Supply and Piping Leak CheckNatural Gas High Altitude Conversion ConversionHigh Altitude Application LP/Propane Gas Sea Level and High Altitude ConversionElectrical Wiring Line Voltage WiringFurnace Rating Orifice Drill Size Plate Input Btu/h Nat START-UP and AdjustmentsLow Voltage Wiring Above Sea LevelStart-Up Procedure Verifying and Adjusting Firing RateElectrical Data Verifying and Adjusting Temperature Rise Verifying Burner OperationGAS Flow Rate Cubic Feet PER Hour Gas Flow RateVerifying Operation of the Supply Air Limit Switch Description of ComponentsG6RC, G6RD and G6RL Integrated Control Board System Diagram For G6RC, G6RD and G6RL Residential FurnacesMaintenance System Operation InformationG6RL Downflow Furnace Location of Major ComponentsHeating Mode Cooling ModeSequence of Operation Fan Mode Furnace Fails to OperateTwinning of Two Furnaces INSTALLATION/PERFORMANCE Check List Fuel Type¢707931*¤